FR-D700INSTRUCTION MANUAL (BASIC)FR-D720-0.1K to 15KFR-D740-0.4K to 15KFR-D720S-0.1K to 2.2KFR-D710W-0.1K to 0.75KINVERTER700456789321CONTENTSOUTLINE
62 INSTALLATION AND WIRINGNOTEyThe life of the inverter is influenced by surrounding air temperature. The surrounding air temperature should be as low
7Peripheral devices22.1 Peripheral devicesCheck the inverter model of the inverter you purchased. Appropriate peripheral devices must be selected acco
8Installation of the inverters and precautions2.2 Installation of the inverters and precautions(1) Installation of the inverterEnclosure surface mount
9Wiring22.3 Wiring2.3.1 Terminal connection diagramNOTEy To prevent a malfunction caused by noise, separate the signal cables more than 10cm from the
10Wiring2.3.2 Terminal specificationsTypeTerminalSymbolTerminal Name Terminal SpecificationMain circuit terminalR/L1, S/L2, T/L3 ∗AC power inputConnec
11Wiring2* For more details, refer to the Safety stop function instruction manual (BCN-A211508-000). (Please contact your sales representative for the
12Wiring2.3.3 Terminal arrangement of the main circuit terminal, power supply and the motor wiringzThree-phase 200V/400V classzSingle-phase 200V class
13Wiring2(1) Wire size and other specifications of the main circuit terminals and the earthing terminalSelect the recommended cable size to ensure tha
14WiringThe line voltage drop can be calculated by the following formula:Line voltage drop [V]=Use a larger diameter cable when the wiring distance is
15Wiring22.3.4 Wiring of control circuit(1) Control circuit terminal layout(2) Wiring methodzWiringUse a blade terminal and a wire with a sheath strip
A-1This Instruction Manual (Basic) provides handling information and precautions for use of the equipment.Please forward this Instruction Manual (Basi
16WiringzWire removal(3) Control circuit common terminals (SD, 5, SE)Terminals SD, SE and 5 are common terminals for I/O signals.(All common terminals
17Connection of a dedicated external brake resistor (MRS type, MYS type, FR-ABR) (0.4K or more)22.4 Connection of a dedicated external brake resistor
18PRECAUTIONS FOR USE OF THE INVERTER3 PRECAUTIONS FOR USE OF THE INVERTERThe FR-D700 series is a highly reliable product, but incorrect peripheral ci
19PRECAUTIONS FOR USE OF THE INVERTER3(12) Do not apply a voltage higher than the permissible voltage to the inverter I/O signal circuits.Application
204 FAILSAFE OF THE SYSTEM WHICH USES THE INVERTERWhen a fault occurs, the inverter trips to output a fault signal. However, a fault output signal may
21Start/stop from the operation panel (PU operation)55 DRIVE THE MOTOR5.1 Start/stop from the operation panel (PU operation)5.1.1 Setting the frequenc
22Start/stop from the operation panel (PU operation)5.1.2 Setting the frequency by switches (three-speed setting) (Pr. 4 to Pr. 6)POINTy Use operation
23Start/stop from the operation panel (PU operation)55.1.3 Setting the frequency by analog input (voltage input)POINTy Operation panel ( ) is used to
24Start and stop using terminals (External operation)5.2 Start and stop using terminals (External operation)5.2.1 Setting the frequency by the operati
25Start and stop using terminals (External operation)55.2.2 Setting the frequency by switches (three-speed setting) (Pr. 4 to Pr. 6)POINTy To give a s
A-2(2) Wiring(3) Trial run(4) Usage(5) Emergency stop(6) Maintenance, inspection and parts replacement(7) Disposalz Do not install a power factor corr
26Start and stop using terminals (External operation)5.2.3 Setting the frequency by analog input (voltage input)POINTy Switch ON across terminals STF(
27Start and stop using terminals (External operation)55.2.4 Operating at 60Hz or higher using the external potentiometer< How to change the maximum
28Simple mode parameters6 PARAMETERSSimple variable-speed operation can be performed with the inverter in the initial settings. Set the required param
29Parameter list66.2 Parameter listREMARKSy indicates simple mode parameters.y The parameters surrounded by a black border in the table allow its set
30Parameter list75Reset selection/disconnected PU detection/PU stop selection0 to 3, 14 to 171477 Parameter write selection 0, 1, 2 078Reverse rotatio
31Parameter list6197 SO terminal function selection0, 1, 3, 4, 7, 8, 11 to 16, 25, 26, 46, 47, 64, 70, 80, 81, 90, 91, 93, 95, 96, 98, 99, 100, 101, 1
32Parameter list∗1 Differ according to capacities.6%: 0.75K or less4%: 1.5K to 3.7K3%: 5.5K, 7.5K2%: 11K, 15K∗2 Differ according to capacities. 5s:
33Reset method of protective function77 TROUBLESHOOTINGWhen a fault occurs in the inverter, the inverter trips and the PU display automatically change
34List of fault displays7.2 List of fault displaysWhen a fault occurs, the inverter trips and the PU display automatically changes to one of the follo
35List of fault displays7Fault∗5Overcurrent trip during constant speedAppears when an overcurrent occurred during constant speed operation.y Keep load
A-3<Abbreviation>PU...Operation panel and parameter unit (FR-PU04/FR-PU07)Inverter...
36Check first when you have a trouble∗1 Resetting the inverter initializes the internal cumulative heat value of the electronic thermal relay function
37Inspection items88PRECAUTIONS FOR MAINTENANCE AND INSPECTIONThe inverter is a static unit mainly consisting of semiconductor devices. Daily inspecti
38Replacement of partsWhen using the safety stop function, periodic inspection is required to confirm that safety function of the safety systemoperate
39Rating99 SPECIFICATIONS9.1 Ratingz Three-phase 200V power supplyz Three-phase 400V power supplyz Single-phase 200V power supplyModel FR-D720-K 0.1
40Common specificationsz Single-phase 100V power supply∗1 The applicable motor capacity indicated is the maximum capacity applicable for use of the Mi
41Outline dimension drawings99.3 Outline dimension drawings• Three-phase 200V class• Three-phase 400V class• Single-phase 200V class• Single-phase 100
42The EU Directives are issued to standardize different national regulations of the EU Member States and to facilitate freemovement of the equipment,
43(2) Low Voltage DirectiveWe have self-confirmed our inverters as products compliant to the Low Voltage Directive (Conforming standard EN 61800-5-1)
44∗ Select a UL and cUL certified fuse with Class T fuse equivalent cut-off speed or faster with the appropriate rating forbranch circuit protection,
45(Standard to comply with: UL 508C, CSA C22.2 No. 14)1. General precautionThe bus capacitor discharge time is 10 minutes. Before starting wiring or i
111OUTLINE1.1 Product checking and parts identificationUnpack the inverter and check the capacity plate on the front cover and the rating plate on the
46REVISIONS*The manual number is given on the bottom left of the back cover. For Maximum Safety• Mitsubishi inverters are not designed or manufactured
International FA CenterKorean FA CenterBeijing FA CenterEuropean FA CenterUK FA CenterCentral and Eastern Europe FA CenterTianjin FA CenterShanghai F
HEAD OFFICE: TOKYO BUILDING 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPANMODELMODELCODE1A2-P34FR-D700INSTRUCTION MANUAL (BASIC)IB(NA)-0600438EN
2Operation panel1.2 Operation panel1.2.1 Names and functions of the operation panelThe operation panel cannot be removed from the inverter.Operation m
3Operation panel11.2.2 Basic operation (factory setting)STOPOperation mode switchoverParameter settingFaults history Monitor/frequency settingAt power
4Operation panel1.2.3 Changing the parameter setting valueChanging exampleChange the Pr. 1 Maximum frequency setting.Operation Display 1. Screen at po
5Operation panel11.2.4 Parameter clear/all parameter clearPOINTy Set "1" in Pr.CL Parameter clear, ALLC all parameter clear to initialize a