Mitsubishi Electric PQRY-P72 Installation Manual

Browse online or download Installation Manual for Power adapters & inverters Mitsubishi Electric PQRY-P72. Mitsubishi Electric PQRY-P72 Installation manual User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 411
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews

Summary of Contents

Page 1

ModelsPURY-P72, P96, P120, P144T(Y)JMU-APURY-P168, P192, P216, P240, P264, P288T(Y)SJMU-A

Page 2 - Safety Precautions

- 1 -HWE09130 GBI Read Before Servicing[1] Read Before Servicing ...

Page 3

[ IV Remote Controller ] - 91 -HWE09130 GB<Entry found><No entries found>(C) To return to the normal displayWhen all the group settings a

Page 4

[ IV Remote Controller ]- 92 -HWE09130 GB2. Remote controller function selection via the ME remote controller(A) To delete group settings(B) To dele

Page 5 - Before installing the unit

[ IV Remote Controller ] - 93 -HWE09130 GB1Hr.NOT AVAILABLEVENTILATIONSTAND BY DEFROSTTIMERCHECK[Operation Procedures]1. Press the [ON/OFF] button o

Page 6

[ IV Remote Controller ]- 94 -HWE09130 GB[3] Interlock Settings via the MA Remote Controller1. LOSSNAY interlock setting (Make this setting only whe

Page 7 - Before the test run

[ IV Remote Controller ] - 95 -HWE09130 GB[4] Using the built-in Temperature Sensor on the Remote Controller1. Selecting the position of temperature

Page 8 - CONTENTS

- 96 -[ IV Remote Controller ]GBHWE09130

Page 9

- 97 -HWE09130 GBV Electrical Wiring Diagram[1] Electrical Wiring Diagram of the Outdoor Unit ...

Page 11

[ V Electrical Wiring Diagram ] - 99 -HWE09130 GBV Electrical Wiring Diagram[1] Electrical Wiring Diagram of the Outdoor Unit(1) PURY-P72TJMU-ADischa

Page 12 - [1] Read Before Servicing

[ V Electrical Wiring Diagram ]- 100 -HWE09130 GB(2) PURY-P96TJMU-ADischarge suction bypassSV2SV2SV9X10CN508black51LED1:Normal operation(Lit) /Er

Page 13

- 2 -

Page 14 - [3] Piping Materials

[ V Electrical Wiring Diagram ] - 101 -HWE09130 GB(3) PURY-P120, P144TJMU-AContactorBoxHeat exchanger capacity controlCooling/Heating switching4-way

Page 15 - Dimension A

[ V Electrical Wiring Diagram ]- 102 -HWE09130 GB(4) PURY-P72, P96YJMU-A+-++++21+++++Discharge suction bypassSV2SV2SV9CN508blackX1051Transformer BoxC

Page 16 - [5] Pipe Processing

[ V Electrical Wiring Diagram ] - 103 -HWE09130 GB(5) PURY-P120, P144YJMU-A+-++++21+++++ContactorBox12black875redwhiteU M3~VW48Heat exchanger capacit

Page 17 - [6] Brazing

[ V Electrical Wiring Diagram ]- 104 -HWE09130 GB[2] Electrical Wiring Diagram of the BC Controller(1) CMB-P104NU-G model(Red)CNTRZNR02ZNR01L2X21CN36

Page 18 - [7] Air Tightness Test

[ V Electrical Wiring Diagram ] - 105 -HWE09130 GB(2) CMB-P105,106NU-G modelsCN36(Green)L2L1ZNR02CN29(Green)CN28(Blue)CN27(Red)ZNR01CN05CN07S(SHIELD)

Page 19

[ V Electrical Wiring Diagram ]- 106 -HWE09130 GB(3) CMB-P108,1010NU-G models 2.The initial set values of switch on CONT.B are as fol

Page 20

[ V Electrical Wiring Diagram ] - 107 -HWE09130 GB(4) CMB-P1013,1016NU-G modelsZNR01ZNR02L1L2TB01M1M2TB02S(SHIELD)CN32CN33(Red)CN34(Black)CN35(Blue)C

Page 21 - [9] Refrigerant Charging

[ V Electrical Wiring Diagram ]- 108 -HWE09130 GB(5) CMB-P108,1010NU-GA modelsNote:1.TB02 is transmission terminal block. Never connect p

Page 22

[ V Electrical Wiring Diagram ] - 109 -HWE09130 GB(6) CMB-P1013,1016NU-GA modelsCNTR(Red)CN41(Green)CN40(Yellow)CN34(Black)CN33(Red)CN35(Blue)ZNR01ZN

Page 23

[ V Electrical Wiring Diagram ]- 110 -HWE09130 GB(7) CMB-P104NU-GB modelZNR02ZNR01CN29(Green)CN28(Blue)CN27(Red)CNTR(Red)CN07L1L2TB01CN13CN03M1M2S(SH

Page 24 - Restrictions

[ I Read Before Servicing ] - 3 -HWE09130 GBI Read Before Servicing[1] Read Before Servicing1. Check the type of refrigerant used in the system to b

Page 25

[ V Electrical Wiring Diagram ] - 111 -HWE09130 GB(8) CMB-P108NU-GB modelCN31(Yellow)CN33(Red)CN34(Black)CN35(Blue)CN30(Black)CN29(Green)CN28(Blue)CN

Page 26 - [1] System configuration

[ V Electrical Wiring Diagram ]- 112 -HWE09130 GB(9) CMB-P1016NU-HA modelL1L2GG(Blue)CNVCC1(Yellow)CN03 CN0222323111321(Black)CNP1123TRCN3813CNTR(Red

Page 27 - 2-core shielded cable

[ V Electrical Wiring Diagram ] - 113 -HWE09130 GB(10) CMB-P1016NU-HB modelL2L1GGNote:1.TB02 is transmission terminalblock.Never connect power lineto

Page 28

[ V Electrical Wiring Diagram ]- 114 -HWE09130 GB[3] Electrical Wiring Diagram of Transmission BoosterAC208V/230VLRedRed RedWhiteGreen250V 2AGroundi

Page 29

- 115 -HWE09130 GBVI Refrigerant Circuit[1] Refrigerant Circuit Diagram ...

Page 30

- 116 -

Page 31

[ VI Refrigerant Circuit ] - 117 -HWE09130 GBVI Refrigerant Ci rcuit[1] Refrigerant Circuit Diagram1. Outdoor unit(1) PURY-P72 model(2) PURY-P96 mode

Page 32 - Terminal

[ VI Refrigerant Circuit ]- 118 -HWE09130 GB(3) PURY-P120, P144 models63HS1O/STH4CJ2SV1aCP1CJ121S4b 21S4aST3ST163LSCV8aCV6aTH7TH3SV4aSV4bSV4dACCST6S

Page 33 - (4) CN3D

[ VI Refrigerant Circuit ] - 119 -HWE09130 GB(4) PURY-P168 model63HS1O/STH4CJ2SV1aCP1CJ121S4aST3ST163LSCV8aCV6aTH7TH3SV4aSV4bSV4dSV2ACCST6ST7ST17TH5T

Page 34

[ VI Refrigerant Circuit ]- 120 -HWE09130 GB(5) PURY-P192 model63HS1O/STH4CJ2SV1aCP1CJ121S4aST3ST163LSCV8aCV6aTH7TH3SV4aSV4dSV2ACCST6ST7ST17TH5TH6CV9

Page 35 - [4] Sample System Connection

[ I Read Before Servicing ]- 4 -HWE09130 GB[2] Necessary Tools and MaterialsPrepare the following tools and materials necessary for installing and se

Page 36 - [ II Restrictions ]

[ VI Refrigerant Circuit ] - 121 -HWE09130 GB(6) PURY-P216 model63HS1O/STH4CJ2SV1aCP1CJ121S4b 21S4aST3ST163LSCV8aCV6aTH7TH3SV4aSV4bSV4dACCST6ST7ST17T

Page 37 - Interlock operation with

[ VI Refrigerant Circuit ]- 122 -HWE09130 GB(7) PURY-P240, P264, P288 models63HS1O/STH4CJ2SV1aCP1CJ121S4b 21S4aST3ST163LSCV8aCV6aTH7TH3SV4aSV4bSV4dA

Page 38

[ VI Refrigerant Circuit ] - 123 -HWE09130 GB2. BC controller(1) CMB-P104 - P1016NU-GTH15 TH12LEV3LEV1TH16PS3PS1TH11SVM1Gas/Liquid separatorCheck val

Page 39 - GroupGroup

[ VI Refrigerant Circuit ]- 124 -HWE09130 GB(2) CMB-P108, P1013, P1016NU-GA (main)(3) CMB-P104, P108NU-GB (sub)TH15 TH12LEV3SVM2LEV1LEV2TH16PS3PS1T

Page 40

[ VI Refrigerant Circuit ] - 125 -HWE09130 GB(4) CMB-P1016V-HA (main)(5) CMB-P1016NU-HB (sub)TH15TH12Gas/Liquid separatorLEV3LEV1TH16PS1PS3TH11SVA,SV

Page 41

[ VI Refrigerant Circuit ]- 126 -HWE09130 GB[2] Principal Parts and Functions1. Outdoor unitPart nameSymbols (functions)Notes Usage Specifications Ch

Page 42

[ VI Refrigerant Circuit ] - 127 -HWE09130 GBThermis-torTH4(Discharge)1) Detects discharge air temper-ature2) Provides high-pressure pro-tectionD

Page 43

[ VI Refrigerant Circuit ]- 128 -HWE09130 GBHeater CH11 Heats the refrigerant in the com-pressorBelt heater P72 model1511 ohm 35WP96, P120, P144 mode

Page 44

[ VI Refrigerant Circuit ] - 129 -HWE09130 GB2. Indoor UnitPart Name Symbol (functions) Notes Usage Specification Check method Linear expan-sion val

Page 45

[ VI Refrigerant Circuit ]- 130 -HWE09130 GB3. BC controller(1) G typePart nameSymbols (functions)Part codeUsage Specifications Check methodPressure

Page 46

[ I Read Before Servicing ] - 5 -HWE09130 GB[3] Piping Materials1. Copper pipe materialsThe distinction between O-materials (Annealed) and 1/2H-mat

Page 47 - GBHWE09130

[ VI Refrigerant Circuit ] - 131 -HWE09130 GB(2) GA typePart nameSymbols (functions)Part codeUsage Specifications Check methodPressure sensorPS1 (Hig

Page 48

[ VI Refrigerant Circuit ]- 132 -HWE09130 GB(3) GB typePart nameSymbols (functions)Part codeUsage Specifications Check methodThermistor TH12(Bypass o

Page 49

[ VI Refrigerant Circuit ] - 133 -HWE09130 GB(4) HA typePart nameSymbols (functions)Part codeUsage Specifications Check methodPressure sensorPS1 (Hig

Page 50 - 41- 41

[ VI Refrigerant Circuit ]- 134 -HWE09130 GB(5) HB typePart nameSymbols (functions)Part codeUsage Specifications Check methodThermistor TH12(Bypass o

Page 51

- 135 -HWE09130 GBVII Control[1] Functions and Factory Settings of the Dipswitches ... 137[2] Cont

Page 52

- 136 -

Page 53 - Group Group

[ VII Control ] - 137 -HWE09130 GBVII Control[1] Functions and Factory Settings of the Dipswitches1. Outdoor unit(1) Control board1) Unless otherwi

Page 54

[ VII Control ]- 138 -HWE09130 GB1) Unless otherwise specified, leave the switch to OFF where indicated by "-," which may be set to OFF f

Page 55

[ VII Control ] - 139 -HWE09130 GB1) Unless otherwise specified, leave the switch to OFF where indicated by "-," which may be set to OFF

Page 56 - Indoor Indoor Indoor

[ VII Control ]- 140 -HWE09130 GB2) PURY-P96, P120, P144TJMU-AAll are set to OFF at factory shipment. Unless otherwise specified, set the switch t

Page 57

[ I Read Before Servicing ]- 6 -HWE09130 GB4. Thickness and refrigerant type indicated on the piping materialsAsk the pipe manufacturer for the symb

Page 58 - BC controller (sub)

[ VII Control ] - 141 -HWE09130 GB2. Function of the switch (Indoor unit)(1) Dipswitches1) SW1,3SW3-1OFFOFFOFFONONONOFFONOFFONOFFONOFFONVery LowLo

Page 59 - Pipe length between main BC

[ VII Control ]- 142 -HWE09130 GB(2) Address switchActual indoor unit address setting varies in different systems. Refer to the installation manual f

Page 60

[ VII Control ] - 143 -HWE09130 GB(2) ME remote controller (PAR-F27MEA-US)Set the address of the remote controller with the rotary switch.To set add

Page 61

[ VII Control ]- 144 -HWE09130 GB[2] Controlling the Outdoor Unit-1- Outline of Control MethodThe outdoor units are designated as OC and OS in the o

Page 62

[ VII Control ] - 145 -HWE09130 GB-5- Bypass ControlBypass solenoid valves (SV1a), which bypass the high- and low- pressure sides, perform the follow

Page 63

[ VII Control ]- 146 -HWE09130 GB(5) Bypass solenoid valve (SV5b) (ON = Open)-6- Compressor Frequency Control Depending on the capacity required, t

Page 64

[ VII Control ] - 147 -HWE09130 GB-7- Defrost Operation Control(1) Starting the defrost operationThe defrost cycle will start when all of the three

Page 65

[ VII Control ]- 148 -HWE09130 GB(2) Defrost operation(3) Stopping the defrost operationThe defrost cycle ends when 12 minutes have passed since the

Page 66

[ VII Control ] - 149 -HWE09130 GB-8- Refrigerant Recovery Control Refrigerant recovery is performed for each BC port during heating operation to pre

Page 67

[ VII Control ]- 150 -HWE09130 GB-9- Capacity Control of Outdoor Fan and Heat Exchanger(1) Control methodDepending on the capacity required, the rot

Page 68 - Outdoor Unit Components

[ I Read Before Servicing ] - 7 -HWE09130 GB[4] Storage of Piping1. Storage locationStore the pipes to be used indoors. (Warehouse at site or owner&a

Page 69

[ VII Control ] - 151 -HWE09130 GB-10- Control at Initial Start-upWhen started up for the first time before 12 hours have elapsed after power on, th

Page 70 - PURY-P72, P96YJMU-A

[ VII Control ]- 152 -HWE09130 GB(2) P168, P192, P216, P240, P264, P288 models1 Qj:Total capacity (models) codeRefer to the VII [1] 2. (1) Dipswit

Page 71 - PURY-P120, P144YJMU-A

[ VII Control ] - 153 -HWE09130 GB-11- Emergency Operation Mode1. Problems with the outdoor unitThe P168 through P240 models of unit have a mode th

Page 72 - PURY-P72YJMU-A

[ VII Control ]- 154 -HWE09130 GB2. Communication circuit failure or when some of the outdoor units are turned offThis is a temporary operation mode

Page 73 - PURY-P96YJMU-A

[ VII Control ] - 155 -HWE09130 GB-12- Control Method The control system configuration for the PURY models is shown in the chart below.Control method

Page 74

[ VII Control ]- 156 -HWE09130 GB-13- Cooling/heating Circuit Control and General Function of System EquipmentHigh-pressure gasHigh-pressure gasHeat

Page 75 - <HIGH VOLTAGE WARNING>

[ VII Control ] - 157 -HWE09130 GB-14- Operation Mode(1) Indoor unit operation modeThe operation mode can be selected from the following 6 modes usin

Page 76

[ VII Control ]- 158 -HWE09130 GB-15- DEMAND ControlCooling/heating operation can be prohibited (Thermo-OFF) by an external input to the indoor units

Page 77 - (R1,R5) Note.2

[ VII Control ] - 159 -HWE09130 GB[3] Controlling BC Controller1. Control of SV A, SV B, and SV CSV A, SV B, and SV C turn on or off depending

Page 78 - Transformer

[ VII Control ]- 160 -HWE09130 GB[4] Operation Flow Chart1. Mode determination flowchart(1) Indoor unit (cooling, heating, dry, fan mode) Start Rem

Page 79

[ I Read Before Servicing ]- 8 -HWE09130 GB[6] BrazingNo changes have been made in the brazing procedures. Perform brazing with special care to keep

Page 80 - 2. M-NET board

[ VII Control ] - 161 -HWE09130 GB(2) Outdoor unit (cooling only, heating only, cooling main and heating main modes) Start Breaker turned on Operati

Page 81

[ VII Control ]- 162 -HWE09130 GB(3) BC controller (cooling only, heating only, cooling main and heating main modes) StartBreaker turned on Operatio

Page 82

[ VII Control ] - 163 -HWE09130 GB2. Operations in each mode(1) Cooling operation Cooling operationTest run mode ON Thermostat ON 3-minute restart p

Page 83

[ VII Control ]- 164 -HWE09130 GB(2) Heating operation*Note 1. When the outdoor unit goes into the defrost mode, defrost command is sent to the BC co

Page 84 - 4. Fan board

[ VII Control ] - 165 -HWE09130 GB(3) Dry operationDry operation*Note 1*Note 2YESYESNONO 4-way valve OFF1. Outdoor unit (compressor) intermittent

Page 85

- 166 -[ VII Control ]GBHWE09130

Page 86 - 5. Noise Filter

- 167 -HWE09130 GBVIII Test Run Mode[1] Items to be checked before a Test Run...

Page 87

- 168 -

Page 88

[ VIII Test Run Mode ] - 169 -HWE09130 GBVIII Test Run Mode[1] Items to be checked before a Test Run(1) Check for refrigerant leak and loose cables a

Page 89 - [4] BC Controller Components

[ VIII Test Run Mode ]- 170 -HWE09130 GB[2] Test Run MethodThe figure shows an MA remote controller (PAR-21MAA). PAR-21MAAON/OFF FILTERCHECKOPERATION

Page 90

[ I Read Before Servicing ] - 9 -HWE09130 GB[7] Air Tightness TestNo changes have been made in the detection method. Note that a refrigerant leak det

Page 91 - Gas pipe (Indoor unit side)

[ VIII Test Run Mode ] - 171 -HWE09130 GB[3] Operating Characteristic and Refrigerant AmountIt is important to have a clear understanding of the char

Page 92 - 1. CMB-P1016NU-G, GA, HA

[ VIII Test Run Mode ]- 172 -HWE09130 GB3. Amount of refrigerant to be addedThe amount of refrigerant that is shown in the table below is factory-ch

Page 93

[ VIII Test Run Mode ] - 173 -HWE09130 GB(2) Example(3) Sample calculationBC controller(GA)BC controller(HB)BC controller(HB)IndooraCbHH′h1h1(P06 - P

Page 94

[ VIII Test Run Mode ]- 174 -HWE09130 GB[5] Refrigerant Amount Adjust Mode1. Procedures Follow the procedures below to add or extract refrigerant as

Page 95

[ VIII Test Run Mode ] - 175 -HWE09130 GBYESYESYESYESYESYESYESYESYESYESNONONONONONONONONOStartPut all indoor units in the test run mode and run the u

Page 96 - Remote Controller

[ VIII Test Run Mode ]- 176 -HWE09130 GB[6] The following symptoms are normal.SymptomsRemote controller displayCauseThe indoor unit does not start af

Page 97

[ VIII Test Run Mode ] - 177 -HWE09130 GB[7] Standard Operation Data (Reference Data)1. Single unit(1) Cooling only operationOperationOutdoor unit mo

Page 98

[ VIII Test Run Mode ]- 178 -HWE09130 GBOperationOutdoor unit modelPURY-P120TJMU-A PURY-P144TJMU-AModel name of BC controller CMB-P104NU-G CMB-P108NU

Page 99

[ VIII Test Run Mode ] - 179 -HWE09130 GB(2) Heating only operationOperationOutdoor unit modelPURY-P72TJMU-A PURY-P96TJMU-AModel name of BC controlle

Page 100 - [ IV Remote Controller ]

[ VIII Test Run Mode ]- 180 -HWE09130 GBOperationOutdoor unit modelPURY-P120TJMU-A PURY-P144TJMU-AModel name of BC controller CMB-P104NU-G CMB-P108NU

Page 101

[ I Read Before Servicing ]- 10 -HWE09130 GB[8] Vacuum Drying (Evacuation)1. Vacuum pump with a reverse-flow check valve (Photo1)To prevent the vacu

Page 102

[ VIII Test Run Mode ] - 181 -HWE09130 GB2. 2-unit combination(1) Cooling only operationOperationOutdoor unit modelPURY-P168TSJMU-APURY-P96TJMU-A PUR

Page 103

[ VIII Test Run Mode ]- 182 -HWE09130 GBOperationOutdoor unit modelPURY-P192TSJMU-APURY-P96TJMU-A PURY-P96TJMU-AModel name of BC controller CMB-P108N

Page 104 - HWE09130 GB

[ VIII Test Run Mode ] - 183 -HWE09130 GBOperationOutdoor unit modelPURY-P216TSJMU-APURY-P120TJMU-A PURY-P96TJMU-AModel name of BC controller CMB-P10

Page 105

[ VIII Test Run Mode ]- 184 -HWE09130 GBOperationOutdoor unit modelPURY-P240TSJMU-APURY-P120TJMU-A PURY-P120TJMU-AModel name of BC controller CMB-P10

Page 106 - Electrical Wiring Diagram

[ VIII Test Run Mode ] - 185 -HWE09130 GBOperationOutdoor unit modelPURY-P264TSJMU-APURY-P144TJMU-A PURY-P120TJMU-AModel name of BC controller CMB-P1

Page 107

[ VIII Test Run Mode ]- 186 -HWE09130 GBOperationOutdoor unit modelPURY-P288TSJMU-APURY-P144TJMU-A PURY-P144TJMU-AModel name of BC controller CMB-P10

Page 108 - (1) PURY-P72TJMU-A

[ VIII Test Run Mode ] - 187 -HWE09130 GB(2) Heating only operationOperationOutdoor unit modelPURY-P168TSJMU-APURY-P96TJMU-A PURY-P72TJMU-AModel name

Page 109 - (2) PURY-P96TJMU-A

[ VIII Test Run Mode ]- 188 -HWE09130 GBOperationOutdoor unit modelPURY-P192TSJMU-APURY-P96TJMU-A PURY-P96TJMU-AModel name of BC controller CMB-P108N

Page 110 - (3) PURY-P120, P144TJMU-A

[ VIII Test Run Mode ] - 189 -HWE09130 GBOperationOutdoor unit modelPURY-P216TSJMU-APURY-P120TJMU-A PURY-P96TJMU-AModel name of BC controller CMB-P10

Page 111 - PURY-P72,96YJMU-A(-BS)

[ VIII Test Run Mode ]- 190 -HWE09130 GBOperationOutdoor unit modelPURY-P240TSJMU-APURY-P120TJMU-A PURY-P120TJMU-AModel name of BC controller CMB-P10

Page 112 - PURY-P120,144YJMU-A(-BS)

ii HWE09130 GBSafety PrecautionsBefore installing the unit, thoroughly read the following safety precautions.Observe these safety precautions for yo

Page 113 - (1) CMB-P104NU-G model

[ I Read Before Servicing ] - 11 -HWE09130 GB7. NotesTo evacuate air from the entire systemApplying a vacuum through the check joints at the refrige

Page 114 - (2) CMB-P105,106NU-G models

[ VIII Test Run Mode ] - 191 -HWE09130 GBOperationOutdoor unit modelPURY-P264TSJMU-APURY-P144TJMU-A PURY-P120TJMU-AModel name of BC controller CMB-P1

Page 115 - (3) CMB-P108,1010NU-G models

[ VIII Test Run Mode ]- 192 -HWE09130 GBOperationOutdoor unit modelPURY-P288TSJMU-APURY-P144TJMU-A PURY-P144TJMU-AModel name of BC controller CMB-P10

Page 116 - (4) CMB-P1013,1016NU-G models

- 193 -HWE09130 GBIX Troubleshooting[1] Error Code Lists...

Page 118 - (Symbol explanation)

[ IX Troubleshooting ] - 195 -HWE09130 GBIX Troubleshooting[1] Error Code ListsError CodePrelimi-nary error codeError (prelim-inary) detail codeError

Page 119 - (7) CMB-P104NU-GB model

[ IX Troubleshooting ]- 196 -HWE09130 GB5102 1217 -Temperature sensor faultIndoor unit pipe tempera-ture (TH22)OOA processing unit pipe temperature (

Page 120 - (8) CMB-P108NU-GB model

[ IX Troubleshooting ] - 197 -HWE09130 GB5401 - - Temperature sensor fault O5701 - - Loose float switch connector O6201 - -Remote controller board f

Page 121

[ IX Troubleshooting ]- 198 -HWE09130 GBThe last digit in the check error codes in the 4000's and 5000's and two-digit detail codes indicat

Page 122 - (10) CMB-P1016NU-HB model

[ IX Troubleshooting ] - 199 -HWE09130 GB[2] Responding to Error Display on the Remote Controller1. Error CodeSerial communication error2. Error def

Page 123

[ IX Troubleshooting ]- 200 -HWE09130 GB1. Error CodeSerial communication error2. Error definition and error detection methodSerial communication er

Page 124 - Refrigerant Circuit

[ I Read Before Servicing ]- 12 -HWE09130 GB[9] Refrigerant Charging1. ReasonsR410A is a pseudo-azeotropic HFC blend (boiling point R32=-52°C[-62°F],

Page 125

[ IX Troubleshooting ] - 201 -HWE09130 GB1. Error CodeDischarge temperature fault2. Error definition and error detection method1) If the discharge

Page 126 - (2) PURY-P96 model

[ IX Troubleshooting ]- 202 -HWE09130 GB1. Error CodeLow pressure fault 2. Error definition and error detection methodWhen starting the compressor f

Page 127 - (3) PURY-P120, P144 models

[ IX Troubleshooting ] - 203 -HWE09130 GB1. Error CodeHigh pressure fault 1 (Outdoor unit)2. Error definition and error detection method1) If the

Page 128 - (4) PURY-P168 model

[ IX Troubleshooting ]- 204 -HWE09130 GB1. Error CodeHigh pressure fault 2 (Outdoor unit)2. Error definition and error detection methodIf the pressu

Page 129 - (5) PURY-P192 model

[ IX Troubleshooting ] - 205 -HWE09130 GB1. Error CodeDrain sensor submergence (Models with a drain sensor)2. Error definition and error detection m

Page 130 - (6) PURY-P216 model

[ IX Troubleshooting ]- 206 -HWE09130 GB1. Error CodeDrain sensor submergence (Models with a float switch)2. Error definition and error detection me

Page 131

[ IX Troubleshooting ] - 207 -HWE09130 GB1. Error CodeDrain pump fault (Models with a drain sensor)2. Error definition and error detection method1)

Page 132 - (1) CMB-P104 - P1016NU-G

[ IX Troubleshooting ]- 208 -HWE09130 GB1. Error CodeDrain pump fault (Models with a float switch)2. Error definition and error detection method1)

Page 133

[ IX Troubleshooting ] - 209 -HWE09130 GB1. Error CodeDrain sensor (Thd) fault2. Error definition and error detection methodIf the open or short ci

Page 134 - (5) CMB-P1016NU-HB (sub)

[ IX Troubleshooting ]- 210 -HWE09130 GB1. Error CodeWater leakage2. Cause, check method and remedyCheck that water does not leak from the pipes in

Page 135

[ I Read Before Servicing ] - 13 -HWE09130 GB[11] Characteristics of the Conventional and the New Refrigerants1. Chemical propertyAs with R22, the ne

Page 136 - 273 t

[ IX Troubleshooting ] - 211 -HWE09130 GB1. Error CodeOut-of-range outside air temperature 2. Error definition and error detection methodWhen the t

Page 137

[ IX Troubleshooting ]- 212 -HWE09130 GB1. Error CodeOpen phase2. Error definition and error detection methodAn open phase of the power supply (L1

Page 138

[ IX Troubleshooting ] - 213 -HWE09130 GB1. Error CodeOpen phase2. Error definition and error detection methodAn open phase of the power supply (L1

Page 139

[ IX Troubleshooting ]- 214 -HWE09130 GB1. Error Code<Transmission power supply fault Error detail code FF (Outdoor unit)>2. Error definition

Page 140

[ IX Troubleshooting ] - 215 -HWE09130 GB1. Error CodeIndoor unit fan operation error2. Error definition and error detection method1) During opera

Page 141

[ IX Troubleshooting ]- 216 -HWE09130 GB1. Error CodePower supply signal sync error2. Error definition and error detection methodThe frequency canno

Page 142

[ IX Troubleshooting ] - 217 -HWE09130 GB1. Error CodeRPM error/Motor error 2. Error definition and error detection methodLOSSNAYThe motor keep ru

Page 143

[ IX Troubleshooting ]- 218 -HWE09130 GB1. Error CodeAbnormal bus voltage drop (Detail code 108)2. Error definition and error detection methodIf Vdc

Page 144

[ IX Troubleshooting ] - 219 -HWE09130 GB1. Error CodeAbnormal bus voltage drop (Detail code 108)2. Error definition and error detection methodIf Vd

Page 145

[ IX Troubleshooting ]- 220 -HWE09130 GB1. Error CodeAbnormal bus voltage rise (Detail code 109)2. Error definition and error detection methodIf Vdc

Page 146

[ I Read Before Servicing ]- 14 -HWE09130 GB[12] Notes on Refrigerating Machine Oil1. Refrigerating machine oil in the HFC refrigerant systemHFC typ

Page 147

[ IX Troubleshooting ] - 221 -HWE09130 GB1. Error CodeVDC error (Detail code 110)2. Error definition and error detection methodBus voltage abnormali

Page 148

[ IX Troubleshooting ]- 222 -HWE09130 GB1. Error CodeLogic error (Detail code 111)2. Error definition and error detection methodH/W errorIf only the

Page 149

[ IX Troubleshooting ] - 223 -HWE09130 GB1. Error CodeLogic error (Detail code 111)2. Error definition and error detection methodH/W errorIf only th

Page 150 - 1) SW1,3

[ IX Troubleshooting ]- 224 -HWE09130 GB1. Error CodeHeatsink overheat protection2. Error definition and error detection methodWhen the heat sink te

Page 151 - Switch setting timing

[ IX Troubleshooting ] - 225 -HWE09130 GB1. Error CodeHeatsink overheat protection2. Error definition and error detection methodWhen the heat sink t

Page 152 - Rotary switch

[ IX Troubleshooting ]- 226 -HWE09130 GB1. Error CodeOverload protection2. Error definition and error detection methodIf the output current of "

Page 153 - -4- Control at Start-up

[ IX Troubleshooting ] - 227 -HWE09130 GB1. Error CodeOverload protection2. Error definition and error detection methodIf the output current of &qu

Page 154 - -5- Bypass Control

[ IX Troubleshooting ]- 228 -HWE09130 GB1. Error CodeIPM error (Detail code 101)2. Error definition and error detection methodIn the case of 4250P72

Page 155

[ IX Troubleshooting ] - 229 -HWE09130 GB1. Error CodeIPM error (Detail code 101)2. Error definition and error detection methodIn the case of 4250Ov

Page 156 - -7- Defrost Operation Control

[ IX Troubleshooting ]- 230 -HWE09130 GB1. Error CodeDCCT overcurrent (H/W detection) (Detail code 103)Instantaneous overcurrent (Detail code 106)Ove

Page 157

- 15 -HWE09130 GBII Restrictions[1] System configuration ...

Page 158

[ IX Troubleshooting ] - 231 -HWE09130 GB1. Error CodeInstantaneous overcurrent (Detail code 106)Overcurrent (effective value) (Detail code 107)2. E

Page 159

[ IX Troubleshooting ]- 232 -HWE09130 GB1. Error CodeOvercurrent error due to short-circuited motor (Detail code 105)2. Error definition and error d

Page 160

[ IX Troubleshooting ] - 233 -HWE09130 GB1. Error CodeReturn air temperature sensor (TH21) fault (Indoor unit)Return air temperature sensor (TH4) fau

Page 161

[ IX Troubleshooting ]- 234 -HWE09130 GB1. Error CodeHeat exchanger outlet temperature sensor (TH3) fault (Outdoor unit)Discharge temperature sensor

Page 162 - -11- Emergency Operation Mode

[ IX Troubleshooting ] - 235 -HWE09130 GB1. Error CodeHeatsink temperature sensor (THHS) fault (Detail code 01)2. Error definition and error detecti

Page 163 - Emergency

[ IX Troubleshooting ]- 236 -HWE09130 GB1. Error CodeLiquid inlet temperature sensor (TH11) fault (BC controller)Bypass outlet temperature sensor (TH

Page 164 - -12- Control Method

[ IX Troubleshooting ] - 237 -HWE09130 GB1. Error CodeHigh-pressure sensor fault (63HS1)2. Error definition and error detection methodIf the high p

Page 165

[ IX Troubleshooting ]- 238 -HWE09130 GB1. Error CodeHigh-pressure sensor fault (Outdoor unit HPS/BC controller PS1)Intermediate pressure sensor faul

Page 166 - -14- Operation Mode

[ IX Troubleshooting ] - 239 -HWE09130 GB1. Error CodeACCT sensor fault (Detail code 115)2. Error definition and error detection methodWhen the form

Page 167 - -15- DEMAND Control

[ IX Troubleshooting ]- 240 -HWE09130 GB1. Error CodeACCT sensor fault (Detail code 115)2. Error definition and error detection methodWhen the formu

Page 169

[ IX Troubleshooting ] - 241 -HWE09130 GB1. Error CodeDCCT sensor circuit fault (Detail code118)2. Error definition and error detection methodWhen a

Page 170

[ IX Troubleshooting ]- 242 -HWE09130 GB1. Error CodeOpen-circuited IPM/Loose ACCT connector (Detail code 119)2. Error definition and error detectio

Page 171

[ IX Troubleshooting ] - 243 -HWE09130 GB1. Error CodeFaulty ACCT wiring (Detail code 120)2. Error definition and error detection methodPresence of

Page 172 - (1) Cooling operation

[ IX Troubleshooting ]- 244 -HWE09130 GB1. Error CodeTemperature sensor fault2. Error definition and error detection methodA short-circuit or an op

Page 173

[ IX Troubleshooting ] - 245 -HWE09130 GB1. Error CodeLoose float switch connector2. Error definition and error detection methodDetection of the dis

Page 174 - (3) Dry operation

[ IX Troubleshooting ]- 246 -HWE09130 GB1. Error CodeAddress overlaps2. Error definition and error detection methodAn error in which signals from mo

Page 175

[ IX Troubleshooting ] - 247 -HWE09130 GB1. Error CodeTransmission processor hardware error2. Error definition and error detection methodAlthough &q

Page 176 - Test Run Mode

[ IX Troubleshooting ]- 248 -HWE09130 GB1. Error CodeTransmission line bus busy error 2. Error definition and error detection methodGenerated error

Page 177

[ IX Troubleshooting ] - 249 -HWE09130 GB1. Error CodeNo ACK error2. Error definition and error detection methodThe error is detected when no acknow

Page 178

[ IX Troubleshooting ]- 250 -HWE09130 GB1. Error CodeNo ACK error2. Error definition and error detection methodThe error is detected when no acknowl

Page 179 - [ VIII Test Run Mode ]

[ II Restrictions ] - 17 -HWE09130 GBII Restrictions[1] System configuration1. Table of compatible indoor unitsThe table below summarizes the types o

Page 180

[ IX Troubleshooting ] - 251 -HWE09130 GB1. Error CodeNo ACK error2. Error definition and error detection methodThe error is detected when no acknow

Page 181

[ IX Troubleshooting ]- 252 -HWE09130 GB1. Error CodeNo ACK error2. Error definition and error detection methodThe error is detected when no acknowl

Page 182 - (3) Sample calculation

[ IX Troubleshooting ] - 253 -HWE09130 GB1. Error CodeNo ACK error2. Error definition and error detection methodThe error is detected when no acknow

Page 183 - Self-diagnosis swithes on Tc

[ IX Troubleshooting ]- 254 -HWE09130 GB1. Error CodeNo ACK error2. Error definition and error detection methodThe error is detected when no acknowl

Page 184

[ IX Troubleshooting ] - 255 -HWE09130 GB1. Error CodeNo ACK error2. Error definition and error detection methodThe error is detected when no acknow

Page 185

[ IX Troubleshooting ]- 256 -HWE09130 GB1. Error CodeNo ACK error2. Error definition and error detection methodThe error is detected when no acknowl

Page 186

[ IX Troubleshooting ] - 257 -HWE09130 GB1. Error CodeNo ACK error2. Error definition and error detection methodThe error is detected when no acknow

Page 187

[ IX Troubleshooting ]- 258 -HWE09130 GB1. Error CodeNo response error2. Error definition and error detection methodWhen no response command is ret

Page 188

[ IX Troubleshooting ] - 259 -HWE09130 GB1. Error CodeMA controller signal reception error (No signal reception)2. Error definition and error detect

Page 189

[ IX Troubleshooting ]- 260 -HWE09130 GB1. Error CodeMA remote controller signal transmission error (Synchronization error)2. Error definition and e

Page 190

[ II Restrictions ]- 18 -HWE09130 GB[2] Types and Maximum allowable Length of Cables1. Wiring work (1) Notes1) Have all electrical work performed b

Page 191

[ IX Troubleshooting ] - 261 -HWE09130 GB1. Error CodeMA remote controller signal transmission error (Hardware error)2. Error definition and error d

Page 192

[ IX Troubleshooting ]- 262 -HWE09130 GB1. Error CodeMA controller signal reception error (Start bit detection error)2. Error definition and error d

Page 193

[ IX Troubleshooting ] - 263 -HWE09130 GB1. Error CodeTotal capacity error2. Error definition and error detection methodThe model total of indoor un

Page 194

[ IX Troubleshooting ]- 264 -HWE09130 GB1. Error CodeCapacity code setting error2. Error definition and error detection method Connection of incompa

Page 195

[ IX Troubleshooting ] - 265 -HWE09130 GB1. Error CodeWrong number of connected units2. Error definition and error detection method The number of co

Page 196

[ IX Troubleshooting ]- 266 -HWE09130 GB1. Error CodeAddress setting error2. Error definition and error detection methodErroneous setting of OC unit

Page 197

[ IX Troubleshooting ] - 267 -HWE09130 GB1. Error CodePort setting error2. Error definition and error detection methodThe port with wrong number is

Page 198

[ IX Troubleshooting ]- 268 -HWE09130 GB1. Error CodeConnection information signal transmission/reception error2. Error definition and error detecti

Page 199

[ IX Troubleshooting ] - 269 -HWE09130 GB1. Error CodeFunction setting error (incorrect resistor connection)2. Error source, cause, check method and

Page 200

[ IX Troubleshooting ]- 270 -HWE09130 GB1. Error CodeModel setting error2. Error source, cause, check method and remedy7117Error source Cause Check

Page 201

[ II Restrictions ] - 19 -HWE09130 GB2) Remote controller wiring*1 MA remote controller refers to MA remote controller (PAR-20MAU, PAR-21MAA), MA

Page 202 - Troubleshooting

[ IX Troubleshooting ] - 271 -HWE09130 GB1. Error CodeIncompatible unit combination2. Error definition and error detection methodThe check code will

Page 203

[ IX Troubleshooting ]- 272 -HWE09130 GB-1- Troubleshooting according to the remote controller malfunction or the external input errorIn the case of

Page 204 - Remote controller

[ IX Troubleshooting ] - 273 -HWE09130 GBIn the case of MA remote controller2. PhenomenaWhen the remote controller operation SW is turned on, the ope

Page 205

[ IX Troubleshooting ]- 274 -HWE09130 GBIn the case of MA remote controller3. Phenomena"HO" or "PLEASE WAIT" display on the remot

Page 206

[ IX Troubleshooting ] - 275 -HWE09130 GBFlow chartEven if the operation button on the remote controller is pressed, the indoor and the outdoor units

Page 207

[ IX Troubleshooting ]- 276 -HWE09130 GBIn case of ME remote controller1. PhenomenaEven if the operation button on the remote controller is pressed,

Page 208 - 0403 (TJMU-A) (Indoor unit)

[ IX Troubleshooting ] - 277 -HWE09130 GBIn case of ME remote controller2. PhenomenaWhen the remote controller operation SW is turned on, a temporary

Page 209 - 0403 (YJMU-A) (Indoor unit)

[ IX Troubleshooting ]- 278 -HWE09130 GBIn case of ME remote controller3. Phenomena"HO" display on the remote controller does not disappear

Page 210

[ IX Troubleshooting ] - 279 -HWE09130 GBIn case of ME remote controller4. Phenomena"88" appears on the remote controller when the address

Page 211

[ IX Troubleshooting ]- 280 -HWE09130 GBBoth for MA remote controller and ME remote controller1. PhenomenaAlthough cooling operation starts with the

Page 212 - +0,-0.15

[ II Restrictions ]- 20 -HWE09130 GB2. M-NET Address settings(1) Address settings tableThe need for address settings and the range of address settin

Page 213

[ IX Troubleshooting ] - 281 -HWE09130 GBCause Check method and remedy4. Long piping lengthThe cooling capacity varies greatly depending on the press

Page 214

[ IX Troubleshooting ]- 282 -HWE09130 GB2. PhenomenaAlthough heating operation starts with the normal remote controller display, the capacity is not

Page 215

[ IX Troubleshooting ] - 283 -HWE09130 GBCause Check method and remedy2. Indoor unit LEV malfunctionInsufficient refrigerant flows due to LEV malfunc

Page 216

[ IX Troubleshooting ]- 284 -HWE09130 GB3. PhenomenaOutdoor unit stops at times during operation.(1) Cause, check method and remedyCause Check metho

Page 217

[ IX Troubleshooting ] - 285 -HWE09130 GB[3] Investigation of Transmission Wave Shape/Noise1. M-NET transmissionControl is performed by exchanging si

Page 218

[ IX Troubleshooting ]- 286 -HWE09130 GB(3) Check method and remedy1) Measures against noiseCheck the followings when noise exists on the wave or

Page 219

[ IX Troubleshooting ] - 287 -HWE09130 GB2. MA remote controller transmissionThe communication between the MA remote controller and the indoor unit

Page 220 - Short detection

[ IX Troubleshooting ]- 288 -HWE09130 GB[4] Troubleshooting Principal Parts-1- High-Pressure Sensor (63HS1, PS1, PS3)1. Compare the pressure that is

Page 221 - 4102 (TJMU-A)

[ IX Troubleshooting ] - 289 -HWE09130 GB-2- Low-Pressure Sensor (63LS)1. Compare the pressure that is detected by the low pressure sensor, and the

Page 222 - 4102 (YJMU-A)

[ IX Troubleshooting ]- 290 -HWE09130 GB-3- Solenoid ValveCheck whether the output signal from the control board and the operation of the solenoid va

Page 223

iiHWE09130 GBWARNINGSecurely attach the terminal block cover (panel) to the unit.If the terminal block cover (panel) is not installed properly, dust a

Page 224

[ II Restrictions ] - 21 -HWE09130 GBUnit or controller Sym-bolAddress setting rangeSetting method Factory address settingSystem controllerGroup remo

Page 225 - (TJMU-A)

[ IX Troubleshooting ] - 291 -HWE09130 GBST1CV8aCV6aTH7TH3SV4aSV4bSV4dTH6CV9aCV10aSV5bCV4aCV2aCV7aCV3a CV5aHEXSolenoid Valves BlockBV1BV2SV5cRefriger

Page 226

[ IX Troubleshooting ]- 292 -HWE09130 GB123456123456Pin-face toolSV4dSV4dSV4cSV4bSV4aValveSolenoid valveSolenoid valve coilPin-face toolTightening to

Page 227

[ IX Troubleshooting ] - 293 -HWE09130 GB123452345ST1CV8aCV6aTH7TH3SV4aSV4bSV4dTH6CV9aCV5aSV5bCV4aCV2aCV7aCV6bCV5bHEX1SV4cBV1BV2SV5cCV3aCV7bCV2bCV4bH

Page 228 - (YJMU-A)

[ IX Troubleshooting ]- 294 -HWE09130 GB(5) In the case of SV5b (Bypass valve) This solenoid valve closes when energized (when the relay is on).This

Page 229

[ IX Troubleshooting ] - 295 -HWE09130 GB-4- Outdoor Unit Fan(1) Fan motorTo check the revolution of the fan, check the inverter output state on the

Page 230

[ IX Troubleshooting ]- 296 -HWE09130 GBYESYESYESYESYESNONONONOReplace the control board.Replace 52F.Is the wiring between the FAN board, 52F, and fa

Page 231

[ IX Troubleshooting ] - 297 -HWE09130 GB-5- LEVLEV operationLEV are stepping-motor-driven valves that operate by receiving the pulse signals from th

Page 232

[ IX Troubleshooting ]- 298 -HWE09130 GB(2) Judgment methods and possible failure modeMalfunction modeJudgment method RemedyMicrocomputer driver cir

Page 233 - 4230 (TJMU-A)

[ IX Troubleshooting ] - 299 -HWE09130 GB-6- Troubleshooting Principal Parts of BC Controller1. Pressure sensorTroubleshooting flow chart for pressur

Page 234 - 4230 (YJMU-A)

[ IX Troubleshooting ]- 300 -HWE09130 GB1) BC controller: Phenomena when the pressure sensor is connected wrongly (reverse connection of P1 and P3)

Page 235 - 4240 (TJMU-A)

[ II Restrictions ]- 22 -HWE09130 GB(2) Power supply switch connector connection on the outdoor unit(Factory setting: The male power supply switch c

Page 236 - 4240 (YJMU-A)

[ IX Troubleshooting ] - 301 -HWE09130 GB2. Temperature sensorPull out the thermistor connector in trouble from the board.Measure the temperature of

Page 237

[ IX Troubleshooting ]- 302 -HWE09130 GB1) For the connectors on the board, TH11 and TH12 are connected to CN10, and TH15 and TH16 are connected to

Page 238

[ IX Troubleshooting ] - 303 -HWE09130 GB3. Troubleshooting flow chart for LEV Solenoid valve(1) LEVCheck whether the electric expansion valve and th

Page 239 - 4250 (TJMU-A)

[ IX Troubleshooting ]- 304 -HWE09130 GB1) BC controller: Phenomena when LEV is connected wrongly (reverse connection of LEV1 and LEV3) to the boar

Page 240 - 4250 (YJMU-A)

[ IX Troubleshooting ] - 305 -HWE09130 GBSelf-diagnosis LED12345678910ON12345678910ON12345678910ON12345678910ON12345678910ON12345678910ON12345678910O

Page 241 - 4260 (YJMU-A)

[ IX Troubleshooting ]- 306 -HWE09130 GBTroubleshooting flow chart for solenoid valve body665432154321251346ToLEVLED10 kStartBrownRedBlueOrangeYellow

Page 242

[ IX Troubleshooting ] - 307 -HWE09130 GB(2) Solenoid valve (SVA, SVB, SVC)Stop the operation of the applied BC remote controller system.Faulty judg

Page 243

[ IX Troubleshooting ]- 308 -HWE09130 GBCheck whether the BC board output signal corresponds with the solenoid valve operation correspond.1) SVA, S

Page 244 - 5110 (YJMU-A)

[ IX Troubleshooting ] - 309 -HWE09130 GB4. BC controller transformer* Before measuring the resistance, pull out the connector.Normal AbnormalCNTR(1

Page 245

[ IX Troubleshooting ]- 310 -HWE09130 GB-7- Inverter (TJMU-A)Replace only the compressor if only the compressor is found to be defective. (Overcurre

Page 246

[ II Restrictions ] - 23 -HWE09130 GB(5) Various start-stop controls (Indoor unit settings)Each indoor unit (or group of indoor units) can be contro

Page 247

[ IX Troubleshooting ] - 311 -HWE09130 GBError display/failure condition Measure/inspection item[1] Inverter related errors4250, 4255, 4220, 4225, 42

Page 248 - 5301 (TJMU-A)

[ IX Troubleshooting ]- 312 -HWE09130 GB(2) Inverter output related troublesItems to be checked Phenomena Remedy[1]Check the INV board error detecti

Page 249 - 5301 (YJMU-A)

[ IX Troubleshooting ] - 313 -HWE09130 GBItems to be checked Phenomena Remedy[3]Check whether the inverter is damaged.(No load)<P72 model> 1) I

Page 250

[ IX Troubleshooting ]- 314 -HWE09130 GB[4]Check whether the inverter is damaged.(During com-pressor opera-tion)Put the outdoor unit into oper-ation.

Page 251

[ IX Troubleshooting ] - 315 -HWE09130 GB(3) Trouble treatment when the main power breaker is tripped.Items to be checked Phenomena Remedy[1] Perfor

Page 252

[ IX Troubleshooting ]- 316 -HWE09130 GB(4) Simple checking procedure for individual components of main inverter circuitBefore checking, turn the pow

Page 253

[ IX Troubleshooting ] - 317 -HWE09130 GB(5) Intelligent power module (P96, P120, P144 models)Measure resistances between each pair of terminals on

Page 254

[ IX Troubleshooting ]- 318 -HWE09130 GB(6) Diode stack (P96, P120, P144 models)Measure resistances between each pair of terminals on the diode stac

Page 255

[ IX Troubleshooting ] - 319 -HWE09130 GBINV board external diagramFaston terminals have a locking function. Make sure the cable heads are securely l

Page 256

[ IX Troubleshooting ]- 320 -HWE09130 GB-7- Inverter (YJMU-A)Replace only the compressor if only the compressor is found to be defective. Replace o

Page 257

[ II Restrictions ]- 24 -HWE09130 GBCAUTION1) Wiring should be covered by insulation tube with supplementary insulation.2) Use relays or switches

Page 258

[ IX Troubleshooting ] - 321 -HWE09130 GBError display/failure condition Measure/inspection item[1] Inverter related errors4250, 4255, 4220, 4225, 42

Page 259

[ IX Troubleshooting ]- 322 -HWE09130 GB(2) Inverter output related troublesItems to be checked Phenomena Remedy[1]Check the INV board er-ror detect

Page 260

[ IX Troubleshooting ] - 323 -HWE09130 GBItems to be checked Phenomena Remedy[4]Check whether the inverter is damaged.(During com-pressor opera-tion)

Page 261

[ IX Troubleshooting ]- 324 -HWE09130 GB(3) Trouble treatment when the main power breaker is tripped(4) Trouble treatment when the main power earth

Page 262

[ IX Troubleshooting ] - 325 -HWE09130 GB(5) Simple checking procedure for individual components of main inverter circuitBefore inspecting the inside

Page 263

[ IX Troubleshooting ]- 326 -HWE09130 GBINV board external diagramJudgment value (reference)Black ( + )SC-P1 FT-N SC-L1 SC-L2 SC-L3Red (-)SC-P1 - - 5

Page 264

[ IX Troubleshooting ] - 327 -HWE09130 GB-8- Control Circuit (TJMU-A)(1) Control power source function block1) PURY-P72TJMU-AOutdoor unit Power so

Page 265

[ IX Troubleshooting ]- 328 -HWE09130 GB2) PURY-P96, P120, P144TJMU-A * MA remote controllers and ME remote controllers cannot be used together.(Bo

Page 266

[ IX Troubleshooting ] - 329 -HWE09130 GB(2) Troubleshooting transmission power circuit of outdoor unit1) PURY-P72TJMU-ACheck the voltage between

Page 267

[ IX Troubleshooting ]- 330 -HWE09130 GB2) PURY-P96, P120, P144TJMU-ADC24 ~ 30V YES NO NO NO NO Check the voltage at the indoor/outdoor transmissi

Page 268

[ II Restrictions ] - 25 -HWE09130 GB(8) Demand control 1) General outline of controlDemand control is performed by using the external signal input

Page 269

[ IX Troubleshooting ] - 331 -HWE09130 GB-8- Control Circuit (YJMU-A)(1) Control power source function block1) PURY-P72, P96, P120, P144YJMU-AOutdo

Page 270

[ IX Troubleshooting ]- 332 -HWE09130 GB(2) Troubleshooting transmission power circuit of outdoor unit1) PURY-P72, P96, P120, P144YJMU-AYESYESYESY

Page 271

[ IX Troubleshooting ] - 333 -HWE09130 GB[5] Refrigerant Leak1. Leak spot: In the case of extension pipe for indoor unit (Cooling season)1) Mount

Page 272

[ IX Troubleshooting ]- 334 -HWE09130 GB3. Leak spot: In the case of extension pipe for indoor unit (Heating season)(1) Run all the indoor units in

Page 273

[ IX Troubleshooting ] - 335 -HWE09130 GB[6] Compressor Replacement Instructions1. Compressor Replacement Instructions Transformerbox*1Follow the

Page 274

[ IX Troubleshooting ]- 336 -HWE09130 GB Compressor cover (top) 4. Remove the compressor cover (top). 5. Remove the compressor wires, compressor

Page 275

[ IX Troubleshooting ] - 337 -HWE09130 GBNO. Parts to be serviced1 Solenoid valve block ASSY (SV4a, SV4b, SV4d)2 Check valve (CV4a)3 Check valve (CV

Page 276 - 2 branches merge

[ IX Troubleshooting ]- 338 -HWE09130 GBHeat exchanger③⑦ A (φ12.7 [1/2"])④⑦ B(φ15.88 [5/8"])④⑦ C(φ19.05 [3/8"])① Coil cover, Solenoid

Page 277

[ IX Troubleshooting ] - 339 -HWE09130 GB(2) Check valve (CV4a, CV6a, CV8a, CV9a, CV10a) replacement procedures① Remove the Solenoid valve block ASS

Page 278

[ IX Troubleshooting ]- 340 -HWE09130 GBDetailed View of Part A②③ Brazing or debrazing pipesL(φ15.88 [5/8"])M(φ28.6 [1-1/8"])③ Check valve

Page 279

[ II Restrictions ]- 26 -HWE09130 GB[4] Sample System ConnectionExamples of typical system connection are shown on pages [5] to [7]. Refer to the Ins

Page 280

[ IX Troubleshooting ] - 341 -HWE09130 GB2. Solenoid valve block ASSY (SV4a, SV4b, SV4c, SV4d), Check valve (CV4a, CV6a, CV8a, CV9a, CV10a) replacem

Page 281

[ IX Troubleshooting ]- 342 -HWE09130 GB④⑦ Brazing or debrazing pipes⑤ Removing Solenoid valve block ASSYE(φ28.6 [1-1/8"])F(φ9.52 [3/8"])

Page 282 - Is the error code 7102

[ IX Troubleshooting ] - 343 -HWE09130 GB(2) Check valve (CV4a, CV6a, CV8a, CV9a, CV10a) replacement procedures① Remove the solenoid valve block ASS

Page 283

[ IX Troubleshooting ]- 344 -HWE09130 GBDetailed View of Part A②③Brazing or debrazing pipesN(φ15.88 [5/8"])O(φ28.6 [1-1/8"])③Check valve r

Page 284 - Flow chart

[ IX Troubleshooting ] - 345 -HWE09130 GB3. Solenoid valve block ASSY (SV4a, SV4b, SV4d), Check valve (CV4a, CV6a, CV8a, CV9a) replacement instructi

Page 285

[ IX Troubleshooting ]- 346 -HWE09130 GB* Refer to the next page for Check valve (CV4a, CV6a, CV8a, CV9a) replacement procedures. B AHeat exchangerCo

Page 286 - Connector contact failure

[ IX Troubleshooting ] - 347 -HWE09130 GB I(ø25.4[1”])2 3 J(ø15.88[5/8”])2 3 L(ø15.88[5/8”])2 3 K(ø19.05[3/4”])2 3 M(ø1

Page 287

[ IX Troubleshooting ]- 348 -HWE09130 GBDetailed View of Part AAngle of the pipes when replacing CV8a,CV9a (Figure as viewed from point N)CV4aCV8aCV9

Page 288

[ IX Troubleshooting ] - 349 -HWE09130 GB4. Solenoid valve (SV1a), Capillary tube ASSY (CP1) replacement instructions1. Applicable modelsPURY-P72TJM

Page 289 - Evaporating temperature Te

[ IX Troubleshooting ]- 350 -HWE09130 GB[7] Servicing the BC controller1. Service panel2. Control box*Special care must be taken when replacing heavy

Page 290

[ II Restrictions ] - 27 -HWE09130 GB

Page 291 - Condensing temperature Tc

[ IX Troubleshooting ] - 351 -HWE09130 GB3. Thermistor (liquid pipe/gas pipe temperature detection)4. Pressure sensor*Special care must be taken whe

Page 292

[ IX Troubleshooting ]- 352 -HWE09130 GB5. LEV6. Solenoid valveWork procedure Explanatory figure(1) Remove the service panel.(Refer to 1. 1) - 3)(2)

Page 293

[ IX Troubleshooting ] - 353 -HWE09130 GB[8] Troubleshooting Using the Outdoor Unit LED Error DisplayIf the LED error display appear as follows while

Page 294 - [Without transmission]

- 354 -[ IX Troubleshooting ]GBHWE09130

Page 295

- 355 -HWE09130 GBX LED Monitor Display on the Outdoor Unit Board[1] How to Read the LED on the Service Monitor ...

Page 296

- 356 -

Page 297 - Vout 0.5 ~ 3.5 V

[ X LED Monitor Display on the Outdoor Unit Board ] - 357 -HWE09130 GBX LED Monitor Display on the Outdoor Unit Board[1] How to Read the LED on the S

Page 298 - Vout 0.5 ~ 3.5 V

[ X LED Monitor Display on the Outdoor Unit Board ]- 358 -HWE09130 GB3. Time data storage functionThe outdoor unit has a simple clock function that

Page 299 - -3- Solenoid Valve

[ X LED Monitor Display on the Outdoor Unit Board ]- 359 -HWE09130ILED Monitor D isplay on the Outdoor U nit BoardLED monitor displayCurrent dataNo.S

Page 300 - SV4d SV4b SV4a SV4d SV4b SV4a

[ X LED Monitor Display on the Outdoor Unit Board ]- 360 -HWE0913011 1101000000External signal(Open input contact point)Contact point de-mandLow-nois

Page 301

- 28 -[ II Restrictions ]GBHWE09130[5] An Example of a System to which an MA Remote Controller is connected1. System with one outdoor unit (automati

Page 302

[ X LED Monitor Display on the Outdoor Unit Board ]- 361 -HWE0913024 0001100000Indoor unit thermo-statTop Unit No. 1 Unit No. 2 Unit No. 3 Unit No. 4

Page 303

[ X LED Monitor Display on the Outdoor Unit Board ]- 362 -HWE0913045 1011010000 TH4 -99.9 to 999.9 A A The unit is [°C]46 0111010000 TH3 -99.9 to 999

Page 304 - 12345678 9 10

[ X LED Monitor Display on the Outdoor Unit Board ]- 363 -HWE0913072 000100100073 100100100074 010100100075 110100100076 001100100077 101100100078 01

Page 305 - Does 52F operate on the

[ X LED Monitor Display on the Outdoor Unit Board ]- 364 -HWE0913094 0111101000 AK 0000 to 9999 A A95 1111101000 FAN 0000 to 9999 A A Fan output [ %

Page 306

[ X LED Monitor Display on the Outdoor Unit Board ]- 365 -HWE09130117 1010111000COMP Operation timeUpper 4 digits0000 to 9999 A AThe unit is[ h ]118

Page 307 - Linear Expansion Valve

[ X LED Monitor Display on the Outdoor Unit Board ]- 366 -HWE09130132 0010000100Relay out-put display BC(Main)Top SVM1 SVM2 SVM1b SVM2bBBottom133 101

Page 308 - Pressure 0MPa [0psi]

[ X LED Monitor Display on the Outdoor Unit Board ]- 367 -HWE09130143 1111000100Relay out-put display BC(Sub2)Top SVA1 SVB1 SVC1 SVA2 SVB2 SVC2BBotto

Page 309

[ X LED Monitor Display on the Outdoor Unit Board ]- 368 -HWE09130164 0010010100 BC(Sub2)TH12 -99.9 to 999.9 B165 1010010100 BC(Sub2)TH25-99.9 to 999

Page 310 - 2. Temperature sensor

[ X LED Monitor Display on the Outdoor Unit Board ]- 369 -HWE09130178 0100110100 Error history 1 0000 to 9999 B B Address and error codes highlighted

Page 311

[ X LED Monitor Display on the Outdoor Unit Board ]- 370 -HWE09130Data before errorNo.SW1ItemDisplayUnit(A, B) *1Remarks1234567890 LD1 LD2 LD3 LD4 LD

Page 312

[ II Restrictions ] 29- 29 -HWE09130 GB(4) Wiring method1) Indoor/outdoor transmission lineDaisy-chain terminals M1 and M2 of the terminal block fo

Page 313

[ X LED Monitor Display on the Outdoor Unit Board ]- 371 -HWE09130216 0001101100 TH4 -99.9 to 999.9 A A The unit is [°C]217 1001101100 TH3 -99.9 to 9

Page 314 - Self-diagnosis LED

[ X LED Monitor Display on the Outdoor Unit Board ]- 372 -HWE09130243 1100111100244 0010111100245 1010111100246 0110111100247 1110111100248 000111110

Page 315 - Control board

[ X LED Monitor Display on the Outdoor Unit Board ]- 373 -HWE09130268 0011000010269 1011000010270 0111000010271 1111000010272 0000100010273 100010001

Page 316

[ X LED Monitor Display on the Outdoor Unit Board ]- 374 -HWE09130294 0110010010COMP number of start-stop eventsUpper 4 digits0000 to 9999 A ACount-u

Page 317

[ X LED Monitor Display on the Outdoor Unit Board ]- 375 -HWE09130Current dataNo.SW1ItemDisplayUnit(A, B)*1Remarks1234567890 LD1 LD2 LD3 LD4 LD5 LD6

Page 318 - Red White Red Red

[ X LED Monitor Display on the Outdoor Unit Board ]- 376 -HWE09130328 0001001010 329 1001001010 330 0101001010 BC(Main)LEV1 0000 to 2000 B331 110100

Page 319 - -7- Inverter (TJMU-A)

[ X LED Monitor Display on the Outdoor Unit Board ]- 377 -HWE09130Data on indoor unit systemNo.SW1ItemDisplayUnit(A, B) *1Remarks1234567890 LD1 LD2 L

Page 320

[ X LED Monitor Display on the Outdoor Unit Board ]- 378 -HWE09130368 0000111010 IC18 Address/capacity code 0000 to 9999 0000 to 9999 B Displayed alt

Page 321

[ X LED Monitor Display on the Outdoor Unit Board ]- 379 -HWE09130396 0011000110 IC46 Address/capacity code 0000 to 9999 0000 to 9999 B Displayed alt

Page 322

[ X LED Monitor Display on the Outdoor Unit Board ]- 380 -HWE09130412 0011100110 IC5 Suction temperature -99.9 to 999.9 B The unit is [°C]413 1011100

Page 323

- 30 -[ II Restrictions ]GBHWE091302. An example of a system with one outdoor unit to which 2 or more LOSSNAY units are connected (manual address se

Page 324

[ X LED Monitor Display on the Outdoor Unit Board ]- 381 -HWE09130436 0010110110 IC29 Suction temperature -99.9 to 999.9 B The unit is [°C]437 101011

Page 325 - Installation direction

[ X LED Monitor Display on the Outdoor Unit Board ]- 382 -HWE09130464 0000101110 IC7 Liquid pipe temperature -99.9 to 999.9 B The unit is [°C]465 100

Page 326

[ X LED Monitor Display on the Outdoor Unit Board ]- 383 -HWE09130492 0011011110 IC35 Liquid pipe temperature -99.9 to 999.9 B The unit is [°C]493 10

Page 327 - L1 L2 L3

[ X LED Monitor Display on the Outdoor Unit Board ]- 384 -HWE09130Setting dataNo.SW1ItemDisplayUnit(A, B)*1Remarks1234567890 LD1 LD2 LD3 LD4 LD5 LD6

Page 328 - SC-USC-RSC-SSC-TTB-N(Note)

[ X LED Monitor Display on the Outdoor Unit Board ]- 385 -HWE09130Data on indoor unit systemNo.SW1ItemDisplayUnit(A, B) *1Remarks1234567890 LD1 LD2 L

Page 329 - -7- Inverter (YJMU-A)

[ X LED Monitor Display on the Outdoor Unit Board ]- 386 -HWE09130Data on indoor unit systemNo.SW1ItemDisplayUnit(A, B) *1Remarks1234567890 LD1 LD2 L

Page 330

[ X LED Monitor Display on the Outdoor Unit Board ]- 387 -HWE09130Data on indoor unit systemNo.SW1ItemDisplayUnit(A, B)*1Remarks1234567890 LD1 LD2 LD

Page 331

[ X LED Monitor Display on the Outdoor Unit Board ]- 388 -HWE09130600 0001101001 IC28SH -99.9 to 999.9 B The unit is [ °C ] 601 1001101001 IC29SH -99

Page 332

[ X LED Monitor Display on the Outdoor Unit Board ]- 389 -HWE09130Data on indoor unit systemNo.SW1ItemDisplayUnit(A, B)*1Remarks1234567890 LD1 LD2 LD

Page 333

[ X LED Monitor Display on the Outdoor Unit Board ]- 390 -HWE09130650 0101000101 IC28SC -99.9 to 999.9 B The unit is [ °C ] 651 1101000101 IC29SC -9

Page 334

iiiiii HWE09130 GBPrecautions for handling units for use with R410ACAUTIONDo not use the existing refrigerant piping.A large amount of chlorine that

Page 335

[ II Restrictions ] 31- 31 -HWE09130 GB(4) Wiring method1) Indoor/outdoor transmission lineDaisy-chain terminals M1 and M2 of the terminal block fo

Page 336 - Noise filter

[ X LED Monitor Display on the Outdoor Unit Board ]- 391 -HWE09130Setting dataNo.SW1ItemDisplayUnit(A, B)* 1Remarks1234567890 LD1 LD2 LD3 LD4 LD5 LD6

Page 337

[ X LED Monitor Display on the Outdoor Unit Board ]- 392 -HWE09130688 0000110101 Current time 00:00 to 23:59 A A Hour: minute689 1000110101 Current

Page 338 - 1) PURY-P72TJMU-A

[ X LED Monitor Display on the Outdoor Unit Board ]- 393 -HWE09130702 0111110101 Time of error detection 7 00:00 to 23:59 A A Hour: minute703 111111

Page 339

[ X LED Monitor Display on the Outdoor Unit Board ]- 394 -HWE09130Data on indoor unit systemNo.SW1ItemDisplayUnit(A, B)* 1Remarks1234567890 LD1 LD2 L

Page 340

[ X LED Monitor Display on the Outdoor Unit Board ]- 395 -HWE09130741 1010011101 IC28 LEV opening 0000 to 9999 B Fully open: 2000742 0110011101 IC2

Page 341

[ X LED Monitor Display on the Outdoor Unit Board ]- 396 -HWE09130769 1000000011 IC6 Operation mode0000 : Stop 0001 : Ventilation 0002 : Cooling

Page 342 - [5] Refrigerant Leak

[ X LED Monitor Display on the Outdoor Unit Board ]- 397 -HWE09130797 1011100011 IC34 Operation mode0000 : Stop 0001 : Ventilation 0002 : Cooling

Page 343

[ X LED Monitor Display on the Outdoor Unit Board ]- 398 -HWE09130825 1001110011 IC12 filter 0000 to 9999 B Hours since last mainte-nance [ h ]826 0

Page 344

[ X LED Monitor Display on the Outdoor Unit Board ]- 399 -HWE09130853 1010101011 IC40 filter 0000 to 9999 B Hours since last mainte-nance [ h ]854

Page 345

[ X LED Monitor Display on the Outdoor Unit Board ]- 400 -HWE09130Other types of dataNo.SW1ItemDisplayUnit(A, B) *1Remarks1234567890 LD1 LD2 LD3 LD4

Page 346

- 32 -[ II Restrictions ]GBHWE091303. Group operation of units in a system with multiple outdoor units(1) Sample control wiring(2) Cautions1) ME r

Page 347

[ X LED Monitor Display on the Outdoor Unit Board ]- 401 -HWE09130887 1110111011 888 0001111011 889 1001111011 890 0101111011 891 1101111011 892 0011

Page 348

PURY-P72, P96, P120, P144T(Y)JMU-APURY-P168, P192, P216, P240, P264, P288T(Y)SJMU-AIssued in Mar. 2010 HWE09130Printed in JapanNew publication effecti

Page 349

[ II Restrictions ] 33- 33 -HWE09130 GB(4) Wiring method1) Indoor/outdoor transmission lineSame as [5] 2.Shielded cable connectionSame as [5] 2.2)

Page 350

- 34 -[ II Restrictions ]GBHWE091304. A system in which a system controller is connected to the transmission line for centralized control and which

Page 351

[ II Restrictions ] 35- 35 -HWE09130 GB(4) Wiring method1) Indoor/outdoor transmission lineSame as [5] 2.Only use shielded cables.Shielded cable co

Page 352

- 36 -[ II Restrictions ]GBHWE091305. An example of a system in which a system controller is connected to the indoor-outdoor transmission line (exce

Page 353

[ II Restrictions ] 37- 37 -HWE09130 GB(4) Wiring method1) Indoor/outdoor transmission lineDaisy-chain terminals M1 and M2 of the terminal block fo

Page 354

- 38 -[ II Restrictions ]GBHWE091306. A system with multiple BC controller connections (with a system controller connected to the centralized contro

Page 355

[ II Restrictions ] 39- 39 -HWE09130 GB(4) Wiring method1) Indoor/outdoor transmission lineDaisy-chain terminals M1 and M2 of the terminal block fo

Page 356

- 40 -[ II Restrictions ]GBHWE09130(5) Address setting methodThe outdoor units in the same refrigerant circuit are automatically designated as OC and

Page 357

ivHWE09130 GBBefore installing the unitWARNINGDo not install the unit where a gas leak may occur.If gaseous refrigerant leaks and piles up around the

Page 358

[ II Restrictions ] 41- 41 -HWE09130 GB

Page 359 - CMB-1016NU-G, GA, HA

- 42 -[ II Restrictions ]GBHWE09130[6] An Example of a System to which an ME Remote Controller is connected(1) Sample control wiring(2) Cautions1)

Page 360 - CMB-1016NU-GA

[ II Restrictions ] 43- 43 -HWE09130 GB(4) Wiring method1) Indoor/outdoor transmission lineSame as [5] 2.Shielded cable connectionSame as [5] 2.2)

Page 361 - Solenoid valve

- 44 -[ II Restrictions ]GBHWE09130[7] An Example of a System to which both MA Remote Controller and ME Remote Controller are connected(1) Sample con

Page 362

[ II Restrictions ] 45- 45 -HWE09130 GB(4) Wiring method1) Indoor/outdoor transmission lineSame as [5] 2.Shielded cable connectionSame as [5] 2.2)

Page 363

- 46 -[ II Restrictions ]GBHWE09130(5) Address setting methodThe outdoor units in the same refrigerant circuit are automatically designated as OC and

Page 364

[ II Restrictions ] - 47 -HWE09130 GB[8] Restrictions on Pipe Length(1) System that requires 16 BC controller ports or fewer <System with only the

Page 365

[ II Restrictions ]- 48 -HWE09130 GB0102030405060700 5 10 15Pipe length between main BCcontroller and farthest indoor unit (m[ft])Height difference b

Page 366 - 7SEG LED

[ II Restrictions ] - 49 -HWE09130 GB(2) System that requires more than 16 BC controller ports or with multiple BC controllers <Outdoor unit P144

Page 367 - Day count

[ II Restrictions ]- 50 -HWE09130 GB1) A system that requires more than 16 BC controller ports requires two or three BC controllers (main and sub),

Page 368 - Current data

vv HWE09130 GBBefore installing the unit (moving and reinstalling the unit) and performing electrical workCAUTIONProperly ground the unit.Do not conne

Page 369

[ II Restrictions ] - 51 -HWE09130 GB(3) System that requires more than 16 BC controller ports or with multiple BC controllers <Outdoor unit P16

Page 370

[ II Restrictions ]- 52 -HWE09130 GB1) A system that requires more than 16 BC controller ports requires two or three BC controllers (main and sub),

Page 371

[ II Restrictions ] - 53 -HWE09130 GB1. Refrigerant pipe size(1) Between outdoor unit and the first twinning pipe (Part A)(2) Between BC controller

Page 372

[ II Restrictions ]- 54 -HWE09130 GB2. Connecting the BC controller(1) Size of the pipe that fits the standard BC controller portsP72 - P120 models*

Page 373

[ II Restrictions ] - 55 -HWE09130 GB1) To connect P06 - P18 models of indoor units use the reducer that is supplied with the BC controller.2) To

Page 374

[ II Restrictions ]- 56 -HWE09130 GB(2) Size of the pipe that fits the main BC controller portsP72 - P288 modelsThe ports of the BC controller accom

Page 375

[ II Restrictions ] - 57 -HWE09130 GB(3) Size of the pipe that fits the sub BC controller portsThe ports of the BC controller accommodates the pipes

Page 376

- 58 -[ II Restrictions ]GBHWE09130

Page 377

- 59 -HWE09130 GBIII Outdoor Unit Components[1] Outdoor Unit Components and Refrigerant Circuit ...

Page 378

- 60 -

Page 379 - Data before error

viHWE09130 GBBefore the test runCAUTIONTurn on the unit at least 12 hours before the test run.Keep the unit turned on throughout the season. If the un

Page 380

[ III Outdoor Unit Components ] - 61 -HWE09130 GBIII Outdoor Unit Components[1] Outdoor Unit Components and Refrigerant Circuit1. Front view of a ou

Page 381

[ III Outdoor Unit Components ]- 62 -HWE09130 GB(2) PURY-P120, P144TJMU-APURY-P120, P144YJMU-AContactorboxContactorboxTransformer box(YJMU-A only)Tra

Page 382

[ III Outdoor Unit Components ] - 63 -HWE09130 GB2. Refrigerant circuit(1) PURY-P72TJMU-APURY-P72YJMU-AHigh-pressure switch(63H1)Low pressure sensor(

Page 383

[ III Outdoor Unit Components ]- 64 -HWE09130 GB(2) PURY-P96TJMU-APURY-P96YJMU-AHigh pressure check joint(CJ1)Low pressure check joint(CJ2)Refrigeran

Page 384

[ III Outdoor Unit Components ] - 65 -HWE09130 GB(3) PURY-P120, P144TJMU-APURY-P120, P144YJMU-AThe YJMU model has a transformer box.Check valve (CV7b

Page 385

[ III Outdoor Unit Components ]- 66 -HWE09130 GB[2] Control Box of the Outdoor Unit1. PURY-P72TJMU-A1) Exercise caution not to damage the bottom an

Page 386 - Data on indoor unit system

[ III Outdoor Unit Components ] - 67 -HWE09130 GB2. PURY-P96, P120, P144TJMU-A1) Exercise caution not to damage the bottom and the front panel of

Page 387

[ III Outdoor Unit Components ]- 68 -HWE09130 GB3. PURY-P72, P96, P120, P144YJMU-A1) Exercise caution not to damage the bottom and the front panel

Page 388

[ III Outdoor Unit Components ] - 69 -HWE09130 GB4. Transformer Box (PURY-P72, P96, P120, P144YJMU-A)Transformer(T03)Transformer(T02)

Page 389

[ III Outdoor Unit Components ]- 70 -HWE09130 GB[3] Outdoor Unit Circuit Board1. Outdoor unit control boardCN332 Output 18VDC GND (Fan boar

Page 390

CONTENTSHWE09130 GBI Read Before Servicing[1] Read Before Servicing...

Page 391

[ III Outdoor Unit Components ] - 71 -HWE09130 GB2. M-NET board Power supply output for centralized control system (30VDC)

Page 392

[ III Outdoor Unit Components ]- 72 -HWE09130 GB3. INV board(1) PURY-P72TJMU-AFaston terminals have a locking function. Make sure the cable heads are

Page 393 - Setting data

[ III Outdoor Unit Components ] - 73 -HWE09130 GB(2) PURY-P96, P120, P144TJMU-AFaston terminals have a locking function. Make sure the cable heads a

Page 394

[ III Outdoor Unit Components ]- 74 -HWE09130 GB(3) PURY-P72, P96, P120, P144YJMU-A1) Before inspecting the inside of the control box, turn off th

Page 395

[ III Outdoor Unit Components ] - 75 -HWE09130 GB4. Fan board(1) PURY-P72, P96, P120, P144TJMU-ACNVDC Bus voltage input  N  P F01 Fuse 250VAC 15A LE

Page 396

[ III Outdoor Unit Components ]- 76 -HWE09130 GB(2) PURY-P72, P96, P120, P144YJMU-ACNVDCBus voltage input N PCNINVInverter output W V

Page 397

[ III Outdoor Unit Components ] - 77 -HWE09130 GB5. Noise Filter(1) PURY-P72TJMU-A GroundingTB21Input/output(L1)CN02Output L1 L2TB22Input/output(L2)T

Page 398

[ III Outdoor Unit Components ]- 78 -HWE09130 GB(2) PURY-P96, P120, P144TJMU-A GroundingF3 Fuse 250VAC 6.3A R1,2 Rush current protection resistor TB

Page 399

[ III Outdoor Unit Components ] - 79 -HWE09130 GB(3) PURY-P72, P96, P120, P144YJMU-ACN4Output(Rectified L2-L3 current) P NCN5Output(Rectified

Page 400

[ III Outdoor Unit Components ]- 80 -HWE09130 GB[4] BC Controller Components1. CMB-P NU-G, GA, HA(1) Front(2) Rear view <G type>Liquid pipe

Page 401

CONTENTSHWE09130 GBIX Troubleshooting[1] Error Code Lists...

Page 402

[ III Outdoor Unit Components ] - 81 -HWE09130 GB(3) Rear view <GA type>(4) Rear view <HA type>TH12TH15TH16TH11SVM2SVM1LEV1LEV3LEV2PS1P

Page 403

[ III Outdoor Unit Components ]- 82 -HWE09130 GB2. CMB-P NU-GB, HB(1) Front(2) Rear viewLiquid pipe (Indoor unit side)Gas pipe (Indoor unit side)TH

Page 404

[ III Outdoor Unit Components ] - 83 -HWE09130 GB[5] Control Box of the BC Controller1. CMB-P1016NU-G, GA, HARelay boardTransformerTerminal block fo

Page 405 - HWE09130

[ III Outdoor Unit Components ]- 84 -HWE09130 GB[6] BC Controller Circuit Board1. BC controller circuit board (BC board)SW1SW2SW5SW6SW4

Page 406

[ III Outdoor Unit Components ] - 85 -HWE09130 GB2. RELAY BOARD (RELAY 4 board)3. RELAY BOARD (RELAY 10 board)

Page 407

- 86 -[ III Outdoor Unit Components ]GBHWE09130

Page 408

- 87 -HWE09130 GBIV Remote Controller[1] Functions and Specifications of MA and ME Remote Controllers ... 89[2] Group

Page 410

[ IV Remote Controller ] - 89 -HWE09130 GBIV Remote Controller[1] Functions and Specifications of MA and ME Remote ControllersThere are two types of

Page 411 - Printed in Japan

[ IV Remote Controller ]- 90 -HWE09130 GB[2] Group Settings and Interlock Settings via the ME Remote Controller1. Group settings/interlock settings&