Mitsubishi Electric PC36 Instruction Manual Page 23

  • Download
  • Add to my manuals
  • Print
  • Page
    / 50
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 22
3. PARAMETERS
3 - 8
3.5.2 Detail description
POINT
The parameter names of [Pr. Po34] and [Pr. Po35] are not displayed with the
following versions of MR Configurator/MR Configurator2. However, their setting
values are changeable. Follow the instructions in this Instruction Manual to set a
value.
MRZJW3-SETUP221E: software version C3 or below
SW1DNC-MRC2-E: software version 1.09K or below
No. Symbol Name and function
Initial
value
Setting
range
Unit
Po34 *STNO CC-Link IE communication station number selection
Use this parameter to set the station number of the servo amplifier.
Convert a decimal value to a hexadecimal value for input.
If you are using an automatic station number, which is designated by the
master station, do not change the initial value "0000h".
If you are designating a station number, set a value in the range of 1 to 120
(0001h to 0078h). A value higher the maximum value will trigger [AL. 37
parameter error].
For example) The setting value "0078h" sets the station number of 120.
The setting value "0079h" or a higher will trigger [AL. 37
parameter error].
0000h 0000h
to
0078h
Po35 *NWNO CC-Link IE communication network number
Use this parameter to set the network number of the servo amplifier.
Convert a decimal value to a hexadecimal value for input.
The network number is 1 at the initial value of "0000h".
The maximum setting value for the network number is 239.
A value higher than the maximum value will trigger [AL. 37 parameter error].
For example) The setting value "00EFh" sets the station number of 239.
The setting value "012Ch" will trigger [AL. 37 parameter error].
If an automatic number has been selected with [Pr. Po34] and the rotary
switch on the MR-J3-_T, this parameter setting is ignored. Instead, the
network number transmitted from the master station is used.
0000h 0000h
to
00EFh
Page view 22