26
10-5. TROUBLE CRITERION OF MAIN PARTS
Part name Check method and criterion Figure
Room temperature
thermistor (RT11)
Indoor coil thermistor
(RT12)
Measure the resistance with a tester.
Refer to 10-7. "Test point diagram and voltage", "1. Indoor electronic control
P.C. board", for the chart of thermistor.
MS-GF20/25/35VA
Indoor fan motor (MF)
INNER FUSE
145 °C CUT OFF
Measure the resistance with a tester.
(Part temperature 10 ~ 30 °C)
Color of the lead wire Normal
WHT-BLK 334 Ω ~ 362 Ω
BLK-RED 370 Ω ~ 402 Ω
MS-GF50/60/80VA
Indoor fan motor (MF)
Check 10-6. "Check of indoor fan motor".
MS-GF20/25/35VA
Horizontal vane motor
(MV)
Measure the resistance between the terminals with a tester.
(Temperature: 10 - 30°C)
Color of the lead wire Normal
RED-BLK 223 Ω ~ 268 Ω
BLK
BLK
RED
BLK
BLK
ROTOR
MS-GF50/60/80VA
Horizontal vane motor
(MV1)
Vertical vane motor
(MV2)
Measure the resistance between the terminals with a tester.
(Temperature: 10 - 30°C)
Color of the lead wire Normal
Horizontal vane motor (MV1)
RED-BLK
313 ~ 375 Ω
Vertical vane motor (MV2) 268 ~ 322 Ω
MAIN
AUX.
BLK
RED WHT
FUSE
Hello! Crazy discounts, hurry up! We are Drop Dead Studio and our goal is to help companies achieve impressive sales results through automated marketing. I. [b]We sell fresh databases for GSA Search Engine Ranker.[/b] • The databases are updated monthly through 24/7 parsing and by connecting purchased databases from other sources. • You have the option to purchase a one-time fresh database or pay for a lifetime subscription for updates. [i][b]ATTENTION![/b][/i] 40% discount only until