When setting parameters, refer to the instruction manual (applied) and understand instructions.
When online auto tuning is selected, excellent torque accuracy is provided
by temperature compensation even if the secondary resistance value of
the motor varies with the rise of the motor temperature.
Select magnetic flux observer when performing vector control.
* Only Pr.95 can be set.
Perform offline auto tuning before performing start-time tuning of the
online auto tuning. Data needs to be calculated.
For using start-time tuning in elevator, examine the utilization of a
brake sequence for the brake opening timing at a start. Though the
tuning ends in about a maximum of 500ms after a start, torque is not
provided fully during that period. Therefore, note that there may be a
possibility of drop due to gravity.
For the SF-V5RU, SF-JR (with encoder) or SF-HRCA (with
encoder), it is not necessary to perform offline auto tuning to select
adaptive magnetic flux observer. (However
, perform offline auto
tuning when the wiring length is long.)
A dedicated V/F pattern can be made by freely setting the V/F
characteristic between a startup and the base frequency and base
voltage under V/F control (frequency voltage/frequency).
The torque pattern that is optimum for the machine's characteristic
can be set.
Set "2" in Pr.71 and voltage and frequency in Pr.100 to Pr.109 .
When frequency values at each point are the same, write disable
error ( ) appears. Set frequency and voltage within the range of
Pr.3 Base frequency and Pr.19 Base frequency voltage .
When Pr.19 Base frequency voltage ="8888" or "9999", Pr.71 cannot be
set to "2". When setting "2" in Pr.71, set the rated voltage value in
Pr.19.
(1) Initial settings and specifications of RS-485
communication (Pr.117 to Pr.124, Pr.331 to Pr.337,
Pr.341)
Used to perform required settings for RS-485 communication
between the inverter and personal computer.
There are two different communications: communication
using the PU connector of the inverter and communication
using the RS-485 terminals.
You can perform parameter setting, monitoring, etc. using
the Mitsubishi inverter protocol or Modbus-RTU protocol.
To make communication between the personal computer
and inverter, initialization of the communication
specifications must be made to the inverter.
Data communication cannot be made if the initial settings
are not made or there is any setting error.
*1 When making communication through Modbus-RTU protocol with the
RS-485 terminals, the setting range of Pr.331 within parenthesis is
applied.
*2 The values in parenthesis are added to the setting range of Pr.332.
Online auto tuning
Pr.95 Online auto tuning selection Pr.574
Second motor online auto tuning
Pr.95, Pr.574 Setting Description
0 (initial value)
Online auto tuning is not performed
1
Start-time tuning (at start-up)
2*
Magnetic flux observer (normal)
96
Refer to the section about Pr. 82.
Adjustable 5 points V/F
Pr.100 V/F1(first frequency) Pr.101 V/F1(first frequency voltage)
Pr.102 V/F2(second frequency) Pr.103 V/F2(second frequency voltage)
Pr.104 V/F3(third frequency) Pr.105 V/F3(third frequency voltage)
Pr.106 V/F4(fourth frequency) Pr.107 V/F4(fourth frequency voltage)
Pr.108 V/F5(fifth frequency) Pr.109 V/F5(fifth frequency voltage)
110, 111
Refer to the section about Pr.7.
112
Refer to the section about Pr.0.
113
Refer to the section about Pr.3.
114, 115
Refer to the section about Pr.22.
116
Refer to the section about Pr.41.
Pr.
95, 574
P
r.
Magnetic flux
Magnetic flux
Magnetic flux
Sensorless
Sensorless
Sensorless
Vector
Vector
Pr.
Pr.
Pr.
100 to 109
P
r.
V/F
V/F
V/F
B
ase frequency
voltage
Pr.19
Base frequency
Pr.3
Torque boost
Pr.0
V/F Characteristic
0
V/F5
V/F4
V/F3
V/F2
V/F1
Frequency
Voltage
Pr.
Pr.
Pr.
Pr.
Pr.
Pr.
Pr.
Pr.
Pr.
Pr.
Communication initial setting
Pr.117 PU communication station number
Pr.118 PU communication speed
Pr.119
PU communication stop bit length
Pr.120 PU communication parity check
Pr.121
Number of PU communication retries
Pr.122
PU communication check time interval
Pr.123 PU communication waiting time setting
Pr.124 PU communication CR/LF presence/absence selection
Pr.331 RS-485 communication station number
Pr.332 RS-485 communication speed
Pr.333
RS-485 communication stop bit length
Pr.334
RS-485 communication parity check selection
Pr.335
RS-485 communication retry count
Pr.336
RS-485 communication check time interval
Pr.337
RS-485 communication waiting time setting
Pr.341
RS-485 communication CR/LF selection
Pr.342
Communication EEPROM write selection
Pr.343
Communication error count
Pr.549 Protocol selection
Pr.
Number
Setting Range Description
117
331
0 to 31
(0 to 247)
*1
Specify the inverter station number.
Set the inverter station numbers when two or
more inverters are connected to one personal
computer.
118
332
48, 96, 192, 384
(3, 6, 12, 24)
*2
Set the communication speed.
The setting value × 100 equals the
communication speed.
For example, the communication speed is
19200bps when the setting value is 192.
119
333
Stop bit length Data length
0 1bit
8bit
1 (initial value) 2bit
10 1bit
7bit
11 2bit
120
334
0
Without parity check
1
With odd parity check
2 (initial value)
With even parity check
121
335
0 to10
Set the permissible number of retries at
occurrence of a data receive error. If the
number of consecutive errors exceeds the
permissible value, the inverter will come to an
alarm stop.
9999
If a communication error occurs, the inverter
will not come to an alarm stop.
122
336
0
No PU connector communication
Communication with RS-485 terminals can be
made, but the inverter will come to an alarm
stop in the NET operation mode.
0.1 to 999.8s
Set the interval of communication check time.
If a no-communication state persists for longer
than the permissible time, the inverter will
come to an alarm stop.
9999 (initial value)
No communication check
123
337
0 to 150ms
Set the waiting time between data
transmission to the inverter and response.
9999 (initial value)
Set with communication data.
124
341
0
Without CR/LF
1 (initial value)
With CR
2
With CR/LF
Pr.
117 to 124, 331 to 337, 341 to 343, 549
P
r.