OPERATING PROCEDURE PHOTOS
Photo 13
Photo 14
Compressor
(MC)
Valve bed
Separator
Separator
fixing screw
Compressor
fixing nut
Power receiver
Power receiver
Outlet
Inlet
12. Removing the compressor (MC)
(1) Remove the service panel. (See Photo 2)
(2) Remove the top panel. (See Photo 1)
(3) Remove the front panel. (See Photo 1)
(4) Remove the back panel. (See Photo 1)
(5) Remove the electrical parts box. (See Photo 5)
(6) Remove the thermistor <Discharge> (TH4) and thermistor
<Comp. surface> (TH34). (See Photo 13)
(7) Remove 3 separator fixing screws (4 × 10) and remove the
separator.
(8) Recover refrigerant.
(9) Remove 3 compressor fixing nuts by using a spanner or an
adjustable wrench.
(10) Remove the welded pipe of motor for compressor inlet
and outlet.
Note: Recover refrigerant without spreading it in the air.
Receiver leg
fixing screw
Receiver leg
13. Removing the power receiver
(1) Remove the service panel. (See Photo 2)
(2) Remove the top panel. (See Photo 1)
(3) Remove the front panel. (See Photo 1)
(4) Remove the back panel. (See Photo 1)
(5) Remove the electrical parts box. (See Photo 5)
(6) Recover refrigerant.
(7) Remove 4 welded pipes of power receiver inlet and outlet.
(8) Remove 2 receiver leg fixing screws (4 × 10).
(9) Remove the power receiver together with the receiver leg.
Note: Recover refrigerant without spreading it in the air.
Thermistor
<Comp.surface> (TH34)
Thermistor<Discharge>
(TH4)