Check the resistance of fan motor. (Refer to
11-4.)
Is the resistance of
fan motor normal?
Replace the outdoor
fan motor.
Disconnect the connector CN771 on the
inverter P.C. board.
Disconnect the connector (CN61) between
compressor and power transistor module.
Turn ON the power supply and press the
EMERGENCY OPERATION switch.
Does the upper lamp of
OPERATION
INDICATOR lamp on
the indoor unit light up?
After 3 minutes, is
there voltage 230 VAC
between CN771
and
on the inverter P.C.
board?
Replace the outdoor
fan motor.
Replace the inverter
P.C. board.
Yes
No
Yes
No
I Check of outdoor fan motor
MUZ-HJ25VA MUZ-HJ35VA
MUZ-HJ50VA
Is the resistance between each ter-
minal of outdoor fan motor normal?
(Refer to 11-4.)
Disconnect CN932 from the inverter P.C. board, and turn on the
power supply.
Rotate the outdoor fan motor manually and measure the voltage
of CN931.
Between 1(+) and 5(-)
Between 2(+) and 5(-)
Between 3(+) and 5(-)
Does the voltage between each terminal become 5 and 0
VDC repeatedly?
Does the outdoor fan motor rotate smoothly?
Replace the outdoor fan motor.
Replace the inverter P.C. board.
Yes
Yes
No
(Fixed to either 5 or 0 VDC)
No
No
Yes
Disconnect the connectors CN931
and CN932 from the inverter P.C.
board.
Check the connection between the
connector CN931 and CN932.
OBH648A