3-6-3 Modifying Today's Schedule
Click the menu item [Schedule Settings], or click [Today’s Schedule] in the sub menu to display the Today’s
Schedule setting screen. Today’s Schedule can be used to set a valid schedule for just the current day without
modifying the weekly or annual schedule.
To set Today’s Schedule, first select the range and object of the setting and then set the contents of the
schedule.
Note: When the contents of an operation are executed as part of a schedule these contents will continue to be in effect until they
are changed by a schedule or browser etc. Therefore, if you are setting a schedule that is only for a particular day, be sure
to set your schedule in a way that will not impact on the next day’s operation.
For example, if you wish to prohibit operations being performed from the remote controller after 17:00, set a Prohibit
operation for 17:00 and set an Enable operation for 23:59.
(1) Select the target for the schedule being set
Follow the procedure outlined for the weekly schedule (see 3-6-1) to select the range and object of the
schedule setting.
(2) Set the contents of the schedule setting
When one of the [Edit] buttons in the Contents of Schedule box is
clicked, a screen to set a schedule operation will appear. Use this
screen to set when to run an operation and set the type of schedule
operation (ON/OFF, operation mode, temperature setting, prohibit
remote controller operation) and then press the [OK] button.
It is also possible to set a schedule operation that is only an operation
mode or temperature setting modification. To do this, simply limit your
setting to the particular details you want to change.
The upper/lower limit temperatures must be set to operate the unit in
the Setback mode.
Note: When setting a schedule for all groups or for a block, it is possible to set
all operation modes such as Auto mode etc, but if some targeted air
conditioner units do not have such a function, then those units will not
run in the specified mode. When setting the schedule, consider what
functions are supported by the air conditioner units.
Note: When setting a schedule for all groups or for a block, it is possible to set prohibit remote controller items individually. When
allowing remote
Note: When setting a schedule for ventilator units, the temperature setting is not displayed.
Moreover, the prohibit remote controller operation is simply [ON/OFF].
Note: Only the ON/OFF operation is possible on the general equipment.
OK Button
Setting Range
Select the range that
scheduling will be set for.
Block Name
Select the block to be set.
Group Name
Select the group to be set.
Group Numbe
r
Select the group to be set.
Undo button
Click to undo the changed
Contents of Schedule
Operations set for the schedule
are displayed here.
Edit button
Click to set a schedule
operation.
Delete button
Click to delete a schedule
operation.
Save Settings button
Click to save the contents of the
schedule setting. The schedule
settings will not be saved unless
this button is pressed.
Copy (Group) / Paste
Click to copy or paste a
schedule between groups.
Page view 25