Mitsubishi Electric CITY MULTI P1016V-E Specifications Page 6

  • Download
  • Add to my manuals
  • Print
  • Page
    / 166
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 5
5
[2] Piping Machining
Use ester oil, ether oil or alkylbenzene (small amount) as the refrigerator oil to coat flares and flange connections.
Use only the necessary minimum quantity of oil !
Reason :
1. The refrigerator oil used for the equipment is highly hygroscopic and may introduce water inside.
Notes :
Introducing a great quantity of mineral oil into the refrigerant circuit may also cause a compressor failure.
Do not use oils other than ester oil, ether oil or alkylbenzene.