External Device Settings
Use the PU/EXT key, MODE key, M dial and SET key in the operation panel of the CPU unit for External Device
communication settings.
Refer to your External Device manual for details.
1 Turn ON the power supply.
2 Press PU/EXT key to select the PU operation mode.
3 Press MODE key to select the parameter setting mode.
4 Display the setting parameter number with M dial.
5 Press SET key to display the current setting value.
6 Set the setting value with M dial.
7 Press SET key to confirm the setting value.
Setting Parameter Number Setting Value Setup Description
117 0 PU communication station number
118 192 PU communication speed
119 1 PU communication stop bit length
120 2 PU communication parity check
121 1 Number of PU communication retries
122 Any Except 0 PU communication check time interval
123 9999 PU communication waiting time setting
124 1 PU communication CR/LF selection
549 0 Protocol selection
Always restart the Eternal Device after changing parameters.