USER’S MANUALCC-Link INTERFACE BLOCK FX2N-32CCL

Page 2

FX2N-32CCL CC-Link Interface Block Introduction 11-2Transmission speedTransmission distance10 Mbps : 100 m5 Mbps : 150 m2.5 Mbps : 200 m625 kbps : 600

Page 3

FX2N-32CCL CC-Link Interface Block Introduction 11-31.2 Connection to CC-LinkThe FX PC connected with the interface block FX2N-32CCL functions as a re

Page 4

FX2N-32CCL CC-Link Interface Block Introduction 11-41.3 System configuration of entire CC-LinkThe figure below shows the system configuration of the e

Page 5

FX2N-32CCL CC-Link Interface Block Specifications 22-12. Product SpecificationsCautions on design• For the status of each station in the case in which

Page 6

FX2N-32CCL CC-Link Interface Block Specifications 22-22.1 Outside dimensions and nomenclatureOuter paint color: Munsell 0.08GY/7.64/0.81 Weigh

Page 7 - CONTENTS

FX2N-32CCL CC-Link Interface Block Specifications 22-32.2 General specifications and performance specificationsGeneral specificationsDielectric streng

Page 8 - Contents

FX2N-32CCL CC-Link Interface Block Specifications 22-4Transmission speed156 kbps, 625 kbps, 2.5 Mbps, 5 Mbps, 10 Mbps (set by rotary switch)Maximum tr

Page 9 - 1. Introduction

FX2N-32CCL CC-Link Interface Block Specifications 22-5Operation indicationLEDs (POWER, L RUN, L ERR, RD, SD)Number of occupiedI/O pointsEight I/O poin

Page 10

FX2N-32CCL CC-Link Interface Block Specifications 22-6Memo

Page 11 - 1.2 Connection to CC-Link

FX2N-32CCL CC-Link Interface Block Connection and Wiring 33-13. Connection and Wiring3.1 Connection to PCConnection of extension cableThe FX2N-32CCL c

Page 12

FX2N-32CCL CC-Link Interface BlockForeword• This manual contains text, diagrams and explanations which will guide the reader in the correct installati

Page 13 - 2. Product Specifications

FX2N-32CCL CC-Link Interface Block Connection and Wiring 33-23.2 Wiring of power supplyWiringHandling of crimp-style terminal• Use crimp-style termina

Page 14 - 80(3.15)

FX2N-32CCL CC-Link Interface Block Connection and Wiring 33-3• Handle the crimp terminal of the following size when 2 wires are used per terminal.6.2

Page 15

FX2N-32CCL CC-Link Interface Block Connection and Wiring 33-43.3 Wiring of CC-LinkSpecifications of twisted pair cableThis paragraph describes a recom

Page 16 - Maximum transmission distance

FX2N-32CCL CC-Link Interface Block Connection and Wiring 33-5Wiring of twisted pair cableWire the FX2N-32CCL and the CC-Link using shielded twisted pa

Page 17

FX2N-32CCL CC-Link Interface Block Setting of Remote Device Stations 44-14. Setting of Remote Device Stations4.1 Setting of station Nos., number of st

Page 18

FX2N-32CCL CC-Link Interface Block Setting of Remote Device Stations 44-2B RATE0512349876Numerics 0 to 4 correspond to 156 kbps to10Mbps respectively

Page 19 - 3. Connection and Wiring

FX2N-32CCL CC-Link Interface Block Setting of Remote Device Stations 44-34.2 List of number of remote points and remote Nos.In the FX2N-32CCL, the num

Page 20

FX2N-32CCL CC-Link Interface Block Assignment of Buffer Memory (BFM) 55-15. Assignment of Buffer Memory (BFM)5.1 Outline of data communicationThe inte

Page 21

FX2N-32CCL CC-Link Interface Block Assignment of Buffer Memory (BFM) 55-25.2 BFM dedicated to readMaster station → FX Buffer memory dedicated t

Page 22 - 3.3 Wiring of CC-Link

FX2N-32CCL CC-Link Interface Block Assignment of Buffer Memory (BFM) 55-3Details of buffer memory[BFM #0 to #7 (remote output RY00 to RY7F)]• Sixteen

Page 23 - Shielded twisted

FX2N-32CCL CC-Link Interface BlockiFX2N-32CCL CC-Link INTERFACE BLOCKThis manual confers no industrial property rights or any rights of any other kind

Page 24

FX2N-32CCL CC-Link Interface Block Assignment of Buffer Memory (BFM) 55-4Example in which the ON/OFF status of multiple BFM points are read to the FX

Page 25

FX2N-32CCL CC-Link Interface Block Assignment of Buffer Memory (BFM) 55-5[BFM #8 to #23 (remote register RWw0 to RWwF)]• To each buffer memory No., a

Page 26

FX2N-32CCL CC-Link Interface Block Assignment of Buffer Memory (BFM) 55-6[BFM #24 (set value of baud rate)]The setting of the baud rate (transmission

Page 27

FX2N-32CCL CC-Link Interface Block Assignment of Buffer Memory (BFM) 55-7[BFM #26 (CC-Link model code)]The model code is saved in the following format

Page 28 - 5.2 BFM dedicated to read

FX2N-32CCL CC-Link Interface Block Assignment of Buffer Memory (BFM) 55-8[BFM #29 (error code)]The contents of an error are saved as the ON/OFF inform

Page 29

FX2N-32CCL CC-Link Interface Block Assignment of Buffer Memory (BFM) 55-95.3 BFM dedicated to writeFX → master station Buffer memory dedicated t

Page 30 - (1 to 8) is

FX2N-32CCL CC-Link Interface Block Assignment of Buffer Memory (BFM) 55-10Details of buffer memory[BFM #0 to #7 (remote input RX00 to RX7F)]• Sixteen

Page 31

FX2N-32CCL CC-Link Interface Block Assignment of Buffer Memory (BFM) 55-11Example in which the ON/OFF status of the FX PC is written to multiple BFM p

Page 32

FX2N-32CCL CC-Link Interface Block Assignment of Buffer Memory (BFM) 55-12[BFM #8 to #23 (remote register RWr0 to RWrF)]• To each buffer memory No., a

Page 33

FX2N-32CCL CC-Link Interface Block Assignment of Buffer Memory (BFM) 55-135.4 System area of remote I/OAs to the number of remote I/O points (RX00 to

Page 34

FX2N-32CCL CC-Link Interface BlockiiGuidelines for the safety of the user and protection of the FX2N-32CCL CC-Link Interface BlockThis manual provides

Page 35 - 5.3 BFM dedicated to write

FX2N-32CCL CC-Link Interface Block Assignment of Buffer Memory (BFM) 55-145.5 Contents of errorsThe table below shows the contents of errors indicated

Page 36

FX2N-32CCL CC-Link Interface Block Programming Examples 66-16. Programming Examples6.1 System configurationA sample program is explained in the system

Page 37

FX2N-32CCL CC-Link Interface Block Programming Examples 66-2Preparation1 ) Set the station No. set switch, the mode set switch, the transmission set s

Page 38

FX2N-32CCL CC-Link Interface Block Programming Examples 66-36.2 Flow of communication dataRemote input (RX), remote output (RY)In a sample program, co

Page 39 - 5.4 System area of remote I/O

FX2N-32CCL CC-Link Interface Block Programming Examples 66-4Remote register (RWr, RWw)In a sample program, communication is performed in remote regist

Page 40 - 5.5 Contents of errors

FX2N-32CCL CC-Link Interface Block Programming Examples 66-56.3 Program in master PCWhen the PC CPU starts to run, data linking is automatically start

Page 41 - 6. Programming Examples

FX2N-32CCL CC-Link Interface Block Programming Examples 66-6M303X0000 X000FM9038Initial pulseM302SETY06SETY06RSTM303RSTK1D100H0668H0000FROMY06RSTX0006

Page 42

FX2N-32CCL CC-Link Interface Block Programming Examples 66-7Y0AX0000 X000FRegistrationcommandM305SETY0ARSTM305RSTK1D101H06B9H0000FROMY0ARSTX000AM304PL

Page 43

FX2N-32CCL CC-Link Interface Block Programming Examples 66-8During operation M301X0000 X000FM9038Initial pulseM300PLSY08SETY08RSTM301RSTK1D100H0668H00

Page 44 - Remote register (RWr, RWw)

FX2N-32CCL CC-Link Interface Block Programming Examples 66-9Program for communication with remote device stationX0000 X0001X000FFROM K1P10CALLH0680H00

Page 45 - 6.3 Program in master PC

FX2N-32CCL CC-Link Interface BlockiiiHardware warningsSoftware warnings1 ) Indicates that the identified danger WILL cause physical and property damag

Page 46

FX2N-32CCL CC-Link Interface Block Programming Examples 66-10RETFROM K4H00E8H0000 K4M900TO K4H0168H0000 K4M1000M9036FROM K8H02F0H0000 D700TO K8H01F0H0

Page 47

FX2N-32CCL CC-Link Interface Block Programming Examples 66-116.4 Program in FX PCWhen the PC starts to run, data linking is automatically started by t

Page 48 - During operation

FX2N-32CCL CC-Link Interface Block Programming Examples 66-12FNC78FROMK8K0K0 K4M300M7Read of remote outputBFM #7 to #0 (RY7F to RY00)→ M427 to M300Uti

Page 49

FX2N-32CCL CC-Link Interface Block Programming Examples 66-13Example of communication program in station No. 2The contents equivalent to those in the

Page 50

FX2N-32CCL CC-Link Interface Block Programming Examples 66-14Memo

Page 52

HEAD OFFICE: TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPANHIMEJI WORKS: 840, CHIYODA CHO, HIMEJI, JAPANJY992D71801E(MEE)Effectiv

Page 53

FX2N-32CCL CC-Link Interface Blockiv• Under no circumstances will Mitsubishi Electric be liable responsible for any consequential damagethat may arise

Page 54

FX2N-32CCL CC-Link Interface Block ContentsvCONTENTS1. Introduction ...

Page 55

FX2N-32CCL CC-Link Interface BlockContentsvi6. Programming Examples ......6-16.

Page 56

FX2N-32CCL CC-Link Interface Block Introduction 11-11. IntroductionThe CC-Link interface block FX2N-32CCL is an interface block which connects the FX0