Mitsubishi Electric FR-E700 Instruction Manual Page 167

  • Download
  • Add to my manuals
  • Print
  • Page
    / 286
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 166
164
Function assignment of external terminals and CC-Link communication virtual terminals
(1) Input terminal function assignment
Using Pr. 180 to Pr. 184, set the functions of the input virtual terminals.
Refer to the following table and set the parameters:
∗1 When Pr. 59 Remote function selection = "1" or "2", the functions of the RL, RM and RH signals are changed as given in the table.
∗2 When Pr. 270 Stop-on contact control selection = "1", functions of RL and RT signals are changed as in the table.
Setting Signal Function Related Parameters
Refer to
Page
0RL
Pr. 59 = 0 (initial value) Low-speed operation command
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27
Pr.232 to Pr.239
130
Pr. 59 = 1, 2 ∗1 Remote setting (setting clear) Pr. 59 132
Pr. 270 = 1 ∗2 Stop-on contact selection 0 Pr. 270, Pr. 275, Pr. 276 158
1RM
Pr. 59 = 0 (initial value) Middle-speed operation command
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27,
Pr. 232 to Pr. 239
130
Pr. 59 = 1, 2 ∗1 Remote setting (deceleration) Pr. 59 132
2RH
Pr. 59 = 0 (initial value) High-speed operation command
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27,
Pr. 232 to Pr. 239
130
Pr. 59 = 1, 2 ∗1 Remote setting (acceleration) Pr. 59 132
3RT
Second function selection Pr. 44 to Pr. 51 165
Pr. 270 = 1 ∗2 Stop-on contact selection 1 Pr. 270, Pr. 275, Pr. 276 158
4, 5, 7 For manufacturer setting. Do not set.
8REX
15-speed selection (combination with three speeds RL, RM,
RH)
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27,
Pr. 232 to Pr. 239
130
10, 12 For manufacturer setting. Do not set.
14 X14 PID control valid terminal Pr. 127 to Pr. 132, Pr. 134 203
15 BRI Brake opening completion signal Pr. 278 to Pr. 283 160
16 For manufacturer setting. Do not set.
18 X18 V/F switchover (V/F control is performed when X18 is ON) Pr. 80, Pr. 81, Pr. 800
112, 114,
117, 146
24 MRS Output stop Pr. 17 166
25, 62,
65 to 67
For manufacturer setting. Do not set.
9999 No function
NOTE
Changing the assignment of a virtual terminal of CC-Link communication with Pr. 180 to Pr. 184 (input terminal function
selection) may affect other functions. Set parameters after confirming the function of each virtual terminal.
Same function can be assigned to two or more virtual terminals. In this case, the logic of virtual terminals input is OR.
The priorities of the speed commands are in order of multi-speed setting (RH, RM, RL, REX) > PID (X14).
Same virtual terminals are used to assign multi-speed (7 speeds) and remote setting. They cannot be set individually.
(Same signal is used since multi-speed (7 speeds) setting and remote setting are not used to set speed at the same
time.)
Switch the control method using external terminal (X18 signal) during an inverter stop. If control method between V/F
control and Advanced (General-purpose magnetic) flux vector control is switched during the operation, the actual
switchover does not take place until the inverter stops. In addition, if control method is switched to V/F control during
the operation, only second function becomes valid as V/F control and second function are selected simultaneously in
V/F control.