When setting parameters, refer to the instruction manual (applied) and understand instructions.
On the assumption that the Pr.849 setting 100% as 0, the
offset voltage is offset as follows:
100%<Pr.849...positive side
100%>Pr.849...negative side
The offset voltage is found by the following formula.
You can select the reset input acceptance, disconnected PU (FR-
DU07/FR-PU04/FR-PU07) connector detection function and PU
stop function.
Reset selection
You can select the operation timing of reset function (RES
signal, reset command through communication) input.
Disconnected PU detection
This function detects that the PU (FR-DU07/FR-PU04/FR-
PU07) has been disconnected from the inverter for longer
than 1s and causes the inverter to provide an alarm output
(E.PUE) and come to an alarm stop.
PU stop selection
In any of the PU operation, external operation and network
operation modes, the motor can be stopped by
pressing of the PU.
At alarm occurrence, its description can be output as a 4-bit digital
signal from the open collector output terminals.
The alarm code can be read by a programmable controller, etc.,
and its corrective action can be shown on a display, etc.
The following table indicates alarm codes to be output.
(0: output transistor off, 1: output transistor on)
You can select whether write to various parameters can be
performed or not. Use this function to prevent parameter values
from being rewritten by misoperation.
This function can prevent reverse rotation fault resulting from the
incorrect input of the start signal.
Offset voltage =
Voltage at 100%
(according to the
Pr.73
setting)
×
Pr.849
-100
[V]
100
Reset selection, disconnected PU detection
Pr.75 Reset selection/disconnected PU detection/PU stop selection
Pr.75
Setting
Reset Selection
Disconnected PU
Detection
PU Stop Selection
0
Reset input normally
enabled
If the PU is
disconnected,
operation will be
continued as-is.
Pressing
decelerates the motor
to a stop only in the PU
operation mode.
1
Reset input enabled only
when the protective
function is activated
2
Reset input normally
enabled
When the PU is
disconnected, the
inverter output is shut
off.
3
Reset input enabled only
when the protective
function is activated
14
(initial
value)
Reset input normally
enabled
If the PU is
disconnected,
operation will be
continued as-is.
Pressing
decelerates the motor
to a stop in any of the
PU, external and
communication
operation modes.
15
Reset input enabled only
when the protective
function is activated
16
Reset input normally
enabled
When the PU is
disconnected, the
inverter output is shut
off.
17
Reset input enabled only
when the protective
function is activated
0% 100%
(10V or 5V)
Pr.849 setting
Frequency
command
Speed setting
signal
Slope determined
according to Pr.125
and C2 to C4
Slope does not
change.
0% 200%100%
Pr.
75
P
r.
Output function of alarm code
Pr.76 Alarm code output selection
Pr.76 Setting Description
0 (initial value)
Without alarm code output
1
With alarm code output (refer to the table below)
2
Alarm code output at alarm occurrence only (refer to the table
below)
Operation Panel
Indication
(FR-DU07)
Output of Output Terminals
Alarm Code
SU IPF OL FU
Normal*
0 0 0 0 0
E.OC1
0 0 0 1 1
E.OC2
0 0 1 0 2
E.OC3
0 0 1 1 3
E.OV1 to
E.OV3
0 1 0 0 4
E.THM
0 1 0 1 5
E.THT
0 1 1 0 6
E.IPF
0 1 1 1 7
E.UVT
1 0 0 0 8
E.FIN
1 0 0 1 9
E.BE
1 0 1 0 A
E. GF
1 0 1 1 B
E.OHT
1 1 0 0 C
E.OLT
1 1 0 1 D
E.OPT
1 1 1 0 E
E.OP3
1 1 1 0 E
Other than the
above
1 1 1 1 F
* When Pr.76 = "2", the output terminals output the signals assigned to Pr.190 to Pr.196
Prevention of parameter rewrite
Pr.77 Parameter write selection
Pr. 77 Setting Description
0 (initial value)
Write is enabled only during a stop.
1
Parameter write is not enabled.
2
Parameter write is enabled in any operation mode regardless of
operation status.
Prevention of reverse rotation of the motor
Pr.78 Reverse rotation prevention selection
Pr.78 Setting Description
0 (initial value)
Both forward and reverse rotations allowed
1
Reverse rotation disabled
2
Forward rotation disallowed
Pr.
76
P
r.
Pr.
77
P
r.
Pr.
78
P
r.