ACTUATOR CONTROL
9
SUZ-KA25VA4.TH SUZ-KA35VA4.TH SUZ-KA50VA4.TH
SUZ-KA60VA4.TH
SUZ-KA71VA4.TH
9-3. RELATION BETWEEN MAIN SENSOR AND ACTUATOR
9-2. R.V. COIL CONTROL
Heating
. . . . . . . . . . . . . . . . .
ON
Cooling . . . . . . . . . . . . . . . . . OFF
Dry
. . . . . . . . . . . . . . . . . . . .
OFF
ON
OFF
ON
OFF
Outdoor fan
Compressor
5 seconds 15 seconds
ON
OFF
Compressor
Outdoor fan
motor
R.V.coil
ON
OFF
ON
OFF
<COOL>
5 seconds
<HEAT>
5 seconds
9-1. OUTDOOR FAN MOTOR CONTROL
The fan motor turns ON/OFF, interlocking with the compressor.
[ON] The fan motor turns ON 5 seconds before the compressor starts up.
[OFF] The fan motor turns OFF 15 seconds after the compressor has stopped running.
NOTE: The 4-way valve reverses for 5 seconds
right before start-up of the compressor.
Sensor Purpose
Actuator
Compressor
LEV
Outdoor fan
motor
R.V.coil
Indoor fan
motor
Discharge temperature
thermistor
Protection

Indoor coil temperature
thermistor
Cooling: Coil frost prevention
Heating: High pressure protection

Defrost thermistor Heating: Defrosting

Fin temperature thermistor Protection

Ambient temperature
thermistor
Cooling: Low ambient temperature operation

Outdoor heat exchanger
temperature thermistor
Cooling: Low ambient temperature operation

Cooling: High pressure protection

OCH545