Page view 107
PARAMETERS
95
4.2.28 Retry function (Pr. 65, Pr. 67 to Pr. 69)
Pr. 65 "retry selection"
Pr. 67 "number of retries at alarm occurrence"
Pr. 68 "retry waiting time"
Pr. 69 "retry count display erasure"
When an alarm occurs, the retry function causes the inverter to automatically reset itself to make a restart
and continue operation. You can select whether retry is made or not, alarms reset for retry, number of retries
made, and waiting time.
Parameter
Number
Factory
Setting
Setting Range
65 0 0 to 5
67 0 0 to 10, 101 to 110
68 1 s 0 to 10 s
69 0 0
<Setting>
Use Pr. 65 to select alarms to be reset for retry.
Errors Reset for Retry Setting
Display 012345
E.OC1
## ###
E.OC2
## ##
E.OC3
## ###
E.OV1
####
E.OV2
####
E.OV3
####
E.THM
#
E.THT
#
E.IPF
##
E.UVT
##
E.FIN
E. GF
##
E. LF
E.OHT
#
E.OLT
##
E.OPT
##
E.OP1
##
E.OP2
##
E.OP3
##
E. PE
##
E.PUE
E.RET
E.CPU
E. 6
E. 7
E.P24
E.CTE
Note:
#
indicates the errors selected for retry.