Terminal connection diagram
3WIRING
3.1 Terminal connection diagram
zThree-phase 200V power input
zThree-phase 400V power input
NOTE
y
To prevent a malfunction caused by noise, separate the signal cables more than 10cm (3.93inch) from the power cables.
y After wiring, wire offcuts must not be left in the inverter.
Wire offcuts can cause an alarm, failure or malfunction. Always keep the inverter clean. When drilling mounting holes
in an enclosure etc., take care not to allow chips and other foreign matter to enter the inverter.
Earth
(Ground)
Motor
IM
Earth (Ground)
Three-phase
AC power
supply
MCCB MC
R/L1
P1 P/+
PR
N/-
S/L2
T/L3
U
V
W
Earth
(Ground)
*7 Brake resistor (FR-ABR, MRS, MYS type)
Install a thermal relay to prevent an
overheat and burnout of the brake resistor.
(The brake resistor can not be connected
to the FR-E720-008 and 015.)
*6 A brake transistor is not built-in to the
FR-E720-008 and 015.
Forward
rotation start
Reverse
rotation start
Middle
speed
High
speed
Low
speed
Output
stop
Reset
Control input signals (No voltage input allowed)
Contact input common
24VDC power supply
(Common for external power supply transistor)
STR
STF
RH
RM
RL
MRS
SD
PC
Relay output
Running
Frequency detection
Open collector output
Open collector output common
Sink/source common
FU
RUN
SE
A
B
C
AM
5
Frequency setting signals (Analog)
2 0 to 5VDC
10(+5V)
2
3
1
4 4 to 20mADC
Frequency
setting
potentiometer
1/2W1k
Terminal 4
input
(Current
input)
(+)
(-)
5(Analog common)
*5 It is recommended to use 2W1k
when the frequency setting signal
is changed frequently.
*5
Connector for
plug-in option connection
Option connector
*3 Terminal input specifications
can be changed by analog
input specifications
switchover (Pr. 73).
*2 When using terminals PC-
SD as a 24VDC power
supply, take care not to
short across terminals
PC-SD.
PU
connector
USB
connector
*1. DC reactor (FR-HEL)
When connecting a DC reactor, remove the
jumper across P1-P/+
Control circuit terminal
Main circuit terminal
Sink logic
Jumper
*1
*7
*6
*2
*3
*4
Terminal functions vary
with the input terminal
assignment (Pr. 178 to
Pr. 184)
Multi-speed selection
Terminal functions vary with
the output terminal assignment
(Pr. 190 and Pr. 191)
Terminal functions vary
by Pr. 192 A,B,C terminal
function selection
SINK
SOURCE
IV
*4
0 to 5VDC
(0 to 10VDC)
0 to 10VDC
*4 Terminal input
specifications can be
changed by analog input
specifications switchover
(Pr. 267). Set the
voltage/current input
switch in the "V" position
to select voltage input (0
to 5V/0 to10V) and "I"
(initial value) to select
current input (4 to 20mA).
Voltage/current
input switch
Main circuit
Control circuit
Standard control temirnal block
R
RES
Relay output
(Fault output)
Brake unit
(Option)
(+)
(-)
Analog signal output
(0 to 10VDC)
E700_NA_Guideline_ib0600333ENG.book 4ージ 2007年11月28日 水曜日 午前10時20分
Page view 6
1 2 3 4 5 6 7 8 9 10 11 12 ... 27 28

Comments to this Manuals

No comments