SERVICE TECHNICAL GUIDE
CONTENTS
1. MSC MICROPROCESSOR CONTROL················6
2. MS MICROPROCESSOR CONTROL ················15
3. MSH MICROPROCESSOR CONTROL··············26
4. MSZ-CA MICROPROCESSOR CONTROL········39
5. MSZ-FA MICROPROCESSOR CONTROL ········54
6. MSZ-GA, MSZ-CB
MICROPROCESSOR CONTROL ············72
7. MCF MICROPROCESSOR CONTROL············100
8. MCFH MICROPROCESSOR CONTROL ·········106
9. MFZ MICROPROCESSOR CONTROL ············115
10. MSZ-HA MICROPROCESSOR CONTROL·····127
11. MSZ-GB MICROPROCESSOR CONTROL·····137
12. MXZ MICROPROCESSOR CONTROL···········150
Wireless type Models
Multi system type Models
SPLIT-TYPE, AIR CONDITIONERS
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
FLOOR AND CEILING TYPE AIR CONDITIONERS
FLOOR TYPE, HEAT PUMP AIR CONDITIONERS
MSC-CA•VB - · MU-GA•VB -
MSC-CB•VB - · MUH-GA•VB -
MSC-GA•VB -
E
EE
EE
· MXZ-A•VA -
E
MCF-GA
VB
- · MUCF-GA•VB -
MCFH-GA
VB
- · MUCFH-GA•VB -
MFZ-KA
VA
-
E
EE
EE
MS-GA•VB - · MU-GA•VB -
MSH-CA•VB -
MSH-CB•VB -
MSH-GA•VB - · MUH-GA•VB -
MSZ-CA•VB - · MUZ-CA•VB -
MSZ-FA•VA - · MUZ-FA•VA -
· MUZ-FA•VAH -
MSZ-GA•VA - · MUZ-GA•VA -
· MUZ-GA•VAH -
MSZ-CB•VA -
MSZ-HA•VA - · MUZ-HA•VA -
MSZ-GB•VA - · MUZ-GB•VA -
EE
EE
E
E
EE
E
EE
EE
EE
E
E
EE
Wireless type Models
Inverter-controlled multi system type Models
· MUX-A•VB -
E
Wireless type Models
No. OBT06
REVISED EDITION-D
Revision D:
• MXZ-5A100VA - has been added.
E
Please void OBT06 REVISED EDITION-C.
OBT06D--1qxp 07.3.2 9:22 AM Page 1
Page view 0
1 2 3 4 5 6 ... 163 164

Summary of Contents

Page 1 - SERVICE TECHNICAL GUIDE

SERVICE TECHNICAL GUIDECONTENTS1. MSC MICROPROCESSOR CONTROL················62. MS MICROPROCESSOR CONTROL ················153. MSH MICROPROCESSOR CONT

Page 2

10ModeCOOL mode of"I FEEL CONTROL"DRY mode of"I FEEL CONTROL"HEAT mode of"I FEEL CONTROL"Initial room temperatureInit

Page 3

100MCF MICROPROCESSOR CONTROL7WIRELESS REMOTE CONTROLLEROnce the operation mode is set, the same operation modecan be repeated by simply turning OPERA

Page 4 - Indoor unit models

101❈1 When the system is restarted with the remote controller, the system operates with the previous set temperature regard-less of the room temperatu

Page 5 - Outdoor unit models

102Compressor and Outdoor fan motorOFFONIndoor fan motorON (continuously at set speed)ONOFF7-1-2. DRY mode of “I FEEL CONTROL”The system for dry

Page 6 - MSC MICROPROCESSOR CONTROL

1037-5. AUTO VANE OPERATION(1) Vane motor driveThis series is equipped with a stepping motor for the vane. The rotating direction, speed, and angle of

Page 7 - 1-2. DRY ( ) OPERATION

104(8) ECONO COOL ( ) operation (ECONOmical operation)When ECONO COOL button is pressed in COOL mode, set temperature is automatically set 2°C higher.

Page 8 - <MUH-GA20/GA25/GA35VB>

1057-6. TIMER OPERATION1. How to set the timer (1) Press OPERATE/STOP(ON/OFF) button to start the air conditioner.(2) Check that the current time is s

Page 9

106MCFH MICROPROCESSOR CONTROL8WIRELESS REMOTE CONTROLLEROnce the operation mode is set, the same operation modecan be repeated by simply turning OPER

Page 10 - • Fuzzy control

107② Time controlWhen the three conditions as follows have been satisfied for 1 hour and 45 minutes, compressor stops for 3 minutes.The indoor fan ope

Page 11 - 1-7. AUTO VANE OPERATION

108CompressorOutdoor fanIndoor fanONOFF(continuously at set speed)OFFONONOperation chartExample8-1-2. DRY mode of “I FEEL CONTROL”The system for dry o

Page 12

109(3) Warm air controlWhen compressor starts in heating operation or after defrosting, the fan changes the speed due to the indoor coil ther-mistor R

Page 13 - PROGRAM TIMER

11High HighMed.LowCOOL and DRY operationHEAT operation <MUH-GA20/GA25/GA35VB>Vane angle is fixed to Angle 1.Vane angle is fixed to Angle 4.1-6.

Page 14 - MUX-2A70VB

1104. DefrostingDefrosting of outdoor heat exchanger is controlled by DEICER P.C. board, with detection by the defrost thermistor RT61.(1) Starting co

Page 15 - MS MICROPROCESSOR CONTROL

1118-3. DRY ( ) OPERATION(1) Press OPERATE/STOP(ON/OFF) button.OPERATION INDICATOR lamp of the indoor unit turns on with abeep tone.(2) Select DRY mod

Page 16

112(5) STOP (operation OFF) and ON-TIMER standbyWhen the following cases occur, the vane returns to the closed position.(a) When OPERATE/STOP (ON/OFF)

Page 17

113(3) Press ON/OFF TIMER buttons to select the operation.“ON-TIMER” button ... AUTO START operation (ON timer)“OFF-TIMER” button ... AUTO STOP operat

Page 18 - 2-2. COOL ( ) OPERATION

1148-7. EMERGENCY / TEST OPERATIONIn case of test run operation or emergency operation, use EMERGENCY OPERATION switch on the front of the indoorunit.

Page 19 - 2-4. FAN ( ) OPERATION

115MFZ MICROPROCESSOR CONTROL9Once the operation mode is set, the same operation mode can be repeated by simply turning OPERATE/STOP(ON/OFF) button ON

Page 20

1162. Indoor fan speed controlIndoor fan operates continuously at the set speed by FAN SPEED CONTROL button regardless of the thermostat’s OFF-ON.In A

Page 21

1171.7 :2.0 :Set temperatureDifference between roomtemperature and set tem-perature during operation1. Thermostat controlThermostat is ON or OFF by di

Page 22 - About 100

1183. High pressure protectionIn HEAT operation the indoor coil thermistor detects the temperature of the indoor heat exchanger. The compressor opera-

Page 23 - EMERGENCY OPERATION switch

119Time chart of defrosting in HEAT mode (reverse type)set positionset speedset positionset speedIndoor fan (upper)Compressor normalOutdoor fanR.V. co

Page 24

12(7) Cold air prevention in HEAT operation <MUH-GA20/GA25/GA35VB>When any of the following conditions occurs in HEAT operation, the horizontal

Page 25

120HighMed.LowSuper HighSuper HightimeRotational frequency9-5. INDOOR FAN MOTOR CONTROL(1) Rotational frequency feedback controlThe indoor fan motor i

Page 26 - MSH MICROPROCESSOR CONTROL

121(4) VANE AUTO ( ) modeThe microprocessor automatically determines the vane angle and operation to make the optimum room temperature dis-tribution.(

Page 27

122 Set the air outlet selection switch to . Set the air outlet selection switch to .Air blows out automatically from the upper and lower air out-let

Page 28

123(11) ECONO COOL ( ) operation (ECONOmical operation)When ECONO COOL button is pressed in COOL mode, set temperature is automatically set 2°C higher

Page 29 - 1°C 1.7°C

124Usage of i-save operation:1.Using as a low-energy modei-save operation can be used as a low-energy mode by setting the temperature 2–3: warmer than

Page 30

1259-9. TIMER OPERATION1. How to set the timer(1) Press OPERATE/STOP (ON/OFF) button to start the air conditioner.(2) Check that the current time is s

Page 31 - 5 seconds

126EMERGENCY OPERATION switchE.O.SWOperation mode COOL HEATSet temperature24:24:Fan speed Medium MediumHorizontal vane Auto Auto• The following indica

Page 32 - 3-4. HEAT ( ) OPERATION

127MSZ-HA MICROPROCESSOR CONTROL10Once the operation mode is set, the same operation mode can be repeated by simply turning OPERATE/STOP(ON/OFF) butto

Page 33 - 3-6. AUTO VANE OPERATION

1282. Indoor fan speed controlIndoor fan operates continuously at the set speed by FAN SPEED CONTROL button regardless of the thermostat’s OFF-ON.In A

Page 34

1293. High pressure protectionIn HEAT operation the indoor coil thermistor detects the temperature of the indoor heat exchanger. The compressor opera-

Page 35 - About 150

LightedNot lightedPress once <Cool>Press again <Heat>Press once again <Stop>w Heat is available only in MUH-GA20/GA25/GA35VB.13EMERG

Page 36

130Time chart of defrosting in HEAT mode (reverse type)set positionset speedset positionset speedIndoor fanCompressor normalOutdoor fanR.V. coil (21S4

Page 37

131(4) VANE AUTO ( ) modeThe microprocessor automatically determines the vane angle and operation to make the optimum room temperature dis-tribution.H

Page 38 - 2: or more and less than 3:

132The air conditioner starts heat-ing operation approx. 3 minutesafter the vane has moved to thehorizontal position.• Sometimes the areaaround your f

Page 39 - MSZ-CA MICROPROCESSOR CONTROL

13310-6. TIMER OPERATION (ON/OFF TIMER)SELECT(OFF TIMER) (ON TIMER) TIMER RELEASE SELECT(1) Press OPERATE/STOP (ON/OFF) button to start the air co

Page 40

13410-8. INVERTER SYSTEM CONTROL10-8-1. Inverter main power supply circuitPOWER P.C. BOARDPowersupplyINVERTER P.C. BOARDR64A R64BCTTR821DB65X64L62 L63

Page 41

1354. Intelligent power module IPM consists of the following components · IGBT (x6) : Converts DC waveform to three-phase AC waveform and out

Page 42

136w The operation frequency in COOL mode is restricted the upper limit frequency after 0.5 ~ 1 hour as shown below for dew prevention.It is rated fre

Page 43

137MSZ-GB MICROPROCESSOR CONTROL11Once the operation mode is set, the same operation mode can be repeated by simply turning OPERATE/STOP(ON/OFF) butto

Page 44

1382. Indoor fan speed controlIndoor fan operates continuously at the set speed by FAN SPEED CONTROL button regardless of the thermostat’s OFF-ON.In A

Page 45 - 4-5. HEAT ( ) OPERATION

1392. Indoor fan speed control (1) Indoor fan operates at the set speed by FAN SPEED CONTROL button.In Auto the fan speed is as follows.Set temperatur

Page 46 - 4-6. INDOOR FAN MOTOR CONTROL

141-10. OUTDOOR UNIT ACTUATOR CONTROLACTUATORONOFFONOFFONOFFON (OPEN)OFF (CLOSE)ON (OPEN)OFF (CLOSE)ON (OPEN)OFF (CLOSE)ON (OPEN)OFF (CLOSE)ON (CLOSE)

Page 47

140Time chart of defrosting in HEAT mode (reverse type)set positionset speedset positionset speedIndoor fanCompressor normalOutdoor fanR.V. coil (21S4

Page 48 - OFF-TIMER

14111-4. AUTO CHANGE OVER ··· AUTO MODE OPERATIONOnce desired temperature is set, unit operation is switched automatically between COOL and HEAT opera

Page 49 - 4-10. INVERTER SYSTEM CONTROL

142(4) VANE AUTO ( ) modeThe microprocessor automatically determines the vane angle and operation to make the optimum room temperature dis-tribution.H

Page 50

143NOTE: When 2 or more indoor units are operated with multi outdoor unit, even if any indoor unit turns thermostat off,this control doesn’t work in t

Page 51

144PROGRAM TIMER(Example 1) The current time is 8:00 PM.The unit turns off at 11:00 PM, and on at 6:00 AM.• OFF timer and ON timer can be used in comb

Page 52

145EMERGENCY OPERATION switchE.O.SWOperation mode COOL HEATSet temperature24:24:Fan speed Medium MediumHorizontal vane Auto AutoThe operation mode is

Page 53

146 4. Power transistor module IPM consists of the following components. · Power Transistors (x6): Converts DC waveform to three-phase AC wavefor

Page 54 - MSZ-FA MICROPROCESSOR CONTROL

147w The operation frequency in COOL mode is restricted the upper limit frequency after 1 hour as shown below for dew prevention.It is rated frequency

Page 55 - 5-1. COOL ( ) OPERATION

14811-12. EXPANSION VALVE CONTROL (LEV CONTROL)(1) Outline of LEV controlThe LEV basic control is comprised of setting LEV opening degree to the stand

Page 56

149In COOL operation, the two indoor coil thermistors (one main and one sub) sense temperature ununiformity (superheat) at the heat exchanger, and whe

Page 57

152MS MICROPROCESSOR CONTROLWIRELESS REMOTE CONTROLLERModeCOOL mode of"I FEEL CONTROL" DRY mode of"I FEEL CONTROL"Initial room t

Page 58

15012MXZ MICROPROCESSOR CONTROL12-1. INVERTER SYSTEM CONTROLMXZ-2A30/40/52VA12-1-1. Inverter main power supply circuitPOWER P.C. BOARDPowersupplyINVER

Page 59

1514. Intelligent power module IPM consists of the following components · IGBT (x6) : Converts DC waveform to three-phase AC waveform and ou

Page 60 - Horizontal

152152 4. Power transistor module IPM consists of the following components. · Power Transistors (x6): Converts DC waveform to three-phase AC wave

Page 61

15312-2. EXPANSION VALVE CONTROL (LEV CONTROL)Linear expansion valve (LEV) is controlled by "Thermostat ON" commands given from each unit.Wh

Page 62 - Warm area Cold area

154The table below shows the role of Exclusive LEV and Receiver LEV in each operation mode.wIn COOL mode, the two indoor coil thermistor (one main and

Page 63 - Approx. 150 degrees

155Standard opening (pulse)01 02 03 04 05 06 07 08COOLLEV Opening(code)HEAT1261401301461341501381701401801422001822242282440929627210310280Code5,6Code

Page 64 - WASH reset switch

1 Discharge temperature 2 Each correction • (Each gas pipe temperature thermistor - Minimum gas pipe temperature thermistor)w 1 • (Main indoor coil

Page 65

157Operation frequency of compressor (Hz)Minimum ~ 2324 ~ 3839 ~ 5455 ~ 6970 ~ 8586 ~ 100101 ~ Maximum1 unit354049586570702 units586065687070703 unit

Page 66 - Not lighted

LEV opening correction (pulse)6[ RT 4[ RT< 6RT<4210Temperature to be decreased (:)6[ RT4[ RT< 6RT<4-10-5-5RTRTb) Correct the L

Page 67 - 5-14. INVERTER SYSTEM CONTROL

15912-3. OPERATIONAL FREQUENCY RANGE12Capacitycode3, 47~ 11Min.353535COOL (Hz)Max.586898DRY(Hz)354568Min.353535Max.989898HEAT (Hz)Defrost989898Number

Page 68

16Previous operationCOOL mode of “I FEEL CONTROL”or COOL mode• Once the mode is fixed, the mode does not change by room temperature afterwards.•

Page 69

160Number ofoperatingunit1234Capacitycode3, 47101213~ 78 ~ 1011 ~ 1314 ~ 1617 ~9 ~12 ~Min.151515151524242424245263COOL (Hz)Max.58586268798080808080909

Page 70

161MXZ-2A30VA MXZ-2A40VA MXZ-2A52VA<Control status>The control performs when the all the following status are satisfied;• When one or more indoo

Page 71

1621. Pre-heat control is turned ON for 15 or 30 minw after the breaker is turned ON.2. 30 min. after the unit is stopped, pre-heat control is turned

Page 72

16312-10. DRY OPERATION12-11. HEAT OPERATION2. High pressure protectionIn HEAT operation the indoor coil thermistor detects the temperature of the ind

Page 73 - 6-1. COOL ( ) OPERATION

New publication, effective Mar. 2007Specifications subject to change without notice.CCCopyright 2005 MITSUBISHI ELECTRIC ENGINEERING CO.,LTDDistribute

Page 74 - 6-3. HEAT ( ) OPERATION

171. Indoor fan speed controlIndoor fan operates at the set speed by FAN SPEED CONTROL button.In AUTO the fan speed is as follows.Initial temperature

Page 75

182-2. COOL ( ) OPERATION(1) Press OPERATE/STOP (ON/OFF) button.OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone.(2) Select COOL

Page 76

19HighRotational frequencyHightimeMed.Low2-5. INDOOR FAN MOTOR CONTROL(1) Rotational frequency feedback controlThe indoor fan motor is equipped with a

Page 77 - 6-7. AUTO VANE OPERATION

1. MSC MICROPROCESSOR CONTROL·························································6Indoor unit models Outdoor unit modelsMSC-CA20VB MSC-CB20VB MSC

Page 78

20COOL and DRY operationFAN operationVane angle is fixed to Angle 1.Vane angle is fixed to Angle 4.(4) VANE AUTO ( ) modeThe microprocessor automatica

Page 79

21(9) LONG MODE ( )By pressing LONG button indoor fan speed becomes faster than setting fan speed on the remote controller, and the hori-zontal vane m

Page 80

222. CancelTIMER setting can be cancelled with ON/OFF TIMER buttons.To cancel ON timer, press “ON-TIMER” button.To cancel OFF timer, press “OFF-TIMER”

Page 81 - 6-10. INVERTER SYSTEM CONTROL

23EMERGENCY OPERATION switchPress once <Cool>Press again <Stop>OPERATION INDICATOR lamp• The following indication applies regardless of

Page 82

24(1) LEV opening correction by discharge temperatureThe LEV opening is corrected according to the temperature difference between target discharge tem

Page 83

252 When the temperature difference RT between indoor coil thermistor (main) RT12 and indoor coil thermistor (sub)RT13 in the indoor unit is 2: or mo

Page 84

26MSH MICROPROCESSOR CONTROL3LightedNot lightedApprox. 2 : or moreDifference between target temperature and room temperatureApprox. 2 : or lessThis sh

Page 85

27ExamplePrevious operationCOOL mode of “I FEEL CONTROL”or COOL mode• Once the mode is fixed, the mode does not change by room temperature afterwar

Page 86 - 6-13. COOL ( ) OPERATION

281. Indoor fan speed controlIndoor fan operates at the set speed by FAN SPEED CONTROL button.In AUTO the fan speed is as follows.Initial temperature

Page 87

29Operation time chartExample3. Coil frost prevention • The operation is as same as coil frost prevention during COOL mode of “I FEEL CONTROL”.• Indoo

Page 88 - 6-15. HEAT ( ) OPERATION

4. MSZ-CA MICROPROCESSOR CONTROL·················································39Indoor unit models Outdoor unit modelsMSZ-CA25VB MUZ-CA25VBMSZ-

Page 89

30(2) Cold air prevention controlThe fan runs at set speed when the indoor coil thermistor RT12 temperature exceeds 22°C. The fan operates Low whenthe

Page 90

31NOTE : During the high pressure protection and for 10 seconds after high pressure protection, defrosting of outdoor heatexchanger is not detected by

Page 91 - 6-19. AUTO VANE OPERATION

32HighRotational frequencyHightimeMed.Low3-5. INDOOR FAN MOTOR CONTROL(1) Rotational frequency feedback controlThe indoor fan motor is equipped with a

Page 92

33AUTOHorizontal1234 5Middle Downward Swing3-6. AUTO VANE OPERATION1. Horizontal vane(1) Vane motor driveThese models are equipped with a stepping mot

Page 93

34(10) LONG MODE ( )By pressing LONG button indoor fan speed becomes faster than setting fan speed on the remote controller, and the hor-izontal vane

Page 94

35612345SWING2. Vertical vane(1) Vane motor driveThese models are equipped with a stepping motor for the vertical vane. The rotating direction, speed,

Page 95 - 6-22. INVERTER SYSTEM CONTROL

36EMERGENCY OPERATION switchPress once <Cool>Press again <Heat>Press once again <Stop>OPERATION INDICATOR l

Page 96

373-9. EXPANSION VALVE CONTROL (LEV CONTROL) <MUH-GA80VB>LEV (Expansion valve) is controlled by “Thermostat ON” commands given from the unit.Con

Page 97

382 When the temperature difference RT between indoor coil thermistor (main) RT12 and indoor coil thermistor (sub)RT13 in the indoor unit is 2: or mo

Page 98

394MSZ-CA MICROPROCESSOR CONTROLOnce the operation mode is set, the same operation modecan be repeated by simply turning OPERATE/STOP(ON/OFF) button O

Page 99

Indoor unit models Outdoor unit modelsMSZ-GA50VA MUZ-GA50VAMSZ-GA60VA MUZ-GA60VAMSZ-GA71VA MUZ-GA71VA6-13. COOL OPERATION ·························

Page 100 - MCF MICROPROCESSOR CONTROL

40ExamplePrevious operationCOOL mode of “I FEEL CONTROL” orCOOL modeExamplePrevious operationCOOL mode of “I FEELCONTROL” or COOLmodeWhen the system i

Page 101

412. Indoor fan speed controlIndoor fan operates continuously at the set speed by FAN SPEED CONTROL button regardless of the thermostat’s OFF-ON.In AU

Page 102 - 3 minutes

424-1-3. HEAT mode of “I FEEL CONTROL” 2. Indoor fan speed control (1) Indoor fan operates at the set speed by FAN SPEED CONTROL button.In Auto the fa

Page 103 - 7-5. AUTO VANE OPERATION

43Gradation of fan speed in initial (example)The upper limit of the fan speed in MANUAL is the set speed.The upper limit of the fan speed in AUTO is t

Page 104 - 18°C to 20°C

44Time chart of defrosting in HEAT mode (reverse type)set positionset speedset positionset speedIndoor fanCompressor normalOutdoor fanR.V. coil (21S4)

Page 105 - OPERATION INDICATOR lamp

454-4. DRY ( ) OPERATION(1) Press OPERATE/STOP(ON/OFF) button.OPERATION INDICATOR lamp of the indoor unit turns on with abeep tone.(2) Select DRY mode

Page 106 - MCFH MICROPROCESSOR CONTROL

46(3) PositioningThe vane presses the vane stopper once to confirm the standard position and then moves to the set angle.Confirming of standard positi

Page 107 - ● Fuzzy control

47<SWING operation>In swing operation of ECONO COOL operation mode, the initial air flow direction is adjusted to “Horizontal”.According to the

Page 108

484-9. EMERGENCY / TEST OPERATIONIn case of test run operation or emergency operation, use EMERGENCY OPERATION switch on the front of the indoorunit.

Page 109 - Difference between room

494-10. INVERTER SYSTEM CONTROL4-10-1. Inverter main power supply circuitPOWER P.C. BOARDPowersupplyINVERTER P.C. BOARDR64A R64BCTTR821DB65X64L62 L63C

Page 110 - 8-2. COOL ( ) OPERATION

10. MSZ-HA MICROPROCESSOR CONTROL·············································127Indoor unit models Outdoor unit modelsMSZ-HA25VA MUZ-HA25VAMSZ-HA3

Page 111 - 8-5. AUTO VANE OPERATION

504. Intelligent power module IPM consists of the following components · IGBT (x6) : Converts DC waveform to three-phase

Page 112

51w The operation frequency in COOL mode is restricted the upper limit frequency after 1 hour as shown below for dew prevention.It is rated frequency

Page 113 - 8-6. TIMER OPERATION

524-12. EXPANSION VALVE CONTROL (LEV CONTROL)(1) Outline of LEV controlThe LEV basic control is comprised of setting LEV opening degree to the standar

Page 114 - OPERATION switch

53In COOL operation, the two indoor coil thermistors (one main and one sub) sense temperature ununiformity (superheat) at the heat exchanger, and when

Page 115 - MFZ MICROPROCESSOR CONTROL

54MSZ-FA MICROPROCESSOR CONTROL5Once the operation mode is set, the same operation mode can be repeated by simply turning OPERATE/STOP(ON/OFF) button

Page 116 - 9-1. COOL ( ) OPERATION

552. Indoor fan speed controlIndoor fan operates continuously at the set speed by FAN SPEED CONTROL button regardless of the thermostat’s OFF-ON.In AU

Page 117 - 9-3. HEAT ( ) OPERATION

562. Indoor fan speed control (1) Indoor fan operates at the set speed by FAN SPEED CONTROL button.In Auto the fan speed is as follows.Set temperature

Page 118 - Defrost heater

575: 8:Defrost heater ONOFF3. High pressure protectionIn HEAT operation the indoor coil thermistor detects the temperature of the indoor heat exchange

Page 119

58Time chart of defrosting in HEAT mode (reverse type)set positionset speedset positionset speedIndoor fanCompressor normalOutdoor fanR.V. coil (21S4)

Page 120

59HighMed.LowSuper HighSuper HightimeRotational frequency5-5. INDOOR FAN MOTOR CONTROL(1) Rotational frequency feedback controlThe indoor fan motor is

Page 121

6MSC MICROPROCESSOR CONTROL1ON/OFFFANTOOWARMTOOCOOLVANEMODEECONO COOL STOP STARTHR.MIN.I FEELCOOLDRY PMCLOCKAMRESETCLOCKHEAT/FAN/Open the fr

Page 122

60(4) VANE AUTO ( ) modeThe microprocessor automatically determines the vane angle and operation to make the optimum room temperature dis-tribution.Ho

Page 123 - Cut the wires on both ends

61<SWING operation>In swing operation of ECONO COOL operation mode, the initial air flow direction is adjusted to “Horizontal”.According to the

Page 124

62i-see Sensori-see Sensor, which is installed on the right side of the air outlet of the indoor unit, is moved with the stepping motor and itdetects

Page 125 - STOP

63(4) AREA setting is cancelled when the "cancel" is sellected by pressing AREA button, or when WIDE VANE button is pressed.· Be sure

Page 126

64PLASMA/WASH lampBlinkingNot lightedLightedWASH reset switchWASHresetE.O.SWEach time this b utton is pressed, the oper ation mode of PLASMA is chang

Page 127 - MSZ-HA MICROPROCESSOR CONTROL

655-12. TIMER OPERATION1. How to set the timer(1) Press OPERATE/STOP (ON/OFF) button to start the air conditioner.(2) Check that the current time is s

Page 128 - 10-2. DRY ( ) OPERATION

66EMERGENCY OPERATION switchWASHresetE.O.SWOperation mode COOL HEATSet temperature24:24:Fan speed Medium MediumHorizontal vane Auto AutoVertical vane

Page 129 - 10-3. HEAT ( ) OPERATION

675-14. INVERTER SYSTEM CONTROL5-14-1. Inverter main power supply circuitPOWER P.C. BOARDPowersupplyINVERTER P.C. BOARDR64A R64BCTTR821DB65X64L62 L63C

Page 130

684. Intelligent power module IPM consists of the following components · IGBT (x6) : Converts DC waveform to three-phase AC waveform and outp

Page 131 - 10-5. AUTO VANE OPERATION

69w The operation frequency in COOL mode is restricted the upper limit frequency after 1 hour as shown below for dew prevention.It is rated frequency

Page 132

7CompressorOutdoor fanOFFON( continuously at set speed)Indoor fanONONOFF② Time controlWhen the three conditions as follows have been satisfied for 1 h

Page 133 - EMERGENCY COOL

705-16. EXPANSION VALVE CONTROL (LEV CONTROL)(1) Outline of LEV controlThe LEV basic control is comprised of setting LEV opening degree to the standar

Page 134 - 10-8. INVERTER SYSTEM CONTROL

71In COOL operation, the two indoor coil thermistors (one main and one sub) sense temperature ununiformity (superheat) at the heat exchanger, and when

Page 135

72MSZ-GA • MSZ-CB MICROPROCESSOR CONTROL6Once the operation mode is set, the same operation mode can be repeated by simply turning OPERATE/STOP(ON/OFF

Page 136 - MUZ-HA35VA

732. Indoor fan speed controlIndoor fan operates continuously at the set speed by FAN SPEED CONTROL button regardless of the thermostat’s OFF-ON.In AU

Page 137 - MSZ-GB MICROPROCESSOR CONTROL

742. Indoor fan speed control (1) Indoor fan operates at the set speed by FAN SPEED CONTROL button.In Auto the fan speed is as follows.Set temperature

Page 138 - 11-1. COOL ( ) OPERATION

753. High pressure protectionIn HEAT operation the indoor coil thermistor detects the temperature of the indoor heat exchanger. The compressor opera-t

Page 139 - 11-3. HEAT ( ) OPERATION

76Time chart of defrosting in HEAT mode (reverse type)set positionset speedset positionset speedIndoor fanCompressor normalOutdoor fanR.V. coil (21S4)

Page 140

77HighMed.LowSuper HighSuper HightimeRotational frequency6-5. INDOOR FAN MOTOR CONTROL(1) Rotational frequency feedback controlThe indoor fan motor is

Page 141

78(4) VANE AUTO ( ) modeThe microprocessor automatically determines the vane angle and operation to make the optimum room temperature dis-tribution.Ho

Page 142 - 11-7. AUTO VANE OPERATION

79<SWING operation>In swing operation of ECONO COOL operation mode, the initial air flow direction is adjusted to “Horizontal”.According to the

Page 143

84. Coil frost preventionThe operation is as same as coil frost prevention during COOL operation.(Refer to 1-1.3.)However when coil frost prevention w

Page 144

80EMERGENCY OPERATION switchE.O.SWOperation mode COOL HEATSet temperature24:24:Fan speed Medium MediumHorizontal vane Auto AutoThe operation mode is i

Page 145 - Press once again <Stop>

816-10. INVERTER SYSTEM CONTROL6-10-1. Inverter main power supply circuitPOWER P.C. BOARDPowersupplyINVERTER P.C. BOARDR64A R64BCTTR821DB65X64L62 L63C

Page 146

824. Intelligent power module IPM consists of the following components · IGBT (x6) : Converts DC waveform to three-phase AC waveform and outp

Page 147 - Rated frequency or less

83w The operation frequency in COOL mode is restricted the upper limit frequency after 1 hour as shown below for dew prevention.It is rated frequency

Page 148

846-12. EXPANSION VALVE CONTROL (LEV CONTROL) MUZ-GA35(1) Outline of LEV controlThe LEV basic control is comprised of setting LEV opening degree t

Page 149 - MUZ-GB50VA

85In COOL operation, the two indoor coil thermistors (one main and one sub) sense temperature ununiformity (superheat) at the heat exchanger, and when

Page 150 - MXZ MICROPROCESSOR CONTROL

86WIRELESS REMOTE CONTROLLERON/OFFTOOCOOLTOOWARMLONGSignal transmitting sectionOperation display sectionOPERATE /STOP(ON /OFF)buttonTEMPERATURE button

Page 151

87The system for dry operation uses the same refrigerant circuit as the cooling circuit.The compressor and the indoor fan are controlled by the room t

Page 152

882. Indoor fan speed control (1) Indoor fan operates at the set speed by FAN SPEED CONTROL button.In Auto the fan speed is as follows.Set temperature

Page 153

89Time chart of defrosting in HEAT mode (reverse type)set positionset speedset positionset speedIndoor fanCompressor normalOutdoor fanR.V. coil (21S4)

Page 154 - MXZ-3A/4A71/4A80VA

9(3) Warm air controlWhen the following any conditions of 1 (a. ~ c.) and the condition of 2 are satisfied at the same time, warm air controlworks.1 a

Page 155 - MXZ-3A54VA MXZ-4A71VA

906-16. AUTO CHANGE OVER ··· AUTO MODE OPERATIONOnce desired temperature is set, unit operation is switched automatically between COOL and HEAT operat

Page 156

916-18. OUTDOOR FAN MOTOR CONTROLFan speed is switched according to the compressor frequency.COOLFan speedUpDownUpDownModeHEATCompressor frequencyMUZ-

Page 157 - - MXZ-5A100VA

92SWING operationIn swing operation of ECONO COOL operation mode, the initial air flow direction is adjusted to “Horizontal”.According to the temperat

Page 158 - MXZ-4A80VA MXZ-5A100VA

93(10) LONG MODE ( )By pressing LONG button indoor fan speed becomes faster than setting fan speed on the remote controller, and the hor-izontal vane

Page 159

946-20. TIMER OPERATION1. How to set the timer(1) Press OPERATE/STOP (ON/OFF) button to start the air conditioner.(2) Check that the current time is s

Page 160 - MXZ-4A80VA - MXZ-5A100VA

956-21. EMERGENCY / TEST OPERATIONIn case of test run operation or emergency operation, use EMERGENCY OPERATION switch on the front of the indoorunit.

Page 161 - - )/ 100°C (4A80VA- /5A) or

96 4. Power transistor module IPM consists of the following components. · Power Transistors (x6): Converts DC waveform to three-phase AC waveform

Page 162 - - MXZ-5A

97w The operation frequency in COOL mode is restricted the upper limit frequency after 1 hour as shown below for dew prevention.It is rated frequency

Page 163 - 12-11. HEAT OPERATION

986-24. EXPANSION VALVE CONTROL (LEV CONTROL)(1) Outline of LEV controlThe LEV basic control is comprised of setting LEV opening degree to the standar

Page 164

99In COOL operation, the two indoor coil thermistors (one main and one sub) sense temperature ununiformity (superheat) at the heat exchanger, and when