PARAMETERS
77
4.2.12 Stall prevention (Pr. 22, Pr. 23, Pr. 66, Pr. 148, Pr. 149, Pr. 154)
Pr. 22 "stall prevention operation level"
Pr. 23 "stall prevention operation level
compensation factor at double speed"
Pr. 66 "stall prevention operation level reduction
starting frequency"
Pr. 148 "stall prevention operation level at 0V input"
Pr. 149 "stall prevention operation level at 10V input"
Pr. 154 "voltage reduction selection during stall prevention operation"
#
Set the output current level at which the output frequency is adjusted so that the inverter will not come to an
alarm stop due to overcurrent etc.
#
For high-speed operation at or over the more base frequency, acceleration may not be made because the
motor current does not increase. To improve the operation characteristics of the motor in such a case, the
stall prevention level in the high-frequency range can be reduced. This is effective for operation of a
centrifugal separator up to the high-speed range. Normally, set 60Hz
50Hz
in Pr. 66 and 100% in Pr. 23.
#
In order to provide torque during stall prevention, Pr. 154 is factory-set not to reduce the output voltage. The
setting of reducing the output voltage further decreases the probability of overcurrent trip occurrence.
#
The stall prevention operation level can be varied by entering the analog signal into terminal 1.
Parameter Number Factory Setting Setting Range Remarks
22 120% 0 to 150%, 9999 9999: Analog variable
23 9999 0 to 200%, 9999 9999: Constant according to Pr. 22
66 60Hz
50Hz
0 to 120Hz
148 120% 0 to 150% (Bias)
149 150% 0 to 150% (Gain)
154 1 0, 1
0: Output voltage reduced
1: Output voltage not reduced
Pr.22
Pr.23
Pr.66
120Hz
Output
frequency (Hz)
Stall prevention
operation level (%)
= 9999
Reduction ratio
compensation factor (%)
(150%)
(120%)
0%
0V
Pr.148
Pr.149
10(5)V
Input voltage (V)
(across frequency setting terminals 1-5)
(Pr.22=120%, Pr.23=100%, Pr.66=60Hz
)
Setting example
120
90
75
060
80 100
120
112.5
Pr.23
Stall prevention
operation level (%)
Stall prevention
operation level (%)
Output
frequency (Hz)
Pr. 9 "electronic thermal O/L relay"
Pr. 48 "second stall prevention
operation current"
Pr. 49 "second stall prevention
operation frequency"
Pr. 73 "0-5V/0-10V selection"
Pr. 156 "stall prevention operation
selection"
Related parameters