4-6. TEST RUN
Be sure to perform the test run for each unit. Make sure each indoor unit op-
eratesproperlyfollowingtheinstallationmanualattachedtotheunit.
• Ifyouperformthetestrunforallindoorunitsatonce,youcannotdetectany
erroneousconnection,if any,of therefrigerantpipesand theindoor/outdoor
unit connecting wires.
About the restart protective mechanism
Once the compressor stops, the restart preventive device operates so the com
-
pressor will not operate for 3 minutes to protect the air conditioner.
Wiring/piping correction function
This unit has a wiring/piping correction function which corrects wiring and piping
combination.Whenthereispossibilityofincorrectwiringandpipingcombination,
andconrmingthecombinationisdifcult,usethisfunctiontodetectandcorrect
thecombinationbyfollowingtheproceduresbelow.
Make sure that the following is done.
Power is supplied to the unit.
Stop valves are open.
Note:
Duringdetection,theoperationoftheindoorunitiscontrolledbytheoutdoor
unit.Duringdetection,theindoorunitautomaticallystopsoperation.Thisisnota
malfunction.
Procedure
Pressthepiping/wiringcorrectionswitch(SW871)1minuteormoreafterturning
onthepowersupply.
Correction completes in 10 to 15 minutes. When the correction is completed,
its result is shown by LED indication. Details are described in the following
table.
To cancel this function during its operation, press the piping/wiring correction
switch(SW871)again.
When the correction completed without error, do not press the piping/wiring
correctionswitch(SW871)again.
When the result was “cannot be corrected”, press the piping/wiring correction
switch(SW871)againtocancelthisfunction.Then,conrmthewiringandpiping
combinationinaconventionalmannerbyoperatingtheindoorunitsonebyone.
The operation is done while the power is supplied. Make sure not to contact
partsotherthantheswitch,includingtheP.C.board.Thismaycauseelectric
shockor burn byhot partsand live partsaround the switch. Contacting the
livepartsmaycauseP.C.boarddamage.
To prevent electronic control P.C. board damage, make sure to perform static
elimination before operating this function.
This function does not operate when the outside temperature is 0°C or be
-
low.
LED indication during detection:
LED
1 (Red) 2 (Yellow) 3 (Green)
Lighted Lighted Blinking
Result of piping/wiring correction function
LED
Result
1 (Red) 2 (Yellow) 3 (Green)
Lighted Not lighted Lighted
Completed
(Correctedsuccessfully)
Blinking Blinking Blinking Cannot be corrected
Other indications
Refer to “SAFETY PRE-
CAUTIONS WHEN LED
FLASHES” located behind
the service panel.
5. RELOCATION AND MAINTENANCE
5-1. PUMPING DOWN
Whenrelocatingordisposingoftheairconditioner,pumpdownthesystemfollowingtheprocedurebelowsothatnorefrigerantisreleasedintotheatmos-
phere.
1) Connect the gauge manifold valve to the service port of the stop valve on the gas pipe side of the outdoor unit.
2)Fullyclosethestopvalveontheliquidpipesideoftheoutdoorunit.
3)Closethestopvalveonthegaspipesideoftheoutdoorunitalmostcompletelysothatitcanbeeasilyclosedfullywhenthepressuregaugeshows0
MPa [Gauge] (0 kgf/cm
2
).
4)StarttheemergencyCOOLoperationonalltheindoorunits.
To start the emergencyoperationinCOOLmode,disconnectthepower supplyplugand/orturnoff thebreaker.After15seconds, connectthepower
supplyplugand/orturnonthebreaker,andthenpresstheE.O.SWonce.(TheemergencyCOOLoperationcanbeperformedcontinuouslyforupto30
minutes.)
5)Fullyclosethestopvalveonthegaspipesideoftheoutdoorunitwhenthepressuregaugeshows0.05to0MPa[Gauge](approx.0.5to0kgf/cm
2
).
6) Stop the emergencyCOOLoperation
.
Press the E.O. SW several times until all LED lamps turn off. Refer to operating instructions for details .
When pumping down the refrigerant, stop the compressor before disconnecting
the refrigerant pipes. The compressor may burst if air etc. get into it.
WARNING
4-7. EXPLANATION TO THE USER
• UsingtheOPERATINGINSTRUCTIONS,explaintotheuserhowtousetheairconditioner(howtousetheremotecontroller,howtoremovetheairl-
ters, how to remove or put the remote controller in the remote controller holder, how to clean, precautions for operation, etc.).
• RecommendtheusertoreadtheOPERATINGINSTRUCTIONScarefully.