Mitsubishi Electric FR-E700 Instruction Manual Page 112

  • Download
  • Add to my manuals
  • Print
  • Page
    / 286
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 111
109
Operation via CC-Link communication and its settings
5
PARAMETERS
(4) Faults and measures
The following table shows how the inverter operates at a fault occurrence in each operation mode.
Depends on the Pr.502 setting.
Measures at fault occurrences
When faults other than the above are displayed, refer to Appendix 6 and remove the cause of the error.
Fault Location
Fault Indication
Status
Operation Mode
Network operation PU operation
Communication
line
E.OP1
Inverter operation Inverter trip
Continued
Data communication Stop Stop
Inverter
Faults other than E.1 and
E.OP1
Inverter operation Inverter trip Inverter trip
Data operation Continued Continued
E.1
Inverter operation Inverter trip
Continued
Data communication Stop Stop
Fault Indication Fault Definition Measures
E.OP1
Communication line
error
Check the LED status of the inverter and remove the cause of the fault.
(Refer to page 75 for LED indication status)
Inspect the master.
E.1
CC-Link
communication circuit
fault in inverter
Check for excessive noise around the inverter. Check that the switch for
manufacturer setting has not been changed and is in the initial status. Remove
the fault cause.
Parameters referred to
Pr. 7 Acceleration time, Pr. 8 Deceleration time, Pr. 44 Second acceleration/deceleration time, Pr. 45 Second deceleration time Refer to page 135