Water Cooled Series
The new water cooled outdoor unit offers a greater efficiency with a higher COP compared to our YGM
conventional model.
System Pipe Lengths
*1 When the outdoor unit is installed below the indoor unit, top-bottom differential is 40m
[131ft].
*1 When the outdoor unit is installed below the indoor unit, top-bottom differential is 40m
[131ft].
[8-36HP (WY series)] [8-24HP (WR2 series)]
Refrigerant Piping Lengths
Total length (8-12HP)
Total length (16-24HP)
Maximum allowable length
Maximum length between heat source and single/main BC controller
*Maximum total length is dependent upon the distance between
the outdoor unit and the single/main BC Controller.
Maximum length between single/main BC controller and indoor
Vertical differentials between units
Indoor/ heat source ( heat source higher)
Indoor/ heat source ( heat source lower)
Indoor/BC controller (single/main)
Indoor/indoor
Main BC Controller/Sub BC Controller
Maximum meters [Feet]
300-550 [984-1,804]
500-750 [1,640-2,460]
165 (190equivalent)
[541 (623)]
110 [360]
40-60 [131-196]
Maximum meters [Feet]
50 [164]
40 [131]
15 [49]
15 (10) [49 (32)]
15 (10) [49 (32)]
COP comparison (energy efficiency)
Downsized by approximately
57%*, the new models enable
an effective use of space.
*8/10/12HP
Compact design
Weight reduction
The reduction in weight leads to easy transportation and installation.
Heat source unit
Between indoor units
top-bottom
differential 15m [49ft]
(10m [32ft])
Between indoor unit
and BC controller
top-bottom differential 15m [49ft]
(10m [32ft])
Top-bottom
differentrial 50m [164ft]
*1
Furthest piping length
190m [623ft]
(equivalent length)
(actual length 165m
[541ft])
Indoor unit
Maximum length
between heat source
and single/main
BC controller
110m [360ft]
Between indoor unit and
BC controller top-
bottom differential
15m [49ft]
BC controllerBC controller
Heat source unit
Indoor unit
Between indoor units
top-bottom differential
15m [49ft]
Top-bottom differential
50m [164ft] *1
Furthest piping length
190m [623ft]
(equivalent length)
(actual length 165m [541ft])
8 10 12 16 18 20 22 24
YGM
Cooling 4.68 4.71 - 3.96 - 3.72 - -
PQHY
Heating 4.68 4.71 - 3.96 - 3.72 - -
YHM
Cooling 5.71 5.13 4.55 5.45 5.08 4.89 4.68 4.45
Heating 6.06 5.43 4.60 5.78 5.37 5.22 4.70 4.46
YGM
Cooling 4.68 4.71 - 3.96 - 3.72 - -
PQRY
Heating 5.33 5.43 - 4.54 - 4.63 - -
YHM
Cooling 5.65 5.08 4.50 5.40 5.03 4.84 4.63 4.41
Heating 6.06 5.43 4.60 5.78 5.37 5.22 4.70 4.46
mm (in.)
unit : kg
HP
COP comparison
8 10 12 16 18 20 22
PQHY
YGM 272 275 - 452 - 456 -
YHM 195 195 195 390 390 390 390
PQRY
YGM 263 266 - 440 - 444 -
YHM 181 181 181 362 362 362 362
HP
Weight comparison
P200, P250YGM (WY/WR2 series)
Height
1,800
(70-7/8)
Depth
550
(21-11/16)
Depth
550
(21-11/16)
Height
1,160
(45-11/16)
P200, P250, P300YHM (WY/WR2 series)
Width
880
(34-11/16)
Width
990
(39)
Refrigerant Piping Lengths
Total length (8-12HP)
Total length (16-36HP)
Maximum allowable length
Farthest indoor from first branch
Vertical differentials between units
Indoor/heat source (heat source higher)
Indoor/heat source (heat source lower)
Indoor/indoor
Maximum meters [Feet]
300 [984]
500 [1,640]
165 (190equivalent)
[541 (623)]
40 [131]
Maximum meters [Feet]
50 [164]
40 [131]
15 [49]
26
-
-
5.22
5.52
-
-
-
-
28
-
-
5.13
5.33
-
-
-
-
30
-
-
4.94
5.19
-
-
-
-
32
-
-
4.69
4.82
-
-
-
-
34
-
-
4.52
4.65
-
-
-
-
36
-
-
4.34
4.40
-
-
-
-
24
-
390
-
362
26
-
585
-
-
28
-
585
-
-
30
-
585
-
-
32
-
585
-
-
34
-
585
-
-
36
-
585
-
-
35
Outdoor Unit
Comments to this Manuals