Continuous operation with 100% torque even at low
speed of 3Hz is possible. (when using real sensorless
vector control)
For the 37kW or less, load torque is not need to be
reduced even at a low speed and constant torque (100%
torque) continuous operation is possible within the range
of speed ratio 1/20 (3 to 60Hz). (The characteristic of
motor running at 60Hz or more is that output torque is
constant.)
Installation size is the same as that of the standard motor
Note that operation characteristic in the chart below can
not be obtained if V/F control is employed.
Continuous rated range of use (real sensorless vector control)
Please contact us separately for the motor constants during real sensorless vector control.
When the vector control dedicated motor (SF-V5RU) and inverter are used, the torque characteristics are as shown below.
Application to constant-torque motors
SF-HRCA type Standard specifications (indoor type)
Output
(kW)
Number
of Poles
Frequency
Range
Common Specifications
0.4
4
3 to 120Hz
Standard frequency 60Hz
Rotation direction (CCW) is
counterclockwise when viewed
from the motor end
Lead wire
3.7kW or less.....3 pcs.
5.5kW or more...6 or 12 pcs.
Ambient temperature: 40 °C
maximum
Protective structure is JP44
0.75
1.5
2.2
3.7
5.5
7.5
11
3 to 100Hz
15
18.5
22
30
37
3 to 65Hz45
55
60Hz Torque Reference (when inverter is 0.4kW to 37kW) 60Hz Torque Reference (when inverter is 45kW to 55kW)
Application to vector control dedicated motors (SF-V5RU) (55kW or less)
Motor torque
150
100
200
70
(60)
63
(50)
50
(45)
45
(40)
0
3
0.3
20
60
120
Values in parenthesis apply to the 0.4kW to 0.75kW
Maximum torque
for short time
(5.5kW to 37kW)
Maximum torque for short time (0.4kW to 3.7kW)
Continuous
operation
torque
220V
200V
Output torque
(%)
Output frequency (Hz)
150
100
70
80
63
50
45
0
3
0.3
2010
60
120
Maximum torque
for short time
200V
220V
Continuous
operation
torque
Output torque
(%)
Output frequency (Hz)
Constant power
Maximum torque for short time
Speed (r/min)
Continuous
operation torque
Continuous
operation torque
(%)
(%)
50
0
75
100
1500 3000
150
Constant power
Reduced outpu
t
Maximum torque for short time
Speed (r/min)
40
0
60
63
94
100
1500
2400 3000
150
When inverter is 1.5kW to 22kW When inverter is 30kW to 55kW
Output torque
Output torque