When setting parameters, refer to the instruction manual (applied) and understand instructions.
This function is used to output from the inverter the mechanical
brake opening completion signal timing signal in vertical lift and
other applications.
This function prevents the load from dropping with gravity at a start
due to the operation timing error of the mechanical brake or an
overcurrent alarm from occurring at a stop, ensuring secure
operation.
<Operation example>
At start: When the start signal is input to the inverter, the inverter
starts running. When the internal speed command reaches
the value set in Pr.278 and the output current is not less
than the value set in Pr.279, the inverter outputs the brake
opening request signal (BOF) after the time set in Pr.280
has elapsed.
When the time set in Pr.281 elapses after the brake opening
completion signal (BRI) was activated, the inverter
increases the output frequency to the set speed.
At stop: When the speed has decreased to the frequency set in
Pr.282 , the brake opening request signal (BOF) is turned
off. When the time set in Pr.283 elapses after the brake
operation confirmation signal (BRI) was activated, the
inverter output is switched off.
* If Pr.292 = "8" (mechanical brake opening completion signal
not input), this time is the time after the brake opening request
signal is output.
1)Pr.292 = "7" (brake opening completion signal input)
2)Pr.292 = "8" (brake opening completion signal not input)
If the difference (absolute value) between the speed command
value and actual speed exceeds the Pr. 285 Speed deviation excess
detection frequency setting for longer than the time set in Pr. 853 Speed
deviation time during speed control under vector control, speed
deviation excessive occurs and error "E. OSD" appears, resulting in
a stop.
Brake sequence function
Pr.278 Brake opening frequency Pr.279 Brake opening current
Pr.280
Brake opening current detection time
Pr.281 Brake operation time at start
Pr.282 Brake operation frequency Pr.283 Brake operation time at stop
Pr.284
Deceleration detection function selection
Pr.285 Overspeed detection frequency
Pr.292
Automatic acceleration/deceleration
Pr.
278 to 285, 292
P
r.
Magnetic flux
Magnetic flux
Magnetic flux
Sensorless
Sensorless
Sensorless Vector
Vector
STF
ON
Output I
Brake opening request
(BOF signal)
ON
Electromagnetic brake
operation
Opened
Closed
Closed
Time
Brake opening completion
(BRI signal)
ON
Pr.278
Pr.282
Target frequency
Pr.13
Pr.280
Pr.281
Output frequency(Hz)
Pr.283
Pr.279
STF
ON
I
ON
Pr.278
Pr.282
Target frequency
(Hz)
Pr.281
Pr.283
Pr.280
Pr.279
Pr.13
Output frequency
Output
Brake opening request
(BOF signal)
Electromagnetic brake
operation
Closed
Opened
Closed
Time
Pr.
Number
Setting
Range
Description
278 0 to 30Hz
Set to the rated slip frequency of the motor + about
1.0Hz.
This parameter may be only set if Pr.278 Pr.282.
279 0 to 220%
Generally, set this parameter to about 50 to 90%. If
the setting is too low, the load is liable to drop due to
gravity at start.
Suppose that the rated inverter current is 100%.
280 0 to 2s
Generally, set this parameter to about 0.1 to 0.3s.
281 0 to 5s
Pr.292 = 7: Set the mechanical delay time until the
brake is loosened.
Pr.292 = 8: Set the mechanical delay time until the
brake is loosened+about 0.1 to 0.2s.
282 0 to 30Hz
At this frequency, the brake opening request signal
(BOF) is switched off.Generally, set this parameter to
the Pr.278 setting + 3 to 4Hz.
This parameter may only be set if Pr.282 Pr.278.
283 0 to 5s
Pr.292 =7: Set the mechanical delay time until the
brake is closed + 0.1s.
Pr.292 =8: Set the mechanical delay time until the
brake is closed + 0.2 to 0.3s.
284
0
(initial value)
Deceleration is not detected.
1
If deceleration is not normal during deceleration
operation, the inverter alarm (E.MB2) is provided to
shut off the output and turn off the brake opening
request signal (BOF).
285
0 to 30Hz
When brake sequence function is made valid under
encoder feedback control
If (detected frequency) - (output frequency) > Pr.285
the inverter alarm (E.MB1) is provided to shut off the
output and turn off the brake opening request signal
(BOF).
9999
(initial value)
Overspeed is not detected.
292
0, 1, 3,
5 to 8, 11
Brake sequence function is made valid when a setting
is "7 or 8".
Speed deviation excess detection
Pr.285 Speed deviation excess detection frequency
Pr.853 Speed deviation time
Pr.
285, 853
P
r.
Vector
Vector
(Hz)
Set frequency
Actual speed
Time
Speed deviation
excessive error activated
(E. OSD)
ONOFF
A
larm output
(across A-C)
Pr.853
Pr.285
Output frequency
Page view 60