CNTR-11CONTROLLER
CONTROLLER
3. System controller
3. System remote controller
DATA U3
CONTROLLER Cntr- 12
3-2. Schedule timer [PAC-YT34STA]
ON/OFF
MONITOR
WEEKLY SET
COLLECTIVE
PATTERN
Sun Mon TueWed Thu Fri Sat
OPERATION
GROUP
CHECK
SET TEMP.
ON/OFF
MODE
TEMP.
ON
TIMER OFF
PROH. PERMIT
ON
OFF
The weekly schedule of up to 50 groups/50 units
can be controlled with one schedule timer.
The weekly schedule of up to ten patterns (no set-
ting + nine patterns) is available for setting.
"ON/OFF", "Operation Prohibit", "COOL /HEAT"
and "Set Temperature" can be scheduled with up
to 16 settings in one pattern.
It can be connected to the central control trans-
mission line or to the indoor/outdoor transmission
line without the power supply unit. It is non-polar
2-wire.
It can be interlocked with a building management
system using the external input/output managing
function.
An error unit address and error code appear on
the display in case of malfunction happening.
Unit control
Schedule control
Operation
Schedule
function
Display
External input
(Timer connection,
emergency stop
input, etc.)
External output
(Error output,
operation output)
Connection position
ON/OFF
Setting
details
Number of
settings
Time setting unit
Timer reset
Item
Operations
Display
50 units/50 groups (Maximum 16 units connected in one group)
Details
One week
ON/OFF operations can be carried out collectively or for each
group.
ON/OFF
COOL/HEAT
Operation prohibit (ON/OFF, operation mode, setting temperature)
Number of setting patterns: Ten (no setting + nine patterns)
(Operation for a week can be set by selecting one of ten
patterns for each day.)
Number of operations: Up to 16 operations can be set in one pattern
The following can be input with the level signals or pulse signals.
Level signal: "Emergency stop input" or "Collective ON/OFF"
Pulse signal: "Collective ON/OFF" or "Local remote controller
prohibit/permit"
One input can be selected from those above.
"ON/OFF" and "error/normal" are output with the level signal.
The optional output cable is required.
Indoor/outdoor transmission line: Connectable
Central system transmission line: Connectable (Optional power
supply unit (PAC-SC50KUA) is needed.)
The item can be set in five-minute units
Current time and day
Error state
Unit operation state
The timer setting details can be disabled collectively
Functions
: Each unit
: Group or collective
: Each block: Each group
: Each floor : Not available