I/O Signals for the Programmable Controller CPU Detailed Description of the Module
HART Analog Output Module ME1DA6HAI-Q 3 – 17
3.4.2 Details of I/O signals
Input signals
* When a watchdog timer error occurs, the RUN LED of the analog output module turns off.
Device No. Signal Name Description
X0 Module ready
When the programmable controller CPU is powered on or reset, this signal turns on
once the preparation for D/A conversion has been completed. Afterwards D/A con
-
version processing is performed.
When the analog output module has a watchdog timer error
*
, "Module ready" (X0)
turns OFF (In this case
D/A conversion processing is not performed.)
X9
Operating
condition setting
completed flag
This signal is used as an interlock condition to turn ON/OFF the Operating condition
setting request (Y9) when any of the following settings has been changed.
– Short-circuit detection setting (buffer memory address Un\G45)
– Rate control enable/disable setting (buffer memory address Un\G46)
– Disconnection detection/warning output setting (buffer memory address
Un\G47)
– Warning output settings (Un\G48)
– Scaling function setting (buffer memory address Un\G53)
– Increase/decrease digital limit value (buffer memory addresses Un\G70 to 81)
– Mode switching setting (buffer memory addresses Un\G158 and 159)
The operating condition setting completed flag (X9) turns OFF when the operating
condition setting request (Y9) is ON.
XD
Disconnection
detection signal
This input turns ON if a disconnection is detected on any channel.
Turning ON the disconnection detection clear request (YD) or operating condition
setting request (Y9) turns OFF the disconnection detection signal (XD).
XE
Warning output
signal
This signal turns ON if the digital input value on any of the channels enabled for
D/A conversion rises to or above the warning output upper limit value or falls below
the warning output lower limit value.
Turning ON the warning output clear request (YE) or operating condition setting
request (Y9) turns OFF the warning output signal (XE).
Tab. 3-10: Detailed description of the input signals (Signal direction ME1DA6HAI-Q CPU Module)
Performed by the ME1DA6HAI-Q
Performed by the sequence program
Module ready (X0)
Operation condition
setting completed
flag (X9)
Operation condition
setting request (Y9)
Performed by the ME1DA6HAI-Q
Performed by the sequence program
Disconnection detection
signal (XD)
Disconnection detection
clear request (YD)
Performed by the ME1DA6HAI-Q
Performed by the sequence program
Warning output
signal (XE)
Warning output clear
request (YE)