Mitsubishi Electric MXZ-5C100VA Service Manual Page 79

  • Download
  • Add to my manuals
  • Print
  • Page
    / 306
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 78
79
MXZ-6C
Upper or
left lamp of
OPERATION
INDICATOR
lamp (Indoor
unit)
Abnormal point
(Failure mode/protection)
LED indication
(Outdoor P.C. board)
Condition Remedy
Indoor/
outdoor
unit failure
mode
recall
function
LED 1 LED 2
OFF None (Normal) Lighting Lighting
2-time ash Outdoor power system Lighting Lighting Overcurrent protection cut-out operates
3 consecutive times, bus-bar voltage
protection cut-out operates 3 consecu-
tive times, or primary current protection
cut-out operates 3 consecutive times
within 1minute after the compressor
gets started.
• Check the connection of
the compressor connecting
wire.
• Refer to 11-6.
How to
check inverter/compressor.
• Check the stop valve.
3-time ash Discharge temperature thermis-
tor
Lighting Once Thermistor shorts or opens during
compressor running.
• Refer to 11-6. "Check of
outdoor thermistors".
Defrost thermistor Lighting Once
Ambient temperature thermistor Lighting Twice
Fin temperature thermistor Lighting 3 times • Replace the power board.
P.C. board temperature thermis-
tor
Lighting 4 times • Replace the power board.
Outdoor heat exchanger tem-
perature thermistor
Lighting 9 times Refer to 11-6. "Check of
outdoor thermistors".
4-time ash Overcurrent Once Goes out 40 A current ows into intelligent power
module.
• Reconnect compressor con-
nector.
• Refer to 11-6.
"How to
check inverter/compressor".
• Check the stop valve.
Out-of-step protection 9 times Goes out Waveform of compressor current is dis-
torted.
• Refer to 11-6.
" How to
check inverter/compressor.
5-time ash Discharge temperature Lighting Lighting Discharge temperature exceeds 114 °C
during operation.
Compressor can restart if discharge
temperature thermistor reads 100 °C or
less 3 minutes later.
• Check refrigerant circuit and
refrigerant amount.
• Refer to 11-6. "Check of
LEV".
6-time ash High pressure Lighting Lighting High-pressure is detected with the
high-pressure switch (HPS) during op-
eration.
• Check refrigerant circuit and
refrigerant amount.
• Check the stop valve.
The outdoor heat exchanger tempera-
ture exceeds 70 °C during cooling or
the indoor gas pipe temperature ex-
ceeds 70°C during heating.
7-time ash Fin temperature 3 times Goes out
The n temperature exceeds
E1
:
110 °C /
E2
:
105 °C during operation.
• Check around outdoor unit.
• Check outdoor unit air pas-
sage.
• Refer to 11-6.
"Check of
outdoor fan motor".
P.C. board temperature 4 times Goes out The P.C. board temperature exceeds
95 °C during operation.
8-time ash Outdoor fan motor Lighting Lighting The fan motor speed is 50 rpm or less
or 1500 rpm or more for 1 minute, or
the fan motor speed is 100 rpm or
less for 15 seconds when the outside
temperature is 20 °C or more.
• Refer to 11-6.
"Check of
outdoor fan motor".
9-time ash Nonvolatile memory data Lighting 5 times Nonvolatile memory data cannot be
read properly.
• Replace the outdoor control
P.C. board.
• Replace the power board.
10-time ash Discharge temperature Lighting Lighting The frequency of the compressor is
kept 58Hz or more and the discharge
temperature is kept under 50 °C (cool-
ing)/40 °C (heating) for more than 40
minutes.
• Check refrigerant circuit and
refrigerant amount.
• Refer to 11-6. "Check of
LEV".