3 PURY-200·250YMF-C
Switch Function
Function according to switch operation Switch set timing
When off When on When off When on
SWU
SW1
SW2
SW3
SW4
1~2
1~8
9~10
1
2
3
4
5
6
7
8
9
10
1
2
3
4
5
6
7
8
9
10
1
2
3
Unit address setting
For self diagnosis/
operation monitoring
Centralized control switch
Deletion of connection
information.
Deletion of error history.
Disregard ambient air
sensor errors, liquid
overflow errors.
Forced defrosting
Defrost prohibited timer
SW3-2 Function valid/
invalid
Indoor unit test operation
Defrosting start tempera-
ture of TH7.
Defrosting end tempera-
ture of TH5.
Pump down operation
Target Td (High pressure)
at Heating
Models
Set on 51~100 with the dial switch.
LED monitering display
Centralized control not
connected.
Storing of refrigeration
system connection
information.
Errors valid.
Ordinary control
43 min.
SW3-2 Function invalid
Stop all indoor units.
6°C
8°C
Invalid
49˚C
Model 200
Centralized control
connected.
Deletion of refrigeration
system connection
information.
Deletion
Disregard errors.
Start forced defrosting.
90 min.
SW3-2 Function valid
All indoor units test
operation ON.
3°C
15°C
Valid
53˚C
Model 250
Before power is turned on.
During normal operation when power
is on.
Should be set on OFF.
Before power is turned on.
Before power is turned on.
During normal operation when power
is on.
During normal operation when power
is on.
During normal operation when power
is on. (Except during defrosting)
During normal operation when power
is on.
When SW3-1 is ON after power is
turned on.
During normal operation when power
is on.
During normal operation when power
is on. (Except during defrosting)
During compressor stop when power
is on.
During normal operation when power
is on.
When switching on the power.
During normal
operation when
power is on.
10 minutes or
more after
compressor
starts.
Note:
SWU1~2=00 when shipped from the factory. Other factory settings are indicated by shaded portions.
If the address is set from 01 to 50, it automatically becomes 100.