Page 1 - VECTOR INVERTER

VECTOR INVERTER-INSTRUCTION MANUAL-FR-V5NSSSCNET COMMUNICATION OPTION

Page 2 - SAFETY INSTRUCTIONS

42.INSTALLATION2.1 Pre-Installation InstructionsMake sure that the input power of the inverter is off.2.2 Setting the Station Numbers and Terminating

Page 3 - 3. Additional Instructions

5INSTALLATION2.2.1 Setting the station numbersSet the inverter station number before switching on the inverter and do not change the setting while pow

Page 4 - (6) General instruction

6INSTALLATION2.2.2 Setting the terminating resistorThe terminating resistor setting jumper connectors are factory-set in the terminating resistor abse

Page 5 - CONTENTS

7INSTALLATION2.3 Installation and Removal(1) Install the option unit to Slot 3. (If you install it to Slot 1 or 2, E.OP1 (E.OP2) is displayed and oper

Page 6 - 8. PRECAUTIONS 25

83. WIRING3.1 Wiring ExampleFR-V500UVWUVWEG1G2PAPARPBPBRPZPZRPGSDEncoderIMFANThermal protectorDedicated motor (SF-V5R)ABCABCDFGSRSDOHMain circuit term

Page 7 - 1.PRE-OPERATION INSTRUCTIONS

9WIRING3.2 Connection ExampleMotion controller CPU Q173CPU or Q172CPUInverter FR-V500 series + FR-V5NS (SSCNET communication unit)Cables1), 5) FR-V5NS

Page 8 - PRE-OPERATION INSTRUCTIONS

10WIRING3.3 SSCNET Cables and Ground CableUse our optional SSCNET connection cables.(1) Cable type * _ in the type represents the cable length.Type *

Page 9

11WIRING(2) Earth (Ground) CableFor wiring to the earth (ground) terminal of the FR-V5NS, use a crimping terminal with sleeve.•Cable gause: 2 mm2•Crim

Page 10 - 2.INSTALLATION

12WIRING3.4 Wiring Route•Route the SSCNET cables using the space on the right side of the control circuit terminal.•Connect the earth (ground) cable t

Page 11 - INSTALLATION

134. SSCNET COMMUNICATION STATUSWhen the inverter is fitted with the SSCNET communication unit (FR-V5NS) and has any of station No. 0 to No. 7, pow-er

Page 12 - Factory setting

A-1Thank you for choosing the Mitsubishi vector inverter option unit.This instruction manual gives handling information and precautions for use of thi

Page 13 - 2.3 Installation and Removal

145. INITIAL COMMUNICATION SETTING FROM MOTION CONTROLLERThe following parameters are set during initial communication with the motion controller.For

Page 14 - 3. WIRING

156. INVERTER SETTINGS AND INDICATIONS6.1 Operation Mode Switchover(1) Starting operation mode(2) Operation mode switchover (When Pr. 79 = 0)Symbol Sw

Page 15 - 3.2 Connection Example

16INVERTER SETTINGS AND INDICATIONS6.2 Initial Communication Waiting Status ("CF" alarm)If SSCNET communication is disabled due to the fault

Page 16 - Connection

17INVERTER SETTINGS AND INDICATIONS6.2.1 Pr. 499 "action selection at SSCNET communication interruption"You can select the operation to be p

Page 17 - (2) Earth (Ground) Cable

187. RESTRICTIONS ON THE FUNCTIONS7.1 Inverter Parameter ListFunction validity: There are restrictions on the inverter functions in the SSCNET communi

Page 18 - 3.4 Wiring Route

19RESTRICTIONS ON THE FUNCTIONS73 Speed setting signalX75Reset selection/disconnected PU detection/PU stop selectionO77 Parameter write disable select

Page 19 - SSCNET communication status

20RESTRICTIONS ON THE FUNCTIONS234 Multi-speed setting (speed 10)X235 Multi-speed setting (speed 11)X236 Multi-speed setting (speed 12)X237 Multi-spee

Page 20

21RESTRICTIONS ON THE FUNCTIONS374 Overspeed detection levelO380 Acceleration S pattern 1X381 Deceleration S pattern 1X382 Acceleration S pattern 2X38

Page 21 - 6.1 Operation Mode Switchover

22RESTRICTIONS ON THE FUNCTIONS483Tenth position feed amount lower 4 digitsX484Tenth position feed amount upper 4 digitsX485Eleventh position feed amo

Page 22

23RESTRICTIONS ON THE FUNCTIONS847Fall-time torque bias No. 3 biasX848Fall-time torque bias No. 3 gainX849 Analog input offset adjustmentX851 Number o

Page 23

A-22. Injury Prevention3. Additional InstructionsAlso note the following points to prevent an accidental failure, injury, electric shock, etc.:(1) Tra

Page 24 - 7.1 Inverter Parameter List

24RESTRICTIONS ON THE FUNCTIONSREMARKSWhether the I/O terminal function in the SSCNET communication operation mode is valid or invalid is indicated by

Page 25 - RESTRICTIONS ON THE FUNCTIONS

258. PRECAUTIONS• The inverter parameter values cannot be changed from the motion controller. Use the PU (FR-DU04-1/FR-PU04V) to change them. (Except

Page 26

269. ALARM INDICATION DEFINITIONS AND CORRECTIVE ACTIONSThis section provides the definitions of the alarm indications and their corrective actions.(1

Page 27

27ALARM INDICATION DEFINITIONS AND CORRECTIVE ACTIONS(2) AlarmWhen the protective function is activated, the output is not shut off.Operation panel in

Page 28

REVISIONS*The manual number is given on the bottom left of the back cover.Print Date *Manual Number RevisionMay, 2002 IB(NA)-0600106E-A First editionJ

Page 29

A-3(3) Usage(4) Maintenance, inspection and parts replacement(5) Disposal(6) General instruction Do not modify the equipment. Do not perform parts r

Page 30 - * The function using the PU

CONTENTS1.PRE-OPERATION INSTRUCTIONS 11.1 Unpacking and Product Confirmation ...

Page 31 - 8. PRECAUTIONS

6.2.1 Pr. 499 "action selection at SSCNET communication interruption" ...176.2.2 Pr. 52 "DU/PU

Page 32 - (1) Faults

11.PRE-OPERATION INSTRUCTIONS1.1 Unpacking and Product ConfirmationTake the option unit out of the package, check the unit name, and confirm that the

Page 33 - (2) Alarm

2PRE-OPERATION INSTRUCTIONS1.4 StructureName FunctionRefer topage1) Terminating resistor Set terminating resistor present/absent using a jumper connec

Page 34 - REVISIONS

3PRE-OPERATION INSTRUCTIONS1.5 Operation OverviewIn communication with the Mitsubishi motion controller, the inverter operation (speed control or posi