<CAUTION> TEST POINT1 is high voltage.
10-9. TEST POINT DIAGRAM
Outdoor controller circuit board
PUHZ-SW40VHA PUHZ-SW40VHA-BS
PUHZ-SW50VHA PUHZ-SW50VHA-BS
CNS
S1-S2: 230V AC
CNAC
2 to 4: Power supply for
outdoor controller circuit
board (230V AC)
1 to 3: Power supply for
indoor and outdoor unit
connection wire
(230V AC)
21S4
Four-way valve
CN4
Transmission to out-
door power circuit
board (CN4)
CNDM
1 to 2: Input of low-level sound priority mode
1 to 3: Input of external contact point
SW7
Demand control setting
CN51
External signal output
• Compressor operating signal
• Abnormal signal
CN2
Connect to the outdoor
power circuit board (CN2)
1-5: Reception from
power circuit board
2-5: Zero cross signal
(0-5V DC)
3,4: Not used
6-5: 16V DC
7-5: 16V DC
CNF1
Connect to the fan motor
1-4: 250-330V DC
5-4: 15V DC
6-4: 0-6.5V DC
7-4: 15V DC(When stopped)
7.5V DC(When operated)
(0V-15V pulse)
63H
High pressure
switch
SW4
Test operation
SW6
Model select
SW5
Function switch
Model select
SW1
Forced defrost,
detect history record
reset, refrigerant
address
TH4
Thermistor
<Discharge>
TH3
Thermistor
<Liquid pipe>
TH7/6
Thermistor
<Ambient/
2-phase pipe>
CNDC
250-330V DC
(1+, 3-)
(Outdoor power circuit
board for RP35-140V)
(Noise filter circuit board
for RP100-250Y)
VFG
(Voltage between
right pins of PC5C
and PC5D, pin 3
and pin 4)
(Same as
(CNF1
7(+)-4(-))
VSP
(Voltage between pins
of C5A, C5B): DC 0V
(when stopped), DC 1–
6.5V
(when operated)
LEV-A,B
Linear expansion
valve
SWP
Pump down
SW8
Pipe replace
Wiring replace
CNM
Connect to A control
service tool
TH34
Thermistor
<Comp. surface>
63HS
High pressure
sensor
OCH525