Functions of the HART Analog Output Module Detailed Description of the Module
HART Analog Output Module ME1DA6HAI-Q 3 – 7
*1 A watchdog timer error occurs when program operations are not completed within the scheduled time due to a hard-
ware problem of the D/A module. In this case, the module ready signal (X0) and the D/A module RUN LED are turned off.
*2 The rate control and scaling function is activated.
*3 HART communication will be stopped without notification for output currents lesser than 2 mA. It will recover automati-
cally if the output current is 2 mA or higher again (refer to section 3.5.16).
*1 A watchdog timer error occurs when program operations are not completed within the scheduled time due to a hard-
ware problem of the D/A module. In this case, the module ready signal (X0) and the D/A module RUN LED are turned off.
*2 The rate control and scaling function is activated.
*3 HART communication will be stopped without notification for output currents lesser than 2 mA. It will recover automati-
cally if the output current is 2 mA or higher again (refer to section 3.5.16).
Setting
combination
Execution status
Analog output for HART
communication
*3
Enable
*3
Disable
CH output enable/disable
flags (Y1 to Y6)
Enable Disable Enable Disable
HOLD/CLEAR setting HOLD CLEAR
HOLD or
CLEAR
HOLD CLEAR
HOLD or
CLEAR
PLC CPU is in RUN
HART communication
Possible
*3
Not possible
Analog output
Analog value of the D/A
converted digital value
*2
Offset value
(4
mA)
Analog value of the D/A
converted digital value
*2
0 mA
PLC CPU is in STOP
HART communication
Possible
*3
Not possible
Analog output Last value Offset value (4 mA) Last value
Offset value
(4
mA)
0 mA
PLC CPU stop error
occurred
HART communication
Possible
*3
Not possible
Analog output Last value Offset value (4 mA) Last value
Offset value
(4 mA)
0 mA
Watchdog timer
error
*1
occurred
HART communication Not possible Not possible
Analog output 0 mA 0 mA
Tab. 3-6: HART communication and analog output in dependence of the setting combinations
(output range: 4 to 20 mA)
Setting
combination
Execution status
Analog output for HART
communication
*3
Enable
*3
Disable
CH output enable/disable
flags (Y1 to Y6)
Enable Disable Enable Disable
HOLD/CLEAR setting HOLD CLEAR
HOLD or
CLEAR
HOLD CLEAR
HOLD or
CLEAR
PLC CPU is in RUN
HART communication
Possible
*3
Not possible
Analog output
Analog value of the D/A
converted digital value
*2
0 mA
Analog value of the D/A
converted digital value
*2
0 mA
PLC CPU is in STOP
HART communication
Possible
*3
Not possible
Analog output Last value 0 mA Last value 0 mA
PLC CPU stop error
occurred
HART communication
Possible
*3
Not possible
Analog output Last value 0 mA Last value 0 mA
Watchdog timer
error
*1
occurred
HART communication Not possible Not possible
Analog output 0 mA 0 mA
Tab. 3-7: HART communication and analog output in dependence of the setting combinations
(output range: 0 to 20 mA)