33
Strainer
#100
Power
receiver
LEV A
LEV B
LEV C
Oil separator
Compressor
Defrost
thermistor
RT61
Distributor
Muffler
4-way valve
LEV E
Indoor unit
C
Indoor unit
B
Indoor unit
A
Indoor unit
A
Indoor unit
B
Indoor unit
C
Capillary tube
Capillary tube
Capillary tube
Capillary tube
Capillary tube
Discharge
temperature
thermistor RT62
Strainer
#100
Strainer
#100
Strainer
#100
R.V. coil
OFF
ON
Refrigerant flow in cooling
Refrigerant flow in heating
Ambient
temperature
thermistor
RT65
Outdoor heat
exchanger
temperature
thermistor
RT68
FAN-OUT
HEX-OUT
Strainer
#100
Stop valve with
service port
Stop valve
High-pressure switch
(MXZ-3B68VA only)
Refrigerant pipe diameter is different according to indoor unit to be connected. When using extension pipes, refer to the
tables below.
When diameter of refrigerant pipe is different from that of outdoor unit union, use optional Different-diameter pipe.
For further information on Different-diameter pipe, refer to "PARTS CATALOG".
UNIT: mm (inch)
UNIT: mm
MXZ-3C54VA
MXZ-3C68VA
MAX REFRIGERANT PIPING LENGTH
Outdoor unit union diameter
For
Indoor unit A
Liquid 6.35(1/4)
Gas 9.52(3/8)
Indoor unit B
Liquid 6.35(1/4)
Gas 9.52(3/8)
Indoor unit C
Liquid 6.35(1/4)
Gas 9.52(3/8)
a
b
c
Outdoor
unit
Indoor
units
15m
10m
15m
Refrigerant piping length (one way, 3 unit total)
Calculation : Xg = 20 g/m x (Refrigerant piping length (m) - 40)
Max.
Height
difference
Outdoor unit
precharged
(g)
50m
200
60m
400
40m
0
2,700
It is irrelevant which unit is higher.
ADDITIONAL REFRIGERANT CHARGE
3C54 3C68
Piping length each indoor unit (a, b, c) 25m 25m
Total piping length (a+b+c) 50m 60m
Bending point for each unit 25 25
Total bending point 50 50