  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 58
59
AA
Check of outdoor unit
No
Start
Press the EMERGENCY
OPERATION switch of all
indoor units.
Yes
Is there 230V AC
between L
- N
on the TB1
of outdoor unit?
No
Is fuse(F61) on the outdoor
control P.C. board broken?
Check and rectify the
connecting wire of
indoor and outdoor unit.
3 minutes later, is there
12V DC between
1 - 2 on the all terminal
blocks of outdoor unit?
Is there 10~15V DC between
JP20 DC12V and JP19 GND
on outdoor control P.C.
board?
Fan motor doesn't operate.
Compressor doesn't operate.
Yes
Yes
Turn OFF the power supply
to outdoor unit.
Does outdoor control P.C.
board connect with outdoor
fan capacitor C61?
Yes
Connect the outdoor control
P.C. board with outdoor fan
capacitor C61.
Disconnect connector of
outdoor fan motor CN91
and outdoor fan capacitor
C61.
Replace the outdoor
fan motor.
Replace the outdoor
control P.C. board.
No
Yes
Turn OFF the power supply.
Replace the outdoor
control P.C. board.
No
Disconnect connector of outdoor fan motor
CN91 and outdoor fan capacitor C61.
Is the resistance 0" or between the lead wire
WHT and BLK of outdoor fan motor, or between
the lead wire RED and BLK of outdoor fan motor?
(Refer to 11-3.)
Yes
Replace the outdoor
fan motor and fuse(F61).
No
Check the power supply
and connecting wire.
No
Is there 12V DC between
1
- 2
on the terminal
block of each indoor unit?
No
Short both terminal
of fuse(F61).
Yes
Is the resistance 0" between
the fuse(F61) and the terminal
of CN903?
Replace the outdoor
control P.C. board.
Yes
Replace
the fuse(F61).
No
No
Check the indoor unit.
Yes
Turn OFF the power supply to outdoor unit.
Disconnect connecting wire of X521 and X522 from outdoor control P.C. board.
Insulate terminal of connecting wires to prevent contact of other parts.
Turn ON the power supply to outdoor unit.
Press the EMERGENCY OPERATION switch of all indoor unit.
Is the resistance 0" or
between the terminal C and
R of MC1, and between the
terminal C and S of MC1?
(Refer to 11-3.)
3 minutes later, is the resistance 0" between the
terminal 3 and 4 of X521 on outdoor control P.C. board,
and between the terminal 3 and 4 of X522 on outdoor
control P.C. board?
Turn OFF the power supply
to outdoor unit.
Yes
Replace the
compressor MC1.
No
Replace the
compressor MC2.
No
Check and
rectify the
connecting wire
of terminal and
compressor.
Turn OFF the power supply
to outdoor unit.
No
Replace the outdoor
control P.C. board.
Is the resistance 0" or
between the terminal C and
R of MC2, and between the
terminal C and S of MC2?
(Refer to 11-3.)
Yes
Yes
Is the resistance 0" or
between the lead wire
WHT and BLK of outdoor
fan motor, or between the
lead wire RED and BLK
of outdoor fan motor?
(Refer to 11-3.)
Measure resistance on
all the solenoid coils.
Is resistance 0"?
Replace the solenoid coil.
Yes
No
2A59/2A70VB
MUX-3A60/3A63/
4A73VB
Compressor and / or outdoor fan doesn’t operate.
11-4.Troubleshooting flow