6 - 3
MDS-DM Series Specifications Manual
6-1 Selection of wire
<MDS-DM-SPV Series>
(3) 600V bridge polyethylene insulated wire (IC) 105 °C product
(Example according to JEAC8001)
<MDS-DM-V3 Series>
<MDS-DM-SPV Series>
Unit type
Terminal name
TE1
(L1, L2, L3)
TE1
(U, V, W)
CN31L/M/S
(U,V,W,PE)
CN22
(VDD.SG)
mm
2
AWG
mm
2
mm
2
mm
2
AWG
mm
2
AWG
Drive unit
MDS-DM-SPV3F-10080
22 4
5.5 10
3.5 12 2 14
MDS-DM-SPV3F-16080 88
MDS-DM-SPV3F-20080 14 6
MDS-DM-SPV3F-200120 14 6
MDS-DM-SPV2F-10080 5.5 10
MDS-DM-SPV2F-16080 88
MDS-DM-SPV2F-20080 14 6
Unit type
Terminal name
TE1
(U, V, W, )
TE2
(L+, L-)
TE3
(L11, L21)
mm
2
AWG
mm
2
AWG
mm
2
AWG
Servo drive
unit
MDS-DM-V3-202020
214
Match with TE2 of selected
power supply unit
1.25 to 2 16 to 14
MDS-DM-V3-404040
Unit type
Terminal name
TE1
(L1, L2, L3)
TE1
(U, V, W)
CN31L/M/S
(U,V,W,PE)
CN22
(VDD.SG)
mm
2
AWG
mm
2
mm
2
mm
2
AWG
mm
2
AWG
Drive unit
MDS-DM-SPV3F-10080
14 6
3.5 12
2 141.2516
MDS-DM-SPV3F-16080 5.5 10
MDS-DM-SPV3F-20080 14 6
MDS-DM-SPV3F-200120 14 6
MDS-DM-SPV2F-10080 3.5 12
MDS-DM-SPV2F-16080 5.5 10
MDS-DM-SPV2F-20080 14 6
1. Selection conditions follow IEC/EN60204-1, UL508C, JEAC8001.
- Ambient temperature is maximum 40°C.
- Cable installed on walls without ducts or conduits.
To use the wire under conditions other than above, check the standards you are supposed
to follow.
2. The maximum wiring length to the motor is 30m.
If the wiring distance between the drive unit and motor is 20m or longer, use a thick wire so
that the cable voltage drop is 2% or less.
3. Always wire the grounding wire.
CAUTION