ENCODER SPECIFICATIONS AND PARAMETER SETTINGS
19
3
3.2 Parameter setting
3.2.1 Parameter for encoder
• If operating at a frequency higher than 120 Hz with Pr.359 = "0 or 1", the motor rotation will be unstable.
Parameter
Number
Pr.
group
Name
Initial
Value
Setting
Range
Description
359 C141
Encoder rotation
direction
1
0
Set when using a motor for which
forward rotation (encoder) is clockwise
(CW) viewed from the shaft
Set for the operation
at 120 Hz or less.
100
Set for the operation
at a frequency
higher than 120 Hz.
1
Set when using a motor for which
forward rotation (encoder) is
counterclockwise (CCW) viewed from
the shaft
Set for the operation
at 120 Hz or less.
101
Set for the operation
at a frequency
higher than 120 Hz.
369 C140
Number of
encoder pulses
1024 0 to 4096
Set the number of encoder pulses output.
Set the number of pulses before it is multiplied by 4.