5. Confirmation of parts attached
This unit includes the following parts. Please check.
For usage methods, refer to item 10.2.
6. Space required around unit
1 In case of single installation
Secure enough space around the unit as shown in the figure on page 2.
[Fig. 6.0.1] (P.2)
<A> Top view <B> Side view
<C> When there is little space up to an obstruction
A Front B Unit height
C Back D Air outlet guide (Procured at the site)
(1) If the distance is 300 mm or more between the rear side and the wall
(2) If the distance is 100 mm or more between the rear side and the wall
(3) If the wall height (H) of the front, rear or side exceeds the wall height
restriction
When the height of the walls on the front, back or on the sides <H> exceeds
the wall height limit as defined here, add the height that exceeds the height
limit <h> to the figures that are marked with an asterisk.
<Wall height limit> Front: Up to the unit height
Back: Up to 500 mm from the unit bottom
Side: Up to the unit height
(4) If there are obstacles at the upper part of the unit
2 In case of collective installation
[Fig. 6.0.2] (P.2)
A Front B Must be open
C Wall height (H)
When multiple units are installed adjacent to each other, secure enough space
to allow for air circulation and walkway between groups of units as shown in
the figures on page 2.
At least two sides must be left open.
As with the single installation, add the height that exceeds the height limit <h>
to the figures that are marked with an asterisk.
If there is a wall at both the front and the rear of the unit, install up to 6 units
consecutively in the side direction and provide a space of 1000 mm or more as
inlet space/passage space for each 6 units.
7. Lifting method
[Fig. 7.0.1] (P.2)
Use suspension ropes that will withstand the weight of the unit.
When moving the unit, use a 4-point suspension, and avoid giving impacts to
the unit (Do not use 2-point suspension).
Place protective pads on the unit where it comes in contact with the ropes to
protect the unit from being scratched.
Set the angle of roping at 40° or less.
Use 2 ropes that are each longer than 8 meters.
Place protective padding at the corners of the product to protect the product
from scratches or dents that might be caused by the rope.
Caution:
Be very careful when carrying/moving the product.
- When installing the outdoor unit, suspend the unit at the specified location of the
unit base. Stabilize as necessary so that it does not move to the side and support
it at 4 points. If the unit is installed or suspended with 3-point support, the unit
may become unstable and fall.
RP200
RP250
RP300
RP350
1 Connecting elbow
ID
ø
25.4 , OD
ø
25.4
<gas side>
1 pc.
1 pc.
1 pc.
1 pc.
2 Connecting pipe
ID
ø
9.52, OD
ø
12.7
<Liquid side>
1 pc.
1 pc.
1 pc.
3 Connecting pipe
ID
ø
12.7 , OD
ø
15.88
<Liquid side>
1 pc.
7 Connecting pipe
ID
ø
25.4 , OD
ø
34.93
<gas side>
1 pc.
4 Connecting pipe
ID
ø
25.4 , OD
ø
19.05
<gas side>
1 pc.
RP200
RP250
RP300
RP350
5 Connecting pipe
ID
ø
25.4 , OD
ø
22.2
<gas side>
1 pc.
1 pc.
6 Connecting pipe
ID
ø
25.4 , OD
ø
28.58
<gas side>
1 pc.
1 pc.
1 pc.
1 pc.
8 Connecting pipe
ID
ø
9.52, OD
ø
9.52
<Liquid side>
1 pc.
1 pc.
1 pc.
9 Connecting pipe
ID
ø
12.7 , OD
ø
12.7
<Liquid side>
1 pc.
Model
Model
WT06215X01_en_e.p65 10.12.17, 13:5413