8-3. TEST POINT DIAGRAM
8-3-1. Indoor controller board
PKFY-P32VHM-E PKFY-P32VHM-ER1
PKFY-P40VHM-E PKFY-P40VHM-ER1
PKFY-P50VHM-E PKFY-P50VHM-ER1
CN3A
Connected to the termial
block (TB15)
(MA-Remote controller
connecting wire)
1 - 3 : 8.7-13V DC
(Pin1 (+))
CN44
Pipe temperature thermistor
1-2 : Liquid (TH22)
3-4 : Gas1 (TH23)
SW4
Model selection
CND
Power supply for
indoor controller board
1-3 : 220-240AC
SW2
Capacity setting
LED1
Main power supply
(Indoor unit :
220-240V)
CN20
Room temperature
thermistor (TH21)
LED2
Power supply for
MA-Remote controller
CN32
Remote switch
Jumper wire J41, J42
Pair No. setting for wireless
remote controller
LDSWE(A)
Connect to the
wireless remote
controller board
(S.B)
CN2M
Connect to the
terminal block (TB5)
(M-NET transmission
connecting wire)
24-30VDC (non-polar)
Power supply from
outdoor unit
SW3
Function setting
CN2G
Pipe temperature
thermistor
Gas2 (TH24)
CN4F
Drain float switch
(FS)
CN51
Centrally control-
led
CN60
Liner expansion
valve (LEV) output
12VDC pluse output
CN52
Remote indicator
CNRU
Connect to the
wireless remote
controller board
(W.B)
CN151
Vane motor output
12VDC pluse
CNP
Drain pump output
(DP)
1-3 : 220-240AC
FUSE
3.15A 250V
CNMF
Connect to the fan motor (MF)
1-3 : DC310~340V
4-3 : DC15V
5-3 : DC0~6V
6-3 : DC0 or DC15V (Stop)
DC7.5V (Operation)
(12VDC pluse)
LD SWE (B)
Connect to the indoor
controller board (I.B)
Page view 18