Mitsubishi Electric FR-E540 Instruction Manual Page 164

  • Download
  • Add to my manuals
  • Print
  • Page
    / 217
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 163
PARAMETERS
151
#
You can set the output frequency of the inverter-operated motor at which the commercial power supply
operation motors start. When the output frequency higher than the preset value continues for longer than
the time set in Pr. 515, the commercial power supply motors start. In this case, the starting sequence
depends on the pattern in Pr. 501. Here, the Pr. 509 value means the set value at which the commercial
power supply motors start when the number of commercial power supply motors running is 0.
Parameter Number Name Setting Range Setting Increments
Factory Setting
<EC version>
509 Auxiliary motor 1 starting frequency
0 to 120Hz
0.01Hz
60Hz
<50Hz>
510 Auxiliary motor 2 starting frequency
0 to 120Hz
0.01Hz
60Hz
<50Hz>
511 Auxiliary motor 3 starting frequency
0 to 120Hz
0.01Hz
60Hz
<50Hz>
#
You can set the output frequency of the inverter-operated motor at which the commercial power supply
operation motors stop. When the output frequency lower than the preset value continues for longer than the
time set in Pr. 516, the commercial power supply motors stop. In this case, the stopping sequence depends
on the pattern in Pr. 501. Here, the Pr. 512 value means the set value at which the commercial power
supply motors stop when the number of commercial power supply motors running is 1.
Parameter Number Name Setting Range Setting Increments Factory Setting
512 Auxiliary motor 1 stopping frequency 0 to 120Hz 0.01Hz 0Hz
513 Auxiliary motor 2 stopping frequency 0 to 120Hz 0.01Hz 0Hz
514 Auxiliary motor 3 stopping frequency 0 to 120Hz 0.01Hz 0Hz
#
You can set the delay time until the auxiliary motor is started. The auxiliary motor starts actually when the
time set in Pr. 515 elapses after the output frequency of the inverter operation motor has risen to or above
the value set in any of Pr. 509 to Pr. 511.
Parameter Number Name Setting Range Setting Increments Factory Setting
515 Auxiliary motor start delay time 0 to 3600s 0.1s 5s
#
You can set the delay time until the auxiliary motor is stopped. The auxiliary motor stops actually when the
time set in Pr. 516 elapses after the output frequency of the inverter operation motor has dropped to or
below the value set in any of Pr. 512 to Pr. 514.
Parameter Number Name Setting Range Setting Increments Factory Setting
516 Auxiliary motor stop delay time 0 to 3600s 0.1s 5s
#
You can set the MC switching interlock time (e.g. time from when RI01 turns off until R01 turns on) when
Pr. 501 = 2.
Parameter Number Name Setting Range Setting Increments Factory Setting
502 MC switching interlock time 0 to 100s 0.1s 1s
#
You can set the time from MC switch-over to a start (time from when RI01 turns off and RI02 turns on until
inverter output starts) when Pr. 501 = 2. Set this time a little longer than the MC switching time.
Parameter Number Name Setting Range Setting Increments Factory Setting
503 Start waiting time 0 to 100s 0.1s 1s
#
You can set the deceleration time until the output frequency varies by the decrement = Pr. 509 to Pr. 512
(for M2) if a motor connection occurs under advanced PID control. When the setting is 9999, the output
frequency is not forcibly changed.
Parameter Number Name Setting Range Setting Increments Factory Setting
504
Auxiliary motor connection-time
deceleration time
0 to 3600s 0.1s/0.01s 1s
#
You can set the acceleration time until the output frequency varies by the increment = Pr. 509 to Pr. 512 (for
M2) if a motor disconnection occurs under advanced PID control. When the setting is 9999, the output
frequency is not forcibly changed.
Parameter Number Name Setting Range Setting Increments Factory Setting
505
Auxiliary motor disconnection-time
acceleration time
0 to 3600s, 9999 0.1s/0.01s 1s
4
Page view 163
1 2 ... 159 160 161 162 163 164 165 166 167 168 169 ... 216 217

Comments to this Manuals

No comments