Mitsubishi Electric PAR-30MAA Installation Manual Page 16

  • Download
  • Add to my manuals
  • Print
  • Page
    / 38
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 15
T9901085-1-3 UK Page 16 of 38
TERMINAL
BLOCK
230v AC
RELAY
MITSUBISHI ELECTRIC
OUTDOOR UNIT
THERMOSCREENS HEAT PUMP AIR CURTAIN
L
L1 L2 L3 N
MAIN INTERFACE
BMS
CONTROL
FILTER
INDICATOR PCB
0
1
2
3
4
5
6
1~
0
2
3
4
5
6
1~
Fan motor 1
CONDENSATE ALARM
Closed Circuit = Alarm
(Compressor Stops)
BlackWhiteRed
IN1(2)
IN1(1)
IN2(2)
IN2(1)
Red
Black
CN105
15
CNX1 CNX4 CNX5
Fan
Control
Heater
Control
Black
Yellow
Brown
MITSUBISHI ELECTRIC
INTERFACE PCB
PAC-IF010B-E (v.H48<)
S1
S2
S3
N
Pink
Blue
Green/Yellow
K1
Wire link connector must
be removed from CNS2
Orange
1
S3
L3
L2
L1
21
11
22
24
12
14
S1 S2 S3
NL
K1
A2
A1
14NO
13NO
DEFROST
CYCLE
AUXILIARY
HEATER
White
Thermistor (TH5) - Factory fitted
Thermistor (Liquid) - Factory fitted
White
S2
pcb track
A1A2
CONTACTOR
CONTACTOR
Orange
Brown
Grey
Black
Brown
RC
230v AC electrical power for condensate pump (if required)
Cooling
On
Fan motor 2
(2m unit only)
For Weather Compensation or
Discharge Control, PAR-W21:
SW1-3, SW3-7, ON
For Inlet Air or Room Control,
PAR-30: SW1-2, 1-3, ON
All other dips- OFF
Dip Switch Settings:-
AB
Black
High
Low
Med
Fan
S
I
T
E
W
I
R
I
N
G
High
Low
Med
Fan
or wire in a Door-Switch:-
Door Open - Higher speed
Door Closed - Lower speed
MITSUBISHI ELECTRIC
PAR-W21MAA for
weather compensation,
or PAR-30MAA for inlet
air control
or wire in Thermoscreens 3-Speed Fan Switch
8
7
6
Carries
230v AC
5
4
3
2
1
High
Low
Med
Fan
wire link for
Medium Speed
fitted as standard
Door-Switch
2A - AC3, 230v AC
1
2
PL
Yellow
Violet
Violet
Violet
Violet
L
Red
Black
N
Electrical Supply for
Outdoor Unit
230V/1ph/50Hz
or 400V/3ph/50Hz
Plug connected prevents
cooling with Inlet Air & Room
Air Control. Remove plug from
CNX5 if using Cooling Mode
Thermistor (Discharge Air or Inlet Air) - Factory fitted
TOC
TOC
Defrost Heater
Thermal Trip
(x2 on 2m unit)
Red
Red
N
FUSE
TERM.
T 5A
FUSE
Red
Yellow
Red
not used
Black
Red
The air curtain is delivered
with the Defrost Cycle
Auxiliary Heater disabled.
230V/1ph/50Hz Electrical Supply
HP1000DXE = 0.8A
HP1500DXE = 1.2A
HP2000DXE = 1.4A
Blue (Neutral)
Brown (High)
Grey
Violet
Orange
Red (Low)
Blue (Neutral)
Brown (High)
Grey
Violet
Orange
Red (Low)
Blue
WIRING DIAGRAM 1 – HP MR SLIM HEAT PUMP AIR CURTAIN (No Defrost Cycle Heater – unit as supplied)