When setting parameters, refer to the instruction manual (applied) and understand instructions.
When a power failure or undervoltage occurs, the inverter can be
decelerated to a stop or can be decelerated and re-accelerated to
the set frequency.
* When the setting of Pr.21 Acceleration/deceleration time increments is "0"
(initial value), the setting range is "0 to 3600s" and setting increments are
"0.1s" and when the setting is "1", the setting range is "0 to 360s" and the
setting increments are "0.01s".
(1) Power failure stop mode (Pr.261="1" "11")
If power is restored during power failure deceleration,
deceleration to a stop is continued and the inverter
remaines stopped. To restart, turn off the start signal once,
then turn it on again.
(2) Original operation continuation at instantaneous
power failure function (Pr.261="2" "12")
When power is restored during deceleration after a power
failure, acceleration is made again up to the set frequency.
When this function is used in combination with the
automatic restart after instantaneous power failure
operation, deceleration can be made at a power failure
and acceleration can be made again after power
restoration.
When power is restored after a stop by deceleration at an
instantaneous power failure, automatic restart operation is
performed if automatic restart after instantaneous power
failure has been selected (Pr.57
"9999")
Operation at instantaneous power failure
Pr.261 Power failure stop selection Pr.262
Subtracted frequency at deceleration start
Pr.263 Subtraction starting frequency Pr.264
Power-failure deceleration time 1
Pr.265 Power-failure deceleration time 2
Pr.266 Power failure deceleration time switchover frequency
Pr.294 UV avoidance voltage gain
Pr.
Number
Setting Range Description
261
0(initial value)
Coasting to stop
When undervoltage or power failure
occurs, the inverter output is shut off.
1
Without UV
avoidance
When undervoltage or
a power failure occurs,
the inverter can be
decelerated to a stop.
11
With UV
avoidance
2
Without UV
avoidance
When undervoltage or
a power failure occurs,
the inverter can be
decelerated to a stop.
If power is restored
during a power failure,
the inverter accelerates
again.
12
With UV
avoidance
262 0 to 20Hz
Normally operation can be performed
with the initial value unchanged. But
adjust the frequency according to the
magnitude of the load specifications
(moment of inertia, torque).
263
0 to 120Hz
When output frequency Pr.263
Decelerate from the speed obtained
from output frequency minus Pr.262.
When output frequency Pr.263
Decelerate from output frequency
9999
Decelerate from the speed obtained
from output frequency minus Pr. 262.
264 0 to 3600s/360s *
Set a deceleration slope down to the
frequency set in Pr.266.
265
0 to 3600s/360s *
Set a deceleration slope below the
frequency set in Pr.266.
9999
Same slope as in Pr.264
266 0 to 400Hz
Set the frequency at which the
deceleration slope is switched from the
Pr.264 setting to the Pr.265 setting.
294 0 to 200%
Adjust response level at UV avoidance
operation. A larger setting will improve
responsiveness to the bus voltage
change. Since the regeneration amount
is large when the inertia is large,
decrease the setting value.
Pr.
261 to 266, 294
P
r.
Pr.264
Power-failure
deceleration time 1
Pr.265
Power-failure
deceleration
time 2
Time
Power supply
Output
frequency
Subtracted
frequency at
deceleration start
Pr.262
Power-failure
deceleration
time switchover
frequency
P
r.266
267
Refer to the section about Pr. 73.
268
Refer to the section about Pr.52.
269
Parameter for manufacturer setting. Do not set.
During deceleration at
occurrence of power failure
During stop at
occurrence of
power failure
STF
Y46
Time
Turn off STF once to make acceleration again
Power
supply
Output frequency
Pr.261 = 1
IPF
Power
supply
Time
Output
frequency
Y46
During deceleration
at occurrence of
power failure
Reacceleration
When power is restored during
deceleration
Pr.261 = 2
During power failure
Power
supply
Output
frequency
Y46
During deceleration
at occurrence of
power failure
Automatic restart
after instantaneous
power failure
Reset time + Pr.57
Pr.261 = 2, Pr.57 9999
When used with automatic restart
after instantaneous power failure
Time
Pr.
Pr.
Pr.
Pr.
Pr.
Pr.