When setting parameters, refer to the instruction manual (applied) and understand instructions.
If an alarm occurs, the inverter resets itself automatically to restart.
You can also select the alarm description for a retry.
When automatic restart after instantaneous power failure is
selected (Pr.57 Restart coasting time
9999), restart operation is
performed at retry operation as at an instantaneous power failure.
Use Pr.65 to select the alarm to be activated for retries.
"
"
indicates the alarms selected for retry.
Set the number of retries at alarm occurrence in Pr.67.
Use Pr.68 to set the waiting time from when an inverter alarm occurs
until a retry is made in the range 0 to 10s.
Reading the Pr.69 value provides the cumulative number of
successful restart times made by retry.
Setting of the used motor selects the thermal characteristic appropriate
for the motor.
Setting is necessary when using a constant-torque motor. Thermal
characteristic of the electronic thermal relay function suitable for
the motor is set.
*1 Motor constants of Mitsubishi high efficiency motor SF-HR
*2 Motor constants of Mitsubishi constant-torque motor SF-HRCA.
*3 Star connection
*4 Delta connection
For the 5.5K and 7.5K, the Pr. 0 Torque boost and Pr. 12 DC injection
brake operation voltage settings are automatically changed according
to the Pr. 71 and Pr.450 settings as follows.
Retry function at alarm occurrence
Pr.65 Retry selection Pr.67
Number of retries at alarm occurrence
Pr.68 Retry waiting time Pr.69 Retry count display erase
Alarm
Indication for
Retry
Pr.65 Setting
0 1 2 3 4 5
E.OC1
E.OC2
E.OC3
E.OV1
E.OV2
E.OV3
E.THM
E.THT
E.IPF
E.UVT
E. BE
E. GF
E.OHT
E.OLT
E.OPT
E.OP1
E.OP2
E.OP3
E. PE
E.MB1
E.MB2
E.MB3
E.MB4
E.MB5
E.MB6
E.MB7
E.OS
E.OSD
E.OD
E.PTC
E.CDO
E.SER
E.ILF
Pr.67 Setting Description
0 (initial value)
No retry function
1 to 10
Set the number of retries at alarm occurrence.
An alarm output is not provided during retry
operation.
101 to 110
Set the number of retries at alarm occurrence. (The
setting value of minus 100 is the number of retries.)
An alarm output is provided during retry operation.
66
Refer to the section about Pr. 22.
67 to 69
Refer to the section about Pr. 65.
70
Refer to the section about Pr. 30.
Pr.
65, 67 to 69
P
r.
Pr.
Pr.
Pr.
Pr.
Pr.
Pr.
Motor selection (applied motor)
Pr.71 Applied motor Pr.450 Second applied motor
Pr.71,
Pr.450
Setting
Thermal Characteristic of the
Electronic Thermal Relay
Function
Motor
({: Motor used)
Standard
(SF-JR,
etc.)
Constant
torque
(SF-JRCA,
etc.)
Vector
(SF-V5RU,
etc.)
0
Thermal characteristics of a standard motor
(Pr. 71 initial value)
1
Thermal characteristics of the
Mitsubishi constant-torque motor
2
Thermal characteristics of a standard motor
Adjustable 5 points V/F
20
Mitsubishi standard motor SF-JR4P
(1.5kW or less) thermal characteristic
for the constant-torque motor
30
Thermal characteristics of the
Mitsubishi vector motor SF-V5RU
40
Thermal characteristic of Mitsubishi
standard motor SF-HR
*1
50
Thermal characteristic of Mitsubishi
constant-torque motor SF-HRCA
*2
3
Standard
Select "offline
auto tuning
setting"
13
Constant-torque
23
Mitsubishi standard
SF-JR4P (1.5kW or less)
33
Mitsubishi vector
SF-V5RU/SF-THY
43
Mitsubishi high
efficiency SF-HR
*1
53
Mitsubishi constant-
torque SF-HRCA
*2
4
Standard
Auto tuning data
can be read,
changed, and set
14
Constant-torque
24
Mitsubishi standard
SF-JR4P (1.5kW or less)
34
Mitsubishi vector
SF-V5RU/SF-THY
44
Mitsubishi high
efficiency SF-HR
*1
54
Mitsubishi constant-
torque SF-HRCA
*2
5
Standard *3
Direct input of
motor constants
is enabled
15
Constant-torque *3
6
Standard *4
16
Constant-torque *4
7
Standard *3
Motor constants
direct input
+
offline auto
tuning
17
Constant-torque *3
8
Standard *4
18
Constant-torque *4
9999
Function invalid (only Pr.450 can be set, initial value)
Pr.71
Pr.450
Standard Motor Setting
0, 2, 3 to 8, 20, 23, 24, 40, 43, 44
Constant-Torque Motor
Setting
1, 13 to 18, 50, 53, 54
Pr.0
3% 2%
Pr.12
4% 2%
Pr.
71, 450
P
r.