TRANSISTORIZED INVERTERINSTRUCTION MANUALIB(NA)-66807-C(0212) MDOC Printed in Japan Specifications subject to change without notice.HEAD OFFICE:MITSUB
1.1 OverviewPRE-OPERATION INFORMATION11 PRE-OPERATION INFORMATION1.1 Overview1.1.1 Appearance and parts identificationUnpack the parameter unit from
PRE-OPERATION INFORMATION2Key DescriptionWRITE key• Used to write a set value in the setting mode.• Used as a clear key in the all parameter clear or
1.2 Installation and RemovalPRE-OPERATION INFORMATION31.2 Installation and RemovalTo ensure safety, install and remove the parameter unit after switc
PRE-OPERATION INFORMATION4 When connecting to the FR-S500/ F500J/ C500 series.1) Remove the front cover.2) Insert the cable plugs securely into the c
1.3 Parameters to Be Checked FirstPRE-OPERATION INFORMATION51.3 Parameters to Be Checked FirstChange the following parameter settings as required.For
This chapter describes the "functions" for use of thisproduct.Always read the instructions before using the equipment.2.1 Monitoring Functio
2.1 Monitoring FunctionFUNCTIONS62 FUNCTIONS2.1 Monitoring Function2.1.1 Display overview120.00OLHzSTF FWD PU(2) PU level meter(1) Main monito
FUNCTIONS7(5) Operation mode indicationDisplays the status of the operation mode.EXT : External operation modePU : PU operation modeEXTj : External jo
FUNCTIONS82.1.2 Using the SHIFT key to change the main screenWhen "0" (factory setting) is set in Pr. 52 "PU main display data selectio
FUNCTIONS92.1.4 Using the HELP key to change the main screenA500 F500 -NA -EC -CHE500 -NA -EC -CHS500 -CHF500J C500CAUTIONThe functions vary with
A - 1Thank you for choosing the Mitsubishi transistorized inverter option unit.This instruction manual gives handling information and precautions for
FUNCTIONS10 When "current monitor" or "power monitor" is selectedNote that any current or power not more than 5% of the rated inve
2.2 Frequency SettingFUNCTIONS112.2 Frequency SettingMake this setting in the PU operation mode.REMARKSThe external start signal (STF or STR) must not
FUNCTIONS122.2.3 Precautions for frequency setting1) Pr. 79 "operation mode selection" must have been set to make the "PU operationmode
2.3 Setting and Changing the Parameter ValuesFUNCTIONS132.3 Setting and Changing the Parameter ValuesThe inverter has a number of parameters. Using th
FUNCTIONS14POINTSet and/or change the parameter values in the PU operation mode. When the PUoperation indication is not shown, refer to page 54 and sw
FUNCTIONS152.3.3 Function-by-function parameter settingA500 F500 -NA -EC -CHE500 -NA -EC -CHS500 -CHF500J C500You can set and/or change only the p
FUNCTIONS162.3.4 User parameter registration and deletionA500 F500 -NA -EC -CHE500 -NA -EC -CHS500 -CHF500J C500Among all parameters, a total of 3
FUNCTIONS17(2) Registration1) Press SET key.The parameter unit is put in the parameter settingmode.SETTING MODESet Pr. NOPr. Pr. List COPYHELP2)
FUNCTIONS18(3) Deletion1) Press SET key.The parameter unit is put in the setting mode.SETTING MODESet Pr. NOPr. Pr. List COPYHELP2) Press READ k
2.4 Calibration of the Meter (Frequency Meter)FUNCTIONS192.4 Calibration of the Meter (Frequency Meter)CAUTIONThe functions vary with the inverter. (R
A - 2 SAFETY INSTRUCTIONS1. Electric Shock Prevention WARNING! Do not run the inverter with the front cover removed. Otherwise, you may accessexposed
FUNCTIONS202.4.2 Calibration of the AM terminalA500 F500 -NA -EC -CHE500 -NA -EC -CHS500 -CHF500J C500 This section provides a way to calibrate th
FUNCTIONS21 Calibration procedure 2 (Example: Output current)To output the output current or another item which cannot easily achieve a 100% valueif o
FUNCTIONS229) Press the SET key.The parameter unit is put in theparameter setting mode.SETTING MODESet <HELP>FOR PR. ListPr. NO.10) Type 1
2.5 Adjustment of the frequency setting signals "bias" and "gain"FUNCTIONS232.5 Adjustment of the frequency setting signals "
FUNCTIONS24(1) Adjust only the bias and gain frequencies and not adjust the voltage Setting of the frequency setting voltage bias1) Press the PU key.T
FUNCTIONS25 Setting of the frequency setting voltage gain7) Press the SHIFT key.The current Pr. 903 setting appears.Set 903 EXTVgain 60.00H
FUNCTIONS26(2) Any point is adjusted with a voltage applied across terminals 2-5 Setting of the frequency setting voltage bias1) Press the PU key.The
FUNCTIONS27(From the preceding page) Setting of the frequency setting voltage gain9) Press the SHIFT key, then theREAD key.The current Pr. 903 setting
FUNCTIONS28(3) Any point is adjusted without a voltage applied across terminals 2-5 Setting of the frequency setting voltage bias1) Press the PU key.T
FUNCTIONS29(From the preceding page) Setting of the frequency setting voltage gain9) Press the SHIFT key, then theREAD key.The current Pr. 903 setting
A - 3(2) Test operation and adjustment CAUTION! Before starting operation, confirm and adjust the parameters. A failure to do somay cause some machine
2.6 Copy and Verify FunctionsFUNCTIONS302.6 Copy and Verify Functions2.6.1 Copying the parameter settingsYou can read and store parameter settings int
FUNCTIONS312.6.2 Verifying the parameters Verify1) Connect the FR-PU04 to the inverter.2) Press the SET key. This selects the setting mode.SETTING MOD
This chapter explains the HELP key in the use of thisproduct.Always read the instructions before using the equipment.3.1 Overview of the Help Function
3.1 Overview of the Help FunctionsH E L P323 HELP3.1 Overview of the Help FunctionsPress the HELP key twice in any operation mode to call the help fun
H E L P333.1.2 Help function display dataCAUTIONThe functions vary with the inverter. keyHELPPress 1 MONITOR 2 PU Oper 3 Pr. List 4 Pr. Clear 5 A
H E L P34 1 Clear Pr. 2 Clear All 3 Clear User 4 Clear NonekeyPress twice. Clear Pr.ExecutingExec <Write>Cancel<ESC>Clear Pr.
H E L P35<S/W> 1 M.Not Run 2 M.Spd Error 3 M.A/Dec Err 4 M.Curr.HighM.NOT RUNNINGMRS is ONM.SPEED ERRORSetF>MaxF1/F2 60. 00 HzPr1/18Stll P
3.2 Operation Procedures for the Help FunctionsH E L P363.2 Operation Procedures for the Help FunctionsCAUTIONThe functions vary with the inverter.3.2
H E L P37 To call the monitoring list directly in the monitoring mode1) Press the MON key.The parameter unit is put in the monitoring mode.(You need n
H E L P383.2.2 Selection of PU operation (direct input)You can select the PU operation mode via direct input (direct setting from the ten digitskey pa
- CONTENTS -I1 PRE-OPERATION INFORMATION 11.1 Overview ...
H E L P393.2.3 Selection of the PU jog operation modeA500 F500 -NA -EC -CHE500 -NA -EC -CHS500 -CHF500J C500(1) Calling from the help function men
H E L P403.2.4 ParametersThe parameter menu is displayed and you can select and perform any of the followingoperations: Setting:...
H E L P41(1) "2 Pr. List"1) Refer to page 40 and call the parameter menu. 1 SettingMODE 2 Pr. List 3 Set Pr. List 4 Def. Pr. List2)
H E L P42(2) Display of "3 Set Pr. List"A500 F500 -NA -EC -CHE500 -NA -EC -CHS500 -CHF500J C500 When the parameter setting has been chan
H E L P433.2.5 Parameter ClearThe parameter clear menu appears and you can select and perform any of thefollowing four operations:Switch to the PU ope
H E L P443.2.6 Alarm HistoryShows the history of eight past alarms. (*1)1) Press the HELP key twice in the operation mode.The help function menu is ca
H E L P453.2.7 Alarm ClearClears all the alarm history.1) Press the HELP key twice in the operation mode.The help function menu is called. 1 MONITOR
H E L P463.2.8 Inverter ResetResets the inverter.1) Press the HELP key twice in the operation mode.The help function menu is called. 1 MONITOR 2 P
H E L P473.2.9 TroubleshootingA500 F500 -NA -EC -CHE500 -NA -EC -CHS500 -CHF500J C500If the inverter appears to operate improperly, perform the fo
H E L P48(1) Troubleshooting guidanceM. NOT RUNNING ALARM Indicated <SHIFT>1) M.NOT RUNNING (Motor does not run)The inverter has alarm-tri
II2.2 Frequency Setting ... 112.2.1 Direct setting ..
H E L P49M. SPEED ERROR SetF>MaxF1/F2 60. 00 Hz Pr1/18Since the running frequency setting is higher than the maximum frequency (Pr. 1) setti
H E L P504) M.Curr.HighInv. Output 60. 00Hz 10A 182. 4V <SHIFT>First, the running frequency,output current and output voltage of the inverter
H E L P513.2.10 SelectopA500 F500 -NA -EC -CHE500 -NA -EC -CHS500 -CHF500J C500Displays the signals assigned to the I/O terminals of the control c
H E L P523.2.11 OptionDisplays what options are fitted to the option connectors.1) Press the HELP key twice in the operation mode.The help function me
3.3 Other PrecautionsH E L P533.3 Other Precautions3.3.1 Precautions for parameter unit operationNote the following items when operating the parameter
This chapter explains the basic "operation" for use of thisproduct.Always read the instructions before using the equipment.4.1 Operation Mod
4.1 Operation ModesOPERATION544 OPERATION4.1 Operation Modes4.1.1 How to select the operation mode(1) Switching from external operation mode [EXT] to
OPERATION55REMARKSIf the operation mode cannot be switched properly, check the following:1. External input signal...(STF
4.2 PU OperationOPERATION564.2 PU OperationCAUTIONThe functions vary with the inverter. (Refer to the inverter instruction manual for details.)4.2.1 O
OPERATION574.2.2 PU jog operationA500 F500 -NA -EC -CHE500 -NA -EC -CHS500 -CHF500J C500Hold down the FWD or REV key to perform operation, and rel
III3.2.1 Monitor function... 363.2.2 Selection of PU o
4.3 Combined Operation (Operation using external input signals and PU)OPERATION584.3 Combined Operation (Operation using external input signals and PU
OPERATION594.3.2 Entering the running frequency from outside and making startand stop from the PU (Pr. 79 = 4)Step Operation Procedure Image1 Switch t
OPERATION604.3.3 Entering the start signal and multi-speed signal from outsideand setting multiple speeds from the PUStep Operation Procedure Image1 S
This chapter provides the "specifications" for use of thisproduct.Always read the instructions before using the equipment.5.1 Specifications
5.1 SpecificationsSPECIFICATIONS615 SPECIFICATION5.1 Specifications5.1.1 Standard specificationsItem SpecificationsAmbient temperature -10°C to +50°C
SPECIFICATIONS625.1.2 Outline drawing125 (4.92)72 (2.83)(0.59)(0.41)18.540 (1.57)80 (3.15)2413 (0.51)2021.5(0.85)14.548 (1.89)(0.97)(0.79)(0.73)(0.57)
REVISIONS*The manual number is given on the bottom left of the back cover.Print Date*Manual NumberRevisionOct., 1997 IB(NA)-066807-A First editionMar.
IV4.2.1 Ordinary operation....... 564.2.2 PU jog operation A50
This chapter provides the basic "pre-operation information(overview)" for use of this product.Always read the instructions before using the