(4) The initial set temperature is decided by the initial room temperature.
1
Mode
Initial room temperature
26 °C or more 24 °C
Initial room temperature
minus 2
°C
25 °C to 26 °C
Initial set temperature
DRY mode of
“I FEEL CONTROL”
COOL mode of
“I FEEL CONTROL”
more than 13 °C, less than 25 °C
Initial room temperature
minus 2
°C
1 When the system is restarted with the remote controller, the system operates with the previous set temperature regard-
less of the room temperature at restart.
The set temperature is calculated by the previous set temperature.
(5) TEMPERATURE buttons
In “I FEEL CONTROL mode, set temperature is decided by the microprocessor based on the room temperature.
In addition, set temperature can be controlled by TOO WARM or TOO COOL buttons when you feel too cool or too warm.
Each time TOO WARM or TOO COOL button is pressed, the indoor unit receives the signal and emits a beep tone.
Fuzzy control
When TOO COOL or TOO WARM button is pressed, the microprocessor changes the set temperature, considering the
room temperature, the frequency of pressing TOO COOL or TOO WARM button and the user’s preference to heat or
cold. So this is called “Fuzzy control”, and works only in “I FEEL CONTROL” mode.
In DRY mode of “I FEEL CONTROL”, the set temperature does not change.
… To raise the set temperature 1 ~ 2
… To lower the set temperature 1 ~ 2
9-5. AUTO VANE OPERATION
1. Horizontal vane
(1) Vane motor drive
These models are equipped with a stepping motor for the horizontal vane. The rotating direction, speed, and angle of
the motor are controlled by pulse signals (approximately 12 V) transmitted from indoor microprocessor.
(2) The horizontal vane angle and mode change as follows by pressing VANE CONTROL button.
1
AUTO
1 2 3 4 5
SWING
(3) Positioning
To confirm the standard position, the vane moves until it touches the vane stopper. Then the vane is set to the
selected angle.
Confirming of standard position is performed in the following cases:
(a) When the operation starts or finishes (including timer operation).
(b) When the test run starts.
(4) VANE AUTO ( ) mode
In VANE AUTO mode, the microprocessor automatically determines the vane angle to make the optimum room tem-
perature distribution.
Vane angle is fixed to Angle 1.
OBH621A
Page view 16
1 2 ... 12 13 14 15 16 17 18 19 20 21 22 ... 41 42

Comments to this Manuals

BryanThubs 07 Apr 2024 | 20:32:56

Hello! Crazy discounts, hurry up! We are Drop Dead Studio and our goal is to help companies achieve impressive sales results through automated marketing. I. [b]We sell fresh databases for GSA Search Engine Ranker.[/b] • The databases are updated monthly through 24/7 parsing and by connecting purchased databases from other sources. • You have the option to purchase a one-time fresh database or pay for a lifetime subscription for updates. [i][b]ATTENTION![/b][/i] 40% discount only until