Mitsubishi Electric FR-E540 Instruction Manual Page 97

  • Download
  • Add to my manuals
  • Print
  • Page
    / 217
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 96
PARAMETERS
84
4.2.20 Output frequency detection (Pr. 42, Pr. 43, Pr. 50)
Pr. 42 "output frequency detection"
Pr. 43 "output frequency detection for reverse rotation"
Pr. 50 "second output frequency detection"
The output frequency signal (FU, FU2) is output when the output frequency reaches or exceeds the setting.
This function can be used for electromagnetic brake operation, open signal, etc.
#
You can also set the detection of the frequency used exclusively for reverse rotation. This function is
effective for switching the timing of electromagnetic brake operation between forward rotation (rise) and
reverse rotation (fall) during vertical lift operation, etc.
Parameter
Number
Factory
Setting
Setting Range Remarks
42 6Hz 0 to 120Hz
43 9999 0 to 120Hz, 9999
9999: Same as Pr. 42
setting
50 30Hz 0 to 120Hz
<Setting>
Refer to the figure below and set the corresponding parameters:
When Pr. 43
9999, the Pr. 42 setting applies to forward rotation and the Pr. 43 setting applies to reverse
rotation.
Pr.50
Pr.42
Pr.50
Pr.43
Output signal
FU,FU2
Output frequency (Hz)
Forward
rotation
Reverse
rotation
Time
OFF OFF OFFON ON
Output Signal
Parameter Number Output Signal
42
43
FU
50 FU2
Use Pr. 190 to Pr. 195 to assign the terminals used to output the FU2 signals.
Note: 1. When terminal assignment is changed using Pr. 190 to Pr. 195, the other functions may be
affected. Check the functions of the corresponding terminals before making setting.
Pr. 44, Pr. 45
%
%%
%
Refer to Pr. 7.
Pr. 46
%
%%
%
Refer to Pr. 0.
Pr. 47
%
%%
%
Refer to Pr. 3.
Page view 96
1 2 ... 92 93 94 95 96 97 98 99 100 101 102 ... 216 217

Comments to this Manuals

No comments