Peripheral devices/cable size list
Voltage
Motor
Output
(kW)
*1
Applicable Inverter
Type
Moulded Case Circuit Breaker (MCCB)*2 or
Earth Leakage Current Breaker (ELB)
Input Side Magnetic
Contactor*3
Recommended
Cable Size
(mm
2
)*4
Reactor connection Reactor connection
R, S, T U, V, W
Without With Without With
200V class
0.4 FR-A720-0.4K 30AF 5A 30AF 5A S-N10 S-N10 2 2
0.75 FR-A720-0.75K 30AF 10A 30AF 10A S-N10 S-N10 2 2
1.5 FR-A720-1.5K 30AF 15A 30AF 15A S-N10 S-N10 2 2
2.2 FR-A720-2.2K 30AF 20A 30AF 15A S-N10 S-N10 2 2
3.7 FR-A720-3.7K 30AF 30A 30AF 30A S-N20, N21 S-N10 3.5 3.5
5.5 FR-A720-5.5K 50AF 50A 50AF 40A S-N25 S-N20, N21 5.5 5.5
7.5 FR-A720-7.5K 100AF 60A 50AF 50A S-N25 S-N25 14 8
11 FR-A720-11K 100AF 75A 100AF 75A S-N35 S-N35 14 14
15 FR-A720-15K 225AF 125A 100AF 100A S-N50 S-N50 22 22
18.5 FR-A720-18.5K 225AF 150A 225AF 125A S-N65 S-N50 38 38
22 FR-A720-22K 225AF 175A 225AF 150A S-N80 S-N65 38 38
30 FR-A720-30K 225AF 225A 225AF 175A S-N95 S-N80 60 60
37 FR-A720-37K 400AF 250A 225AF 225A S-N150 S-N125 80 80
45 FR-A720-45K 400AF 300A 400AF 300A S-N180 S-N150 100 100
55 FR-A720-55K 400AF 400A 400AF 350A S-N220 S-N180 100 100
75 FR-A720-75K
NV400AF400A S-N300 125 125
90 FR-A720-90K
NV400AF400A S-N300 150 150
400V class
0.4
FR-A740-0.4K
30AF 5A 30AF 5A S-N10 S-N10 2 2
0.75
FR-A740-0.75K
30AF 5A 30AF 5A S-N10 S-N10 2 2
1.5
FR-A740-1.5K
30AF 10A 30AF 10A S-N10 S-N10 2 2
2.2 FR-A740-2.2K 30AF 10A 30AF 10A S-N10 S-N10 2 2
3.7
FR-A740-3.7K
30AF 20A 30AF 15A S-N10 S-N10 2 2
5.5
FR-A740-5.5K
30AF 30A 30AF 20A S-N20 S-N11, N12 2 2
7.5
FR-A740-7.5K
30AF 30A 30AF 30A S-N20 S-N20 3.5 3.5
11
FR-A740-11K
50AF 50A 50AF 40A S-N20 S-N20 5.5 5.5
15 FR-A740-15K 100AF 60A 50AF 50A S-N25 S-N20 8 8
18.5 FR-A740-18.5K 100AF 75A 100AF 60A S-N25 S-N25 14 8
22
FR-A740-22K
100AF 100A 100AF 75A S-N35 S-N25 14 14
30
FR-A740-30K
225AF 125A 100AF 100A S-N50 S-N50 22 22
37
FR-A740-37K
225AF 150A 225AF 125A S-N65 S-N50 22 22
45
FR-A740-45K
225AF 175A 225AF 150A S-N80 S-N65 38 38
55 FR-A740-55K 225AF 200A 225AF 175A S-N80 S-N80 60 60
75 FR-A740-75K 225AF 225A S-N95 60 60
90
FR-A740-90K
225AF 225A S-N150 60 60
110
FR-A740-110K
225AF 225A S-N180 80 80
132
FR-A740-132K
400AF 400A S-N220 100 125
150
FR-A740-160K
400AF 400A S-N300 125 125
160 FR-A740-160K 400AF 400A S-N300 125 125
185 FR-A740-185K 400AF 400A S-N300 150 150
220
FR-A740-220K
600AF 500A S-N400 2 × 100 2 × 100
250
FR-A740-250K
600AF 600A S-N600 2 × 100 2 × 100
280
FR-A740-280K
600AF 600A S-N600 2 × 125 2 × 125
315
FR-A740-315K
800AF 700A S-N600 2 × 150 2 × 150
355 FR-A740-355K 800AF 800A S-N600 2 × 200 2 × 200
400 FR-A740-400K 1000AF 900A S-N800 2 × 200 2 × 200
450
FR-A740-450K
1000AF 1000A
1000A rated
product
2 × 250 2 × 250
500 FR-A740-500K 1200AF 1200A
1000A rated
product
2 × 250 2 × 250
*1. Selections for use of the Mitsubishi 4-pole standard motor with power supply voltage 200VAC (200V class)/400VAC (400V class) 50Hz.
*2. Install one MCCB per inverter.
For installations in the United States or Canada, use the fuse certified by the UL and cUL.
For details, refer to the Instruction Manual (basic)
*3. Magnetic contactor is selected based on the AC-1 class. The electrical durability of magnetic contactor is 500,000 times. When the magnetic contactor is used for
emergency stop during motor driving, the electrical durability is 25 times.
When using the MC for emergency stop during motor driving or using on the motor side during commercial-power supply operation, select the class AC-3 rated current for
the motor rated current.
*4. Cable
For the 55K or less, the cable size is that of the cable (HIV cable (600V class 2 vinyl-insulated cable) etc.) with continuous maximum permissible temperature of 75°C. Assumes
that the ambient temperature is 50°C or less and the wiring distance is 20m or less.
For the 75K or more, the recommended cable size is that of the cable (e.g. LMFC (heat resistant flexible cross-linked polyethylene insulated cable)) with continuous maximum
permissible temperature of 90°C. Assumes that the ambient temperature is 50°C or less and wiring is performed in an enclosure.
MCCB INV
MCCB INV
IM
IM
Page view 83