Fig. 1 Fig. 2
Fig. 3 Fig. 4
Fig. 5 Fig. 6
3. FLARING WORK AND PIPE CONNECTION
3-1. FLARING WORK
Pipe diameter
(mm)
Nut
(mm)
A (mm) Tightening torque
Clutch
typetool
for R410A
Clutch
typetool
for R22
Wing nut
typetool
for R22
N•m kgf•cm
ø6.35 (1/4”)
17
0 to 0.5 1.0 to 1.5
1.5 to 2.0
13.7to17.7 140 to 180
ø9.52(3/8”)
22 34.3 to 41.2 350 to 420
ø12.7(1/2”)
26 2.0 to 2.5 49.0to56.4 500to575
ø15.88 (5/8”)
29 - 73.5to78.4 750to800
Tilted Uneven Burred
Good
No good
Burr
Copper pipe
Spare reamer
Pipe cutter
Smooth all
around
Even length
all around
Inside is shin
-
ingwithoutany
scratches.
Flare nut
Die
Copper pipe
Clutchtype
Flaring tool
Wingnuttype
3-2. PIPE CONNECTION
• Fastenarenutwithatorquewrenchasspeciedinthetable.
• When fastenedtootight, arenutmay brakeaftera longperiodand
cause refrigerant leakage.
Outdoor unit connection
Connect pipes to stop valve pipe joint of the outdoor unit in the same
manner applied for indoor unit.
• For tightening, use a torque wrench or spanner and use the same
tightening torque applied for indoor unit.
3-3. INSULATION AND TAPING
1) Cover piping joints with pipe cover.
2)Foroutdoorunitside,surelyinsulateeverypipingincludingvalves.
3)Usingpiping tape(E),apply tapingstartingfrom theentryof outdoor
unit.
• Stop the end of piping tape (E) with tape (with adhesive agent at
-
tached).
• When piping have to be arranged through above ceiling, closet or
wherethetemperatureandhumidityarehigh,windadditionalcom
-
merciallysoldinsulationtopreventcondensation.
Service port cap
(Torque13.7to
17.7N•m,140 to
180 kgf
•cm)
4-1. PURGING PROCEDURES AND LEAK TEST
Stop valve
for GAS
Stop valve cap
(Torque19.6to
29.4N•m,200
to 300 kgf•cm)
Gauge manifold
valve (for R410A)
Compound pressure
gauge (for R410A)
–0.101MPa
(–760mmHg)
Handle
Low
Handle High
Vacuum pump
(for R410A)
Charge hose
(for R410A)
*Close
*Open
Hexagonal wrench
*4to5turns
Stop valve
for LIQUID
4. PURGING PROCEDURES, LEAK TEST, AND TEST RUN
Pressure gauge
(for R410A)
Precautions when using
the control valve
When attaching the control valve to
theserviceport,valvecoremayde-
form or loosen if excess pressure is
applied.Thismaycausegasleak.
Service port
Charge hose
(for R410A)
Body
Close
Open
Control
valve
A
When attaching the control valve to
the service port, make sure that the
valve core is in closed position, and
then tighten part A. Do not tighten
partAorturn the bodywhenvalve
core is in open position.
Copper
pipe
1)Cutthecopperpipecorrectlywithpipecutter.(Fig.1,2)
2)Completelyremoveallburrsfromthecutcrosssectionofpipe.(Fig.3)
• Puttheendofthecopperpipetodownwarddirectionasyou
remove burrs in order to avoid to let burrs drop in the piping.
3)Removearenutsattachedtoindoorandoutdoorunits,thenputthem
on pipe having completed burr removal. (Not possible to put them on
afteraringwork.)
4)Flaring work (Fig. 4, 5). Firmly hold copper pipe in the dimension
shown in the table. Select A mm from the table according to the tool
youuse.
5) Check
• ComparethearedworkwithFig.6.
• Ifareisnotedtobedefective,cutoffthearedsectionanddo
aringworkagain.
1) Remove service port cap of stop valve on the side of the outdoor unit
gas pipe. (The stop valve will not work in its initial state fresh out of the
factory,totallyclosedwithcapon.)
2) Connect gauge manifold valve and vacuum pump to service port of
stop valve on the gas pipe side of the outdoor unit.
3) Run the vacuum pump. (Vacuumize for more than 15 minutes.)
4) Check the vacuum with gauge manifold valve, then close gauge mani
-
fold valve, and stop the vacuum pump.
5) Leave as it is for one or two minutes. Make sure pointer gauge mani
-
foldvalveremainsinthesameposition.Conrmthatpressuregauge
shows–0.101MPa[Gauge](–760mmHg).
6)Removegaugemanifoldvalvequicklyfromserviceportofstopvalve.
7)After refrigerant pipes are connected and evacuated, fully open all
stop valves on both sides of gas pipe and liquid pipe. Operating with
-
outfullyopeninglowerstheperformanceandthiscausestrouble.
8) Refer to 1-3., and charge the prescribed amount of refrigerant if
needed. Be sure to charge slowly with liquid refrigerant. Otherwise,
compositionoftherefrigerantin thesystem maybe changedandaf
-
fect performance of the air conditioner.
9)Tightencapofserviceporttoobtaintheinitialstatus.
10) Leak test
WARNING
When installing the unit, securely
connect the refrigerant pipes before
starting the compressor.
MXZ-4B_5BVA-A1 JG79A313H01.indd 6 2009/10/13 10:17:27
Comments to this Manuals