WALL-MOUNTED Inverter Heat Pump
M series
TROUBLESHOOTING
WALL-
MOUNTED
C-157
Indoor unit failure mode table
w OPERATION INDICATOR lamp
POWER lamp (
MSZ-FD)
Upper lamp (
MSZ-GE, MSZ-HC)
Left lamp (
MSZ-SF)
NOTE : Blinking patterns of this mode differ from the ones of "Troubleshooting check table".
12-time flash
2.5-second OFF
Indoor control system
It cannot properly read data in the
nonvolatile memory of the indoor electronic
control P.C. board.
11-time flash
2.5-second OFF
Indoor fan motor
The rotational frequency feedback signal is
not emitted for 12 seconds after indoor fan
motor is operated.
2-time flash
2.5-second OFF
Indoor coil thermistor
The indoor coil thermistor short or open
circuit is detected every 8 seconds during
operation.
3-time flash
2.5-second OFF
Serial signal
The serial signal from outdoor unit is
not received for 6 minutes.
1-time flash
every 0.5-second
Room temperature
thermistor
The room temperature thermistor short
or open circuit is detected every 8 seconds
during operation.
Not lighted Normal —
POWER/Upper/Left lamp of
OPERATION INDICATOR lamp
Abnormal point
(Failure mode)
Condition
PLASMA operation failure mode table
5-time flash
The voltage between CN1 (+) and (GND)
on the PLASMA POWER P.C board rises
above the normal voltage value (3 V).
4-time flash
PLASMA DEODORIZING
The voltage between CN1 (+) and (GND)
on the PLASMA POWER P.C.board falls
significantly. (0.4 V / 0.5 ms)
3-time flash
Abnormal electric
discharge error 1
The voltage between CN1 (+) and (GND)
on the PLASMA POWER P.C.board falls by
0.9 V below the normal voltage value (3 V).
2-time flash Spark discharge
1-time flash
PLASMA power supply
control
The voltage between CN1 (+) and (GND)
on the PLASMA POWER P.C.board falls
below 1.6 V(spark discharge judgment
voltage).
PLASMA power supply cannot be turned
OFF even if the PLASMA operation is turned
OFF with the remote controller.
POWER lamp
Abnormal point
(Failure mode)
Condition
Abnormal electric
discharge error 2
NOTE1 : Blinking patterns of this mode differ from the ones of "Troubleshooting check table".
NOTE2 : As soon as an abnormality is detected, PLASMA operation goes OFF, therefore measuring
instrument which records the voltage wave is required in order to perform the above mentioned voltage
measurement.
NOTE3 : When POWER lamp flashes 1-time or 2-time, please perform PLASMA operation check.
MSZ-FD25VA
MSZ-FD25VAS
MSZ-FD35VA
MSZ-FD35VAS
MSZ-FD50VA
MSZ-FD50VAS
MSZ-FD25VA MSZ-GE22VA MSZ-GE60VA MSZ-HC25VA MSZ-SF15VA
MSZ-FD25VAS MSZ-GE25VA MSZ-GE71VA MSZ-HC35VA MSZ-SF20VA
MSZ-FD35VA MSZ-GE35VA MSZ-HC35VAB
MSZ-FD35VAS MSZ-GE42VA
MSZ-FD50VA MSZ-GE50VA
MSZ-FD50VAS