ORIENTATION CONTROL
23
4
4.2 Terminals
Option FR-A8AX terminal
Inverter terminal
 Refer to the Instruction Manual (Detailed) for details of Pr.178 to Pr.189 (input terminal function selection) and Pr.190 to Pr.196
(output terminal function selection).
Terminal
Symbol
Terminal Name Description
X0 to X15 Digital signal input terminal
Input the digital signal at the relay contact or open collector terminal.
Using Pr. 360, speed or position command is selected as the command signal entered.
DY
Data read timing input signal
terminal
Used when a digital signal read timing signal is necessary. Data is read only during the DY
signal is on.
By switching the DY signal off, the X0 to X15 data before signal-off is retained.
Terminal
(Signal)
Terminal (Signal) Name Application Explanation
Input X22 Orientation command
Used to enter an orientation signal for orientation.
For the terminal used for X22 signal input, set "22" in any of Pr. 178 to Pr. 189 to assign
the function.

Output
ORA Orientation complete
Switched LOW if the orientation has stopped within the in-position zone while the start
and X22 signals are input.
For the terminal used for the ORA signal output, assign the function by setting "27
(positive logic) or 127 (negative logic)" in any of Pr. 190 to Pr. 196.

ORM Orientation fault
Switched LOW if the orientation has not completed within the in-position zone while the
start and X22 signals are input.
For the terminal used for the ORA signal output, assign the function by setting "28
(positive logic) or 128 (negative logic)" in any of Pr. 190 to Pr. 196.
